background image

49

Heatilator  •  RAVE4013I-D  •   2328-900 Rev. F  •  9/17

A.  Wiring Requirements

NOTICE: 

This appliance must be electrically wired 

and grounded in accordance with local codes or, in the 

absence of local codes, with 

National Electric Code 

ANSI/NFPA 70-latest edition

 or the 

Canadian Electric 

Code CSA C22.1.

•  Wire the appliance junction box to 110-120 VAC. This is 

required for use of optional accessories (standing pilot 

ignition) or proper operation of the appliance (IntelliFire 

ignition).

•  A 110-120 VAC circuit for this product must be protected 

with ground-fault circuit-interrupter protection, in 

compliance with the applicable electrical codes, when 

it is installed in locations such as in bathrooms or near 

sinks.

•  Low voltage and 110-120 VAC voltage cannot be shared 

within the same wall box.

WARNING! 

Risk of Shock or Explosion! 

DO NOT

 wire 

110V to the valve or to the appliance wall switch. Incorrect 

wiring will damage controls.

B.  IntelliFire Ignition System Wiring

• Wire the appliance junction box to 110-120 VAC for 

proper operation of the appliance.

WARNING! 

Risk of Shock or Explosion! 

DO NOT

 wire 

IPI controlled appliance junction box to a switched circuit. 

Incorrect wiring will override IPI safety lockout.

•  Refer to Figure 12.2, IntelliFire Pilot Ignition (IPI) Wiring 

Diagram.

•  This appliance is equipped with an IntelliFire control valve 

which operates on a 3 volt system.

Wiring for optional Hearth & Home Technologies approved 

accessories should be done now to avoid reconstruction. 

Follow instructions that come with those accessories.

12 

Electrical Information 

 

Battery Pack Location

Batteries are to be installed only when battery power is 

required.  Because of the limited accessibility to valve 

cavity, the battery pack and IPI control module must be 

installed as shown in Figure 12.1. 

The  battery  pack,  control  module,  and  remote  control 

receiver can be accessed through the air space between 

the  firebox  front  and  the  lower-front  finishing  cover 

panel.  The decorative front and glass assembly must be 

removed to access these components.

The battery pack is attached with velcro to the inside of 

the lower cover panel.  The IPI control module is placed 

on the firebox bottom.  

•  Plug the 3-volt AC transformer into the appliance junction 

box to supply power to the unit OR install two D cell 

batteries  (not  included)  into  the  battery  pack  before 

use.

NOTICE: 

Batteries should not be placed in the battery 

pack  while  using  the  transformer.  Remove  batteries 

before using the transformer, and unplug the transformer 

before installing the batteries. Battery polarity must be 

correct or module damage will occur.

C.  Optional Accessories Requirements

•  This appliance may be used with a wall switch, wall 

mounted thermostat and/or a remote control.

NOTE: Install

 optional remote receiver adjacent to battery 

pack using velcro provided in the appliance.  See Figure 11.5.

GAS VALVE

CONTROL 

MODULE

AC ADAPTER

BATTERY 

PACK

CONTROL MODULE GROUND

Figure 12.1  Valve Cavity

Содержание RAVE4013I-D

Страница 1: ...s only for use with the type s of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used DO NOT store or use gasoline or other flam...

Страница 2: ...e utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if an...

Страница 3: ...stallation Considerations 16 C Tools and Supplies Needed 16 D Inspect Appliance and Components 16 5 Framing and Clearances A Selecting Appliance Location 17 B Constructing the Appliance Chase 18 C Cle...

Страница 4: ...57 14 Appliance Setup A Remove Fixed Glass Assembly 58 B Remove the Shipping Materials 58 C Clean the Appliance 58 D Accessories 58 E Fixed Glass Assembly 59 F Install the Decorative Front 59 G Air S...

Страница 5: ...of original purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authoriz...

Страница 6: ...ONS This warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur Th...

Страница 7: ...s appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in residential heating calculations D High Altitude Installa...

Страница 8: ...eating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector...

Страница 9: ...ntrols out of reach of children Never leave children alone near a hot fireplace whether operating or cooling down Teach children to NEVER touch the fireplace Consider not using the fireplace when chil...

Страница 10: ...ly install one For more information refer to the instructions supplied with your decorative door or front F Remote Controls Wall Controls and Wall Switches Follow the instructions supplied with the co...

Страница 11: ...nt clean See installation and operating instruc tions accompanying appliance Hot while in operation DO NOT touch Keep children clothing furniture gasoline and other liquids having ammable vapors away...

Страница 12: ...hould be cleaned within 3 to 4 hours of initial burning A non abrasive cleaner such as gas appliance glass cleaner may be nec essary See your dealer Metallic noise Noise is caused by metal expanding a...

Страница 13: ...ive you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Fronts Frequency Annually By Homeowner Tools needed Protective gloves stable w...

Страница 14: ...move all foreign objects Verify unobstructed air circulation Burner Ignition and Operation Frequency Annually By Qualified Service Technician Tools needed Protective gloves vacuum cleaner whisk broom...

Страница 15: ...L PENETRATION FRAMING SECTION 8 B VERTICAL TERMINATION CAP SECTION 10 H NON COMBUSTIBLE ROOF FLASHING MAINTAINS MINIMUM CLEARANCE AROUND PIPE SECTION 10 F STORM COLLAR SECTION 10 G VENT PIPE SECTIONS...

Страница 16: ...ce dry C Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplies are available Tape measure Framing material Pliers Non corrosive leak check...

Страница 17: ...Actual installation may vary due to individual design preference 1 IN A E A B C TOP VENT ONE 900 ELBOW ALCOVE INSTALLATION D TOP VENT ONE 90 ELBOW B F Figure 5 1 Appliance Locations A B C D E F Inche...

Страница 18: ...ghtness To further prevent drafts the wall shield and ceiling fire stops should be caulked with caulk with a minimum of 300 F continuous exposure rating to seal gaps Gas line holes and other openings...

Страница 19: ...irspace may cause overheating and a fire C B D A Figure 5 2 Clearances to Combustibles MINIMUM FRAMING DIMENSIONS A B C D E F G H I J Rough Opening Vent Pipe Rough Opening Height Rough Opening Depth R...

Страница 20: ...mension Diagram Figure 16 1 14 IN MIN 12 IN MAX 1 2 IN Thick Wall Sheathing MEASUREMENT FROM TOP OF FIREPLACE OPENING See Dimension T on Appliance Dimension Diagram Figure 16 1 Note For non combustibl...

Страница 21: ...21 Heatilator RAVE4013I D 2328 900 Rev F 9 17 3 1 2 IN 1 IN AIR SPACE NON COMBUSTIBLE BOARD SHIPPED WITH APPLIANCE 1 IN Figure 5 8 Non Combustible Zone...

Страница 22: ...H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 6 Termination Locations Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materi...

Страница 23: ...l Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACT...

Страница 24: ...standards Pipe measurements are shown using the effective length of pipe see Figure 7 3 Measurements are made from the appliance outer wrap not from the standoffs Horizontal terminations are measured...

Страница 25: ...between ceiling firestops ALWAYS maintain specified clearances around venting and firestop systems Install wall shield and ceiling firestops as specified Failure to keep insulation or other material a...

Страница 26: ...90 Elbow 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 6 ft 1 8 m 4 ft 1 2 m 15 ft 4 6 m H1 H2 MAX 15 ft 4 6 m V H1 H2 MAX 40 ft 12 2 m Note There MUST be a 25 reduction in to...

Страница 27: ...ft 3 0 m 2 ft 610 mm 12 ft 3 7 m 3 ft 914 mm 14 ft 4 3 m H1 H2 MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 cannot exceed 40 ft 12 2 m Note T...

Страница 28: ...NG ONLY 3 ft 914 mm 15 ft 4 6 m H1 H2 H3 MAX 15 ft 4 6 m V1 MAX 7 ft 2 1 m V1 H1 H3 H2 INSTALLED HORIZONTALLY INSTALLED HORIZONTALLY Note There MUST be a 25 reduction in total H when using flex vent e...

Страница 29: ...rcing screws to secure vent restric tor to firebox heat shield See Figure 7 10 Exhaust restrictors are recommended for these vertically terminated products which have excessive draft Exhaust restricto...

Страница 30: ...2 V1 V2 Minimum 90 Elbow 2 ft 610 mm 1 ft 152 mm 3 ft 914 mm 2 ft 457 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 1 m 15 ft 4 6 m H MAX 15 ft 4 6 m V1 V2 H MAX 40 ft 12 2 m No specific restrictions on...

Страница 31: ...2 Maximum V2 V1 V2 Minimum 90 Elbow 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 3 ft 914 mm 6 ft 1 8 m 4 ft 1 2 m 14 ft 4 3 m H MAX 14 ft 4 3 m V1 V2 H1 H2 MAX 40 ft 12 2 m No specific...

Страница 32: ...es components only Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation see Figure 17 7 V1 MIN H1 MAX V2 MIN H2 MAX V3 MIN 1 1 2 ft 45...

Страница 33: ...echnologies recommends that NFI or CSIAcertified pro fessionals or technicians under the direction of certified professionals conduct a minimum of a NFPA 211 Level 2 inspection of the chimney Replace...

Страница 34: ...f the DV 46DVA GCL adapter with three self tapping screws TOP VENT WARNING Risk of Fire Explosion or Asphyxiation Do NOT connect this gas appliance to a chimney flue serving a separate solid fuel or g...

Страница 35: ...ge in venting direc tion and in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 7 17 requires only enough support to main...

Страница 36: ...8 2 Wall Penetration Shows center of vent framing hole for top venting The center of the hole is one 1 in 25 4 mm above the center of the horizontal vent pipe Figure 8 1 Horizontal Venting Clearances...

Страница 37: ...rheating Figure 8 3 Installing Ceiling Firestop ATTIC ABOVE A PIPE SLP A 9 in 229 mm A Figure 8 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYST...

Страница 38: ...r two Heat Zone Gas Kits may be installed Only one Heat Zone Plus Kit may be installed See Figure 8 5 Remove the knockouts from the appliance with a tin snips Center the duct collar around the exposed...

Страница 39: ...IPE GASKET Figure 9 2 Elbow Shield Shown Installed If venting with a 90 degree elbow directly off of the top of the appliance the elbow heat shield must be repositioned as shown in Figure 9 2 If not v...

Страница 40: ...abs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing Level the appliance from s...

Страница 41: ...ly fitted and locked into the preceding component Commercial Multi family Multi level exceeding two sto ries or High Rise Applications For Installation into a commercial multi family multi level excee...

Страница 42: ...flue is not required All unit collar pipe slip section elbow and cap outer flues shall be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and sli...

Страница 43: ...on the ceiling and drill a small hole through the ceiling and roof at this point Locate the hole and mark the outline of the cathedral ceiling support box on the outside roof Remove shingles or other...

Страница 44: ...UM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Figure 10 13 Assembling the Storm Collar Around the Pipe NOTICE Failure to properly caulk the roof flashing and pipe seams may permit entry of water Cau...

Страница 45: ...re heat shields must extend through the entire wall thick ness DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 10 16 Heat shields...

Страница 46: ...the cap base Flash and seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z22...

Страница 47: ...essures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig WARNING Note This appliance does include a manual gas shutoff va...

Страница 48: ...ignite Purge should be performed by qualified service technician Ensure adequate ventilation Ensure there are no ignition sources such as sparks or open flames Light the appliance It will take a shor...

Страница 49: ...for optional Hearth Home Technologies approved accessories should be done now to avoid reconstruction Follow instructions that come with those accessories 12 Electrical Information Battery Pack Locat...

Страница 50: ...he junction box heat shield such that it is positioned over the junction box TRANSFORMER 3 VAC PLUG IN BLACK RED BATTERY PACK WIRE ASSEMBLY WIRES TO BROWN ORANGE GREEN VALVE WHITE ORANGE IGNITION MODU...

Страница 51: ...fire Non Combustible Materials Specification Material which will not ignite and burn Such materials are those consisting entirely of steel iron brick tile concrete slate glass or plasters or any comb...

Страница 52: ...to lower cover panel Note Refer to Section 13 C regarding installation details associated with the Inside and Overlap Fit methods Do not drill or install screws which may penetrate the low er cover p...

Страница 53: ...Wallboard and non combustible board should be fastened to the framing with at least 1 1 4 in long screw fasteners located within 1 1 2 in from each corner and at no more than 12 inch intervals along...

Страница 54: ...UM UNLIMITED FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram Figure 16 1 Note For non combustible fireplace finish material marble stone etc specifications refer to Section 13 C 14 IN...

Страница 55: ...thinset and adhesive used to attach the decorative finish material The non combustible finish material can be installed up to the fireplace opening covering the top left and right finishing flanges Se...

Страница 56: ...the decorative front and inside edge of the surrounding finish materials HHT recommends that the front be temporarily installed as a template traced to ensure the finishing materials will fit properl...

Страница 57: ...liance 26 7 16 in 672 mm B Bottom of decorative front to bottom of appliance 6 7 8 in 175 mm C Inside dimension of decorative front width 39 in 991 mm D Outside dimension of decorative front width 44...

Страница 58: ...structions included with accessories Contact your dealer for a list of ap proved accessories WARNING Risk of Fire and Electric Shock Use ONLY Hearth Home Technologies approved optional acces sories wi...

Страница 59: ...the two spring latches that are on the upper left and right of the fireplace 3 Use both index fingers to release spring latches See Figure 14 1 4 Allow glass to tilt forward Grasp glass on the upper r...

Страница 60: ...guration or wiring harness Remove and reinstall the wiring harness that plugs into module Verify there is a tight fit Verify pilot assembly wiring to module Re move and verify continuity of each wire...

Страница 61: ...rifice is installed and gas inlet is set to pressure specifications Polish flame sensing rod with fine steel wool to remove any contaminants that may have accumulated on flame sensing rod c Module is...

Страница 62: ...ons G Q H O F P GAS LINE ACCESS LEFT VIEW FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS A B C D E T U V L N I J K M S R 1 INCH STANDOFF Location Inches Millimeters L 37 3 4 959 M 16 3 4 425 N 6 5 8 168 O 39...

Страница 63: ...mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 SLP FLEX 2 24 610 SLP FLEX 3 36 914 SLP FLEX 5 60 1524 SLP FLEX 10 120 3048 SLP FLEX...

Страница 64: ...SLP CCS BK Cathedral Ceiling Support Box Black 12 1 2 in 318 mm 12 in 305 mm SLP TVHW Vertical Termination Cap 13 in 330 mm 13 in 330 mm 1 5 16 in 34 mm SLP DCF BK Ceiling Firestop Black SLP WT BK Wa...

Страница 65: ...sed on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP...

Страница 66: ...arness PVI WH60 80 ft PV Wire Harness PVI WH80 100 ft PV Wire Harness PVI WH100 12 1 2 IN 318 mm 20 3 4 IN 527 mm 13 5 8 IN 346 mm PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Approved for...

Страница 67: ...4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View PVLP BEK Brick Kit Note Wire har...

Страница 68: ...ter COAXIAL to COLINEAR VENTING Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP...

Страница 69: ...__________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ___...

Отзывы: