background image

480-1091                                                                                                        16                                                                                                              4-03

Constitution

EPA Certified Fireplace

WARNING!

Maintain a minimum of 2” air clearance to all parts of the 

chimney system at all times! 

Failure to maintain this 2” air 

clearance will cause a structure fire.

NOTE: 

You must provide support for the pipe during construction 

and check to be sure inadvertent loading has not dislodged the 

chimney section from the fireplace or at any chimney joint.

WARNING!

When  chimney  sections  exceeding  six  feet  in  length 

are  installed  between  an  offset  and  return, structural 

support  must  be  provided  to  reduce  off-center  loading 

and  prevent  chimney  sections  from  separating  at  the 

chimney joints.

FIRESTOP

JOINT BAND 

(OPTIONAL)

STRAPS

OPTIONAL 

ADDITIONAL 

SUPPORT

Figure 16B - Offset/Return with Stabilizer

10 Securing the Chimney System

When offsets and returns are joined to straight pipe sections, 

they  must  be  locked  into  position  with  the  screws  provided 

(outer  only),  using  the  predrilled  holes. To  prevent  gravity 

from pulling the chimney sections apart, the returns and the 

chimney  stabilizers  have  straps  for  securing  these  parts  to 

joists or rafters. See Figure 16B.

11.Marking the Exit Point of the Roof

Locate  the  point  where  the  chimney  will  exit  the  roof  by 

plumbing down to the center of the chimney. Drive a nail up 

through the roof to mark the center. See Figure 16C.

12.Cutting out the Hole in the Roof

Measure  to  either  side  of  the  nail  7-1/4”  and  mark  the 

14-1/2” x 14-1/2” opening required. This is measured on the 

horizontal; actual length may be larger depending on the pitch 

of the roof. Cut out and frame the opening. See Chapter 25 of 

the 

Uniform Building Code for Roof Framing Details. 

Be sure to maintain a 2” minimum air space between the 

chimney section and the roof.

13.Assembling the Chimney Sections 

Through the Roof

Continue to add chimney sections through the roof opening, 

maintaining at least a 2” air space.

Figure 16C - Ceiling/Attic Construction

9. SL-300 MH842 Celing/Roof Thimble  (Cont’d)

NAIL

FLASHING

PLATE

CHIMNEY

THIMBLE

EXTENSION

SCREW

FLASHING

THIMBLE

ADJUSTABLE 

EXTENSION 

HOLES

Figure 16A - Installing an MH842 Configuration 3

Содержание CONSTITUTION

Страница 1: ...ead entire manual before you install and use your fireplace O T L Tested and Listed by Beaverton Oregon USA OMNI Test Laboratories Inc C Hearth Home Technologies 1915 W Saunders Street Mount Pleasant...

Страница 2: ...hock Also make sure the replace is completely cooled before servicing Installation and Draft Considerations 4 A Listings and Code Approvals 3 B Description of the Fireplace System 3 C Fireplace Dimesi...

Страница 3: ...ey System Chimney Termination Cap Outside Air Kit Hearth Extension Firebrick A LISTINGS AND CODE APPROVALS This fireplace system has been tested and listed in accordance with UL127 and ULC S610 M87 st...

Страница 4: ...ation Location NOT Recommended Cathedral Ceiling Construction 2nd Floor Balcony 1st Floor Multi level Roofs OUTSIDE AIR KIT INSTALLATION NOTE The outside air kit is installed on the right hand side of...

Страница 5: ...tructed of non combustible materials such as cement block or equivalent material Decorative combustible flooring on the raised hearth must be 20 508mm in front of and 8 203mm to either side of the fue...

Страница 6: ...n 36 long SL348 Chimney Section 48 long SL3 Chimney Stabilizer SL315 Chimney Offset Return 15 SL330 Chimney Offset Return 30 FS338 Firestop Straight FS339 Firestop 15 FS340 Firestop 30 AS8 Straight At...

Страница 7: ...irestop Spacer 24 A 8 101 2 Inside Diameter 8 Outside Diameter 101 2 20 3 4 Inside Diameter 8 Outside Diameter 101 2 A B 14 1 2 10 1 2 2 10 1 2 JB877 Joint Band 12 24 5 8 27 3 8 12 31 24 5 8 SL306 6 4...

Страница 8: ...re Termination Cap CT35 Chase Top CAK4A Chimney Air Kit 15 3 4 TR342 TERMINATION CAP TOP OF UPPERMOST CHIMNEY SECTION 14 1 2 MAX DISTANCE CHASE TOP 23 14 3 4 17 3 4 8 Flue 10 1 2 Outer 16 1 2 13 1 4 2...

Страница 9: ...to you when choosing a location for your fireplace This fireplace may be used as a room divider installed along a wall across a corner or used in an exterior chase See Figure 9A Locating the fireplace...

Страница 10: ...exibility in construction The following figures are the minimum distances from the base of the fireplace 2 Framing the Fireplace 1 Min overall straight height 13 ft 2 Min height with offset return 14...

Страница 11: ...ticular chimney parts 5 Whenever the chimney penetrates a floor ceiling a firestop spacer must be installed 6 The effective height of the fireplace assembly is measured from the base of fireplace to t...

Страница 12: ...it passes through the roof See Figure 12A b These chimney heights are necessary in the interest of safety but do not ensure smoke free operation Trees buildings adjoining roof lines adverse wind condi...

Страница 13: ...pproximately 23 x 4 These strips are used to provide added protection where the fireplace and the hearth extension meet Slide each metal strip 2 under the front edge of the fireplace The individual pi...

Страница 14: ...e dimension lumber used in the ceiling joists Install the firestop spacer These firestop spacers are designed to provide the minimum 2 air space required around the chimney In all situations the fires...

Страница 15: ...L 300 MH842 Celing Roof Thimble 1 Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney Lay out cut and frame a 14 1 2 square opening measured on the hori...

Страница 16: ...nt gravity from pulling the chimney sections apart the returns and the chimney stabilizers have straps for securing these parts to joists or rafters See Figure 16B 11 Marking the Exit Point of the Roo...

Страница 17: ...rks The construction of and materials used for a hearth extension are shown in Figures 17A and 17B A hearth extension of this construction may be covered with any noncombustible decorative material an...

Страница 18: ...ustible and must not be used The floor protection specified includes some form of thermal designation such as R value thermal resistance or k factor thermal conductivity PROCEDURE 1 Convert specificat...

Страница 19: ...this metal template is HHT Template 21 Mantel A combustible mantel may be positioned no lower than 60 from base of the fireplace The combustible mantel may have a maximum depth of 12 Combustible trim...

Страница 20: ...rovided with it Storm Collar Chase Flashing 6 min 2 min 2 min Storm Collar Chase Flashing 2 min 14 1 2 max Top of uppermost chimney section 2 Chase Top Construct a chase of desired materials main tain...

Страница 21: ...laced through cracks around windows under doors etc Most newly constructed houses or existing homes fitted with tightly sealed doors and windows are relatively air tight The Constitution Fireplace com...

Страница 22: ...ry important to reload your fireplace while enough lively hot coals remain in order to provide the amount of heat needed to dry and rekindle the next load of wood It is best to open the air control fo...

Страница 23: ...installation and installed in a standard wall mount with junction box on the wall 6 Burning Guidelines The Heat Zone accessory kit conveys warm air from the fireplace through air duct s to remote loca...

Страница 24: ...vapor rise from the fireplace surface this is normal We recommend that you open a window until the odor dissipates and paint is cured NOTE Fireplace should be run full open for a minimum of 15 minute...

Страница 25: ...species of wood you burn the single most important factor that affects the way your fireplace operates is the amount of moisture in the wood The majority of the problems fireplace owners experience a...

Страница 26: ...em These three factors work together as a system to create the flue draft Increasing or decreasing any one of them will affect the other two and thus change the amount of draft in the entire system If...

Страница 27: ...closed container until all embers have thoroughly cooled 1 Creosote and Soot a Formation and need for removal When wood is burned slowly it produces tar and other organic vapors which combine with ex...

Страница 28: ...le attachment knob hang over the edge of the table top so door lays flat on a soft surface 5 Remove the screws from each glass tab 5 on each door using a 2 Phillips Head screwdriver HINT Soak screws i...

Страница 29: ...you have the proper brick in the correct location Measue the brick size for accuracy After the coals are completely cooled remove all old brick and ash from unit and vacuum out firebox 1 Remove new br...

Страница 30: ...replace After Fireplace Installation 1 Remove the firebrick from the bottom of the fireplace 2 Remove the 2 screws from the access panel in the firebox floor 3 Pry up the access panel using the screwd...

Страница 31: ...r channel and out of hole at the other end It is necessary to remove the first tube in order to remove the baffle 5 Slide fiber board baffle forward to front of fireplace and straight out through door...

Страница 32: ...A Certified Fireplace 480 1091 32 4 03 Service Parts Beginning Manufacturing Date 02 17 03 Ending Manufacturing Date __________ Part number list on following page Door Assembly EXPLODED VIEW 1 0 27 1...

Страница 33: ...d SRV480 0510 3 Brick Set BRICK 480 4 Ceramic Blanket 1 cut to fit see drawing on page 32 832 3400 5 Door Handle Assembly includes 2 door handles HANDLES 480 securing bracket lock nut latch cam key an...

Страница 34: ...ace Enclosure 16 17 Locations 9 Firestop Spacer 7 Installation 14 Firewood 25 26 Floor Protection 5 Flue 26 Framing 9 10 Fuel 2 25 26 G General Information 21 Glass Cleaning 28 Glass Replacement 28 Go...

Страница 35: ...ents regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded compone...

Страница 36: ...4 03 36 480 1091 PLEASE RETURN THESE INSTRUCTIONS TO THE HOME OWNER WHEN INSTALLATION IS COMPLETE ATTENTION INSTALLER...

Отзывы: