Heatilator • ECO-WINS18 • 7065-132D • November 22, 2011
42
NOTICE:
•
Construction, clearance and termination must be in com-
pliance with the UMC Table 9C. This installation must also
comply with NFPA 211.
NOTICE:
Top sections of chimney must be removable to allow
maximum clearance of 13.5 feet (411cm) from ground level
for transportation purposes.
1.
An outside air inlet must be provided for combustion and
must remain clear of leaves, debris, ice and/or snow. It
must be unrestricted while unit is in use to prevent room
air starvation which can cause smoke spillage and an
inability to maintain
a fi re. Smoke spillage can also set
off smoke alarms.
2.
Unit must be secured to the mobile home structure.
Remove bolts from each side of insert and use plumbers
tape to secure to structure (a washer may be required).
Re-install bolts.
3.
Unit must be grounded with #8 solid copper grounding
wire or equivalent and terminated at each end with N.E.C.
approved grounding device.
4.
The factory-built fireplace must meet (UM)84-HUD
requirements for outside combustion air supply to the
fi replace fi re chamber and the chimney must be listed to
UL103 HT or a listed UL-1777 full length six inch (152mm)
diameter liner must be used. It must be equipped with a
spark arrestor cap and the outside air must be installed
on the insert (see page 37 for details).
5.
Refer to
page 30
of this manual for clearance to
combustibles and fl oor protections requirements.
All
clearances must be followed precisely.
6.
Use silicone to create an effective vapor barrier at the
location were the chimney or other component penetrates
to the exterior of the structure.
7.
Follow the chimney and chimney connector manufacturer’s
instructions when installing the fl ue system for use in a
mobile home.
8.
Burn wood only. Other types of fuels may generate
poisonous gases (e.g., carbon monoxide).
9.
If unit burns poorly while an exhaust blower is on in home,
(i.e., range hood), increase combustion air.
10. Installation shall be in accordance with the Manufacturers
Home & Safety Standard (HUD) CFR 3280, Part 24.
CAUTION
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-
TAINED
Do NOT cut through:
• Floor joist, wall studs, or ceiling trusses.
•
Any supporting material that would affect the structural
integrity.
•
NEVER INSTALL IN A SLEEPING ROOM.
Consumes oxygen in the room.
WARNING
Asphyxiation Risk.
WARNING
Do not draw outside combustion air from:
• Wall, fl oor or ceiling cavity
• Enclosed space such as an attic or garage
• Close proximity to exhaust vents or
chimneys.
Fumes or odor may result
Fire Risk.
Asphyxiation Risk.
10
Mobile Home Installation
11