background image

8  

 

 

 

 

Part # 25000102

In systems equipped with capacity control compressors, 

or where multiple compressors are used with one or more 

compressors cycled off for capacity control, double suction 

risers should be installed. See Figure 6 below. The two 

lines should be sized so that the total cross-section area 

is equivalent to the cross section area of a single riser that 

would have both satisfactory gas velocity and acceptable 

pressure drop at maximum load conditions. The two lines 

normally are different in size, with the larger line trapped as 

shown. The smaller line must be sized to provide adequate 

velocities and acceptable pressure drop when the entire 

minimum load is carried in the smaller riser.

In  operation,  at  maximum  load  conditions  gas  and 

entrained  oil  will  be  flowing  through  both  risers.  At 

minimum load conditions, the gas velocity will not be 

high enough to carry oil up both risers. The entrained oil 

will drop out of the refrigerant gas flow and accumulate 

in the “P” trap forming a liquid seal. This will force all of the 

flow up the smaller riser, there by raising the velocity and 

assuring oil circulation through the system.
When connecting more than one suction line to a main 

trunk line, connect each branch line with an inverted trap. 

See Figure 7 below:

Straight runs should be supported near each end.
Long runs require additional supports.
A general guide is:

3/8” to 7/8” every 5 feet
1-1/8” to 1-3/8” every 7 feet
1-5/8” to 2-1/8” every 10 feet

When changing directions, supports should be placed a 

maximum of 2 feet in each direction.
Piping attached to a vibrating object (such as a compressor 

or compressor base) must be supported in such a manner 

that will not restrict the movement of the vibrating object. 

Rigid mounting will fatigue the copper tubing.
Use only a suitable silver solder alloy on suction and liquid 

lines.
Limit the soldering paste or flux to the minimum required 

to prevent contamination of the solder joint internally. Flux 

only the male portion of the connection, never the female. 

After brazing, remove excess flux.





Installation and Operations Manual

When  brazing  refrigerant  lines,  an  inert  gas  should 

be passed through the line at low pressure to prevent 

scaling and oxidation inside the tubing. Dry nitrogen is 

preferred.
Use long radius ell’s for lower pressure drop.
Provide  expansion  loops  in  long  straight  refrigerant 

lines that are subject to expansion and contraction. See 

Expansion Loops in this manual for more information.

Refrigerant Line Insulation

Insulate suction lines from the evaporators to the parallel 

unit  with  minimum  3/4”  thickness  closed-cell  type 

insulation on low temperature circuits. Insulate suction 

lines on medium temperature circuits with minimum 1/2” 

thick insulation to prevent condensation.
Long liquid lines run in areas exposed to high temperatures 

should be fully insulated with minimum 1/2” insulation.
Suction  and  liquid  lines  should  never  be  taped  or       

soldered together.

Refrigerant Line Support

Strap  and  support  tubing  to  prevent  excessive  line 

vibration and noise. All tubing clamps should have an 

insulating material (i.e. Hydra Sorb bushing) to prevent 

metal to metal contact.


Figure 6. Double Suction Risers

Figure 7. Inverted Trap

Figure 8. Pipe Support

Содержание H-IM-PCS

Страница 1: ...Parallel Compressor Systems Bulletin No H IM PCS October 2004 Part Number 25000102 Replaces H IM 72B October 2004 Installation and Operation Manual...

Страница 2: ...peland Lubricants Carlyle Compressors Approved Carlyle Lubricants Oil Pressure Table 13 O6D E Oil Pressure History Table 14 Oil Safety Switch 22 Table 15 Part Load Performance Multipliers Table 16 Req...

Страница 3: ...tive and the carrier of the damage immediately Request an immediate joint inspection with the carrier Do not repair the unit until inspected by carrier s representative Care should be exercised when u...

Страница 4: ...es at the rear and 42 inches in the front of panel or as required by National or Local Codes For parallel system units placed end to end 24 inches between units is suggested Floor Foundation Requireme...

Страница 5: ...e ground level provides some protection from ground water and wind blown matter The concrete slab should be isolated from the building structure Finally before tightening mounting bolts recheck the le...

Страница 6: ...whenever possible Care should be taken to see that ample room is left for maintenance work through access doors and panels When the unit is in an area where it is enclosed by three walls the unit mus...

Страница 7: ...ment Before starting up a parallel unit insure that all fuses and motor protective devices are in place and that all wiring is secure A complete wiring diagram for troubleshooting the unit will be fou...

Страница 8: ...ed a maximum of 2 feet in each direction Pipingattachedtoavibratingobject suchasacompressor or compressor base must be supported in such a manner that will not restrict the movement of the vibrating o...

Страница 9: ...ially on hot gas lines to prevent line breakage This is critical on long straight runs of generally 70 or more where expansion loops must be provided and hangers should allow for longitudinal movement...

Страница 10: ...04A R 507 4 1 1 1 6 1 1 6 8 2 2 1 10 2 2 7 12 2 3 3 16 3 4 1 20 4 5 6 30 6 8 3 40 8 11 8 Table 2 Pressure Loss of Liquid Refrigerants In Liquid Line Risers Expressed in Pressure Drop PSIG and Subcooli...

Страница 11: ...2 57 3 50 4 98 14 27 40 26 42 58 40 64 95 61 93 1 32 1 91 1 33 1 87 1 5 8 12 134A 22 R 507 502 404A 90 9 90 0 78 0 3 65 4 96 7 07 20 37 56 37 59 82 57 90 1 35 87 1 33 1 86 1 30 1 88 2 64 2 1 8 12 134...

Страница 12: ...8 2 1 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 1 5 8 1 5 8 1 5 8 84 000 1 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8...

Страница 13: ...8 5 8 5 8 72 000 1 5 8 2 1 8 2 1 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 5 8 5 8 5 8 5 8 5 8 7 8 78 000 2 1 8 2 1 8 2 1 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 1 5 8 1...

Страница 14: ...1 5 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 84 000 1 1 8 1 1 8 1 3 8 1 3 8 1 3 8 1 5 8 1 1 8 1 3 8 1 3 8 1 3 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 1 3 8 1 5 8 1 5 8...

Страница 15: ...5 8 5 8 72 000 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 1 2 1 2 5 8 5 8 5 8 7 8 78 000 1 5 8 2 1 8 2 1 8 1 3 8 1 5 8 1 5 8 2 1 8 2 1 8 2 1 8 1 3 8 1 5...

Страница 16: ...1 8 1 3 8 1 1 8 1 1 8 180 000 50 100 1 5 8 2 1 8 1 3 8 1 3 8 1 3 8 1 3 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 1 3 8 1 5 8 1 3 8 1 3 8 240 000 50 100 1 5 8 2 1 8 1 5 8 1 5 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5...

Страница 17: ...e pull down The wiring diagramfortheunitwillhavetobeconsultedtodetermine how to best force the fans to operate for this step 4 With all compressor and control breakers and toggle switches turned off a...

Страница 18: ...eturned into the liquid manifold the Priority I design returns the liquid to the condenser through a liquid drain manifold Hot discharge gas is injected into the suction line at the parallel rack and...

Страница 19: ...igerant being returned to the compressor This will cause dilution of the oil and eventual failure of the bearings and piston rings In extreme cases the compressor will fail as a result of the diluted...

Страница 20: ...est The compressors are solid mounted to a base frame or mounted on the refrigerant receiver All reciprocating compressors incorporate oil floats Crankcase heaters will be installed and wired Cylinder...

Страница 21: ...1 24 to 1 8 18 to 34 1 24 to 2 3 Carlyle Compressors Approved Carlyle Lubricants For CFC and HCFC Refrigerants Use Totaline 150 Suniso 3GS Shrieve Zerol 150 Texaco WFI 32 150 IGI Petroleum Cryol 150...

Страница 22: ...eactivated after a specified trip delay The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time Restart Delay The trip delay prevents nuis...

Страница 23: ...Vessel is exposed to excessive heat When a Vessel containing liquid refrigerant is shut off from otherpartsofthesystemariseintemperaturewillcausearisein pressure If theVessel is completely filled wit...

Страница 24: ...let 350 400 425 450 Angle 526E 3 8 MPT 3 8 FLARE 10 2 11 6 12 3 13 0 527E 1 2 MPT 5 8 FLARE 28 5 32 4 34 4 36 3 Straight Through 5231 3 8 MPT 3 8 FLARE 11 2 12 7 13 5 14 3 5231 A 3 8 MPT 1 2 FLARE 18...

Страница 25: ...cannot be reset until the pressure drops to a predetermined level The latching mechanism inside the manual reset model is trip free The electrical contacts will cutout even if the reset button is hel...

Страница 26: ...d to insure the system will work properly Low Pressure Oil System This type system is normally used for parallel compressors and uses three basic components Oil Separator Oil Reservoir and Oil Level R...

Страница 27: ...pressure expansion valve with a range of 0 to 90 psig Temprite Part No is 67070000 An alternative valve manufactured by Sporlan is Model ADRI 11 4 0 90 Oil Level Regulators The AC R adjustable oil re...

Страница 28: ...n the motor cavity on semi hermetic models the compressor will overfill The oil line sight glass is a good way to see how the separator is working Look for movement in the glass If the separator is no...

Страница 29: ...strainers and filter driers 3 Install a replacement compressor and make a complete electrical check 4 Make sure the suction line adjacent to the compressor is clean Install a liquid line filter drier...

Страница 30: ...r pressure The regulator closes as the condenser pressure drops below the set point thus back flooding the condenser and reducing the inside surface area available for condensing Valve B is and Outlet...

Страница 31: ...utdoor temperature to allow the system pressures to drop below the regulator pressure settings Before adjusting make sure that all manual opening stems on the regulators are set for automatic operatio...

Страница 32: ...0psig withonecompleteturnequal toapproximately4psichange Adjustmentsshouldbemade insmallincrements allowingforthesystemtostabilizeafter each turn 6 Vary the evaporator load to test at various conditio...

Страница 33: ...connections Checkoperationandconditionofcontactsoncompressor fan motor contactors Check appearance of control panel interior Check appearance of exterior conduit junction boxes Check appearance of ins...

Страница 34: ...tor Check stator If leads are all right replace stator Eliminate cause of excessive pressure Check oil level Correct binding Unit Operates Long Or Continuously 1 2 3 4 5 6 Control contacts sticking in...

Страница 35: ...ters Check and reset for proper superheat Check means for regulating condensing temperature Check for proper sizing Little or No Oil Pressure 1 2 3 4 5 6 7 8 9 Clogged suction oil strainer Excessive l...

Страница 36: ..._ Group __________________ Group _________________ Compressor Model Serial No __________________ __________________ Group __________________ Compressor Model Serial No __________________ _____________...

Отзывы: