HEAT & GLO • PHOENIX42-IFT Installation Manual • 4096-901 Rev. A
• 02/18
36
10
Finishing
A. Facing Material
• Metal front faces may be covered with non-
combustible materials only.
•
Appliance may be recessed a maximum of 12 inches into
non-combustible framing/finishing matrials above and
on the sides of the appliance.
•
Facing and/or finishing materials must not interfere with
air flow through the front of the appliance, access for
service or the operation of optional mesh doors.
•
Facing and/or finishing materials must never overhang
into the appliance opening.
•
See Section 10.C for combustible and non-combustible
finishing material thickness requirements.
•
Observe all clearances when applying combustible
materials.
•
Seal joints between the finished wall and appliance
top and sides using a 300º F minimum sealant. Refer
to Figure 10.1.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specified in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
NOTICE: Surface temperatures around the appliance will
become warm while the appliance is in operation. Ensure
finishing materials used for all surfaces (floor, walls,
mantels, etc.) will withstand temperatures up to 190
°
F.
B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specified. Framing closer than the minimums list-
ed must be constructed entirely of non-combustible materi-
als (i.e., steel studs, concrete board, etc.).
Combustible Mantels
Figure 10.3 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Combustible or Non-Combustible Mantel Legs or
Wall Projections
Figure 10.2 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Note:
Mantel Measurement is taken from top of
the opening, NOT the top of the fireplace.
May be recessed a maximum of 12 inches into non-
combustible framing/finishing materials, above and
on the sides of the appliance. A maximum combus
-
tible projection of 12 inches is allowed. Metal front
faces may be covered with non-combustible materi-
als only.
30 in.minimum
clearance to ceiling
H
V
Measured from
top of opening
Side View
of
Appliance
H Max.
V Min.
Inches
mm
Inches
mm
12
305
12
305
13
330
13
330
14
356
14
356
15
381
15
381
16
406
16
406
17
432
17
432
18
457
18
457
A
B
Mantel Leg or Perpendicular Wall
Top View of
Appliance
Drywall
A
B
1 in. (25 mm) min. to
perpendicular wall
5-1/8 in. (130 mm) min. from
fireplace opening to
perpendicular wall
0 in.
0 in.
0 in.
High Temperature Sealant (300º F/149º C min.)
Top and Seal Joint
Figure 10.1 High Temperature Sealant