26
Heat & Glo • 6000BEC-IPI, 6000BEC-IPILP • 2187-900 Rev. K • 4/15
H
1
V
1
V
2
Top Vent - Vertical Termination (continued)
Figure 7.10
Two Elbows
Figure 7.9 Setting the Flue Restrictor
Note
: If the DVP-2SL or DVP-SLP24 adapter is used with
SLP pipe, you MUST subtract one number from the table
in Figure 7.8.
Example:
Top vent 40 ft vertical with DVP pipe = 5-4
Top vent 40 ft vertical with SLP pipe = 4-3
V
1
H
1
Maximum
V
2
V
1
+ V
2
Min.
Elbow only
2 ft.
610 mm
*
*
*
6 in.
152 mm
6 ft.
1.8 m
*
*
*
2 ft.
610 mm
11 ft.
3.4 m
*
*
*
3 ft.
914 mm
16 ft.
4.9 m
*
*
*
4 ft.
1.2 m
20 ft
6.1 m
*
*
*
V
1
+ V
2
+ H
1
= 50 ft (15.2 m) Maximum
*No speci
fi
c restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 50 ft (15.2 m)
1 2 3 4 5
5 4 3 2 1
ALWAYS USED WITH THE
HOLES TO THE LEFT
ALWAYS USED WITH THE
HOLES TO THE RIGHT
FLUE RESTRICTOR SET TO 4-4
4 5
5 4 3 2 1