23
Heat & Glo • 6000BEC-IPI, 6000BEC-IPILP • 2187-900 Rev. K • 4/15
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
H
1
V
1
Figure 7.3
Figure 7.4
Top Vent - Horizontal Termination
Top Vent - Horizontal Termination
One Elbow
Two Elbows
Note:
For corner installations: A 6 inch (152
mm) section of straight pipe may need to
be attached to the appliance before a 90º
elbow, to allow the vent pipe to clear the top
standoffs.
Note:
For corner installations: A 6 inch
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º
elbow, to allow the vent
pipe to clear the top standoffs.
V
1
Minimum
H
1
Maximum
Elbow only
2 ft
610 mm
1 ft.
305 mm
3 ft.
914 mm
2 ft.
610 mm
6 ft.
1.8 m
3 ft.
914 mm
11 ft.
3.4 m
4 ft.
1.2 m
20 ft.
6.1 m
V
1
+ H
1
= 40 ft. (12.2 m) Maximum
H
1
= 20 ft. (6.1 m) Maximum
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling
fi
restops.
• ALWAYS maintain speci
fi
ed clearances around
venting and
fi
restop systems.
• Install wall shield and ceiling
fi
restops as speci-
fi
ed.
Failure to keep insulation or other material away
from vent pipe may cause
fi
re.
Note: The 6000 series fireplaces can adapt to SLP series vent pipe,
if desired.
When venting off the top of the unit, use a DVP-2SL adapter and a
minimum 48 inch vertical section of SLP series vent pipe.
A DVP-SLP24 adapter may also be used with a 24 inch vertical
section of SLP series vent pipe.
After
the 48 inch vertical section, the venting table rules must be
followed. The
fi
rst 48 inch
vertical
section is NOT counted as part
of the vertical components in the table. It is still counted as part of
the overall maximum run. All venting table rules for the vent run
must still be followed.
Example:
DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal
SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal
V
1
Minimum
H
1
+ H
2
Maximum
Elbow only
1 ft.
305 mm
6 in.
152 mm
2 ft.
610 mm
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
4 ft.
1.2 m
3 ft.
914 mm
9 ft.
2.7 m
4 ft.
1.2 m
18 ft.
5.5 m
5 ft.
1.5 m
20 ft.
6.1 m
V
1
+ H
1
+ H
2
= 40 ft. (12.2 m) Maximum
H
1
+ H
2
= 20 ft. (6.1 m) Maximum
Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZC-
SS termination caps on top vented
fi
replaces, a
6 inch minimum vertical vent section is required
before installing
fi
rst elbow.
WARNING
WARNING
E. Vent Diagrams