10
Installing the
Fireplace
Step 1
Locating the
Fireplace
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
A
B
C
D
E
SL-550TR-CE 94.0
41.3
72.8
102.9
145.7
NOTE: DIMENSIONS SHOWN IN CM.
NOTE: DIMENSIONS ARE SHOWN WITH THE SIDES, BACK
AND/OR CORNERS OF THE UNIT TOUCHING THE WALL.
*
Figure 2. Fireplace Dimensions, Locations, and
Space Requirements
MODEL
RECESSED DEPTH
SL-550TR-CE -C
41.3cm
The minimum clearance to a perpendicular wall extending past the face of the
fireplace is 7.62cm.
The back of the fireplaces may be recessed into combustible construction, as
shown below.
Minimum Clearances from the Fireplace to
Combustible Materials
Glass Back of Sides of Top of
Front Floor Fireplace Fireplace Fireplace
Ceiling
91.4 cm 0 1.3cm 1.3cm
3.8cm
78.7cm
Clearance Requirements
The top and back of the fireplace are defined by stand-offs.
1.3cm
C
7.6cm
A
B
D
E