29
!
CEILING
CEILING FIRESTOP
RAFTER
NAILS (4 REQUIRED)
If the area above the ceiling
IS
an attic, position and
secure the firestop on top of the previously framed
hole.
This shows an attic
installation.
1. Keep insulation away
from the flue pipe at
least 25 mm.
Figure 23. Attic Firestop
C. Flue Termination
For Horizontal Terminations -
To attach and secure
the termination to the last section of horizontal flue:
• Rotate and interlock the ends as described at the
beginning of the Installing Flue Components sec-
tion.
• The termination kit should pass through the wall
firestops from the exterior of the building.
• Adjust the termination cap to its final exterior posi-
tion on the building.
WARNING:
THE TERMINATION CAP MUST BE
POSITIONED SO THAT THE ARROW IS
POINTING UP.
For roundcap termination kits:
• Use the exterior pipelock hole provided on the round
flange of the wall firestop to secure the flue pipe in
place.
For trapezoidal cap termination kits:
• Using screws, secure the cap to the exterior wall
through the flanges built into the cap.
• Use a high-temperature sealant or fiberglass rope
gasket to seal between the flue pipe and exterior
firestop.