Heat-N-Glo Grand-50-D Скачать руководство пользователя страница 16

18

u

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

______________________________________________________________________

V

= VENT  TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

     Figure 20.  Vent Termination Minimum Clearances

A

= 12" ....................... clearances above grade, veran-

da, porch, deck or balcony

B

= 12" ....................... clearances to window or door

that may be opened, or to per-
manently closed window.

D*

= 36" ....................... vertical clearance to ventilated

soffit located above the terminal
within a horizontal distance of 2
feet (60 cm) from the center-line
of the terminal

E*

= 36" ....................... clearance to unventilated soffit

F

=  9" ......................... clearance to outside corner

G

= 6" .......................... clearance to inside corner

H

= 3 ft. (Canada) ...... not to be installed above a gas

meter/regulator assembly within
3 feet (90cm) horizontally from the
center-line of the regulator

I

= 3 ft. (U.S.A.)

6 ft. (Canada) ....... clearance to service regulator

vent outlet and electric service

J

= 9" (U.S.A.)

12" (Canada) ......... clearance to non-mechani-

cal air supply inlet to build-
ing or the combustion air in-
let to any other appliance

K

= 3 ft. (U.S.A.)

6 ft. (Canada) ......... clearance to a mechanical

air supply inlet

L** = 7 ft. ......................... clearance above paved

sidewalk or a paved driveway
located on 

public

 property

M*** = 36" ......................... clearance under veranda,

porch, deck or balcony

N

= 6” ........................... non-vinyl soffit and siding

12” ......................... vinyl soffit and siding

O

= 18” ......................... non-vinyl soffit and siding

42” ......................... vinyl soffit and siding

P

= 8 ft.

D

E

B

L

v

v

v

v

v

v

v

v

B

B

A

H

M

X

J or K

I

A

G

F

U.S.

(3 FT)

B

CAUTION: 

IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR

KIT TO THE TOP OF THE EXTERIOR FIRESTOP (FOR ALL ROUND TERMINATION CAPS). IT IS STRONGLY RECOMMENDED
WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT.

 5 foot minimum for vinyl clad soffits.

  ** a vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings
and serves both dwellings.

 *** only permitted if veranda, porch, deck or balcony is fully open on

a minimum of 2 sides beneath the floor.

NOTE 1

: On private property where termination is less than 7 feet

above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested.

NOTE 2

: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 

1

. There must be 3 feet minimum

between termination caps. 

2. 

 All mechanical air intakes within 10 feet

of a termination cap must be a minimum of 3 feet below the termination
cap. 

3.

 All gravity air intakes within 3 feet of a termination cap must be

a minimum of 1 foot below the termination cap.

O

N

P

R

Q

(See Note 1)

(See Note 1)

(See Note 2)

NOTE 3

: Local codes or regulations may require different

clearances.

NOTE 4: 

Termination caps may be hot. Consider their proximity to

doors or other traffic areas.

WARNING: In the U.S:

 Vent system termination is 

NOT

 permitted

in screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.

In Canada:

 Vent system termination is 

NOT

 permitted in screened

porches. Vent system termination is permitted in porch areas
with two or more sides open. You must follow all side walls,
overhang and ground clearances as stated in the instructions.

Heat-N-Glo assumes no responsibility for the improper perfor-
mance of the fireplace when the venting system does not meet
these requirements.

    

Q

MIN

     R

MAX

  1 cap

  3 feet

   2 x Q 

ACTUAL

  2 caps

  6 feet

   1 x Q 

ACTUAL

  3 caps

  9 feet

2/3 x Q 

ACTUAL

  4 caps

12 feet

1/2 x Q 

ACTUAL

Q

MIN

 = # termination caps x 3        R

MAX

 = (2 / # termination caps) x Q

ACTUAL

Содержание Grand-50-D

Страница 1: ...IANCE FOR FUTURE REFERENCE Please contact your Heat N Glo dealer with any questionsorconcerns Forthenumberofyournearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2002 Hea...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...Approvals 11 B Installing Vent Components 15 C Vent Termination 17 Step 4 Positioning Leveling and Securing the Fireplace 20 Step 5 The Gas Control Systems 20 Step 6 The Gas Supply Line 21 Step 7 Gas...

Страница 4: ...22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada Approvals and Codes High Altitude Installations U L Listed gas fireplaces a...

Страница 5: ...ilure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following...

Страница 6: ...AL ACCESS VENT COLLARS 34 864mm 17 432mm 25 1 8 638mm 16 5 8 421mm 47 1 4 1200mm 44 1 8 1121mm 50 5 8 1286mm 56 1 2 1435mm 7 1 8 181mm 2 3 4 70mm GAS LINE ACCESS HOOD TOP STANDOFFS ELECTRICAL ACCESS G...

Страница 7: ...inimum clearances of direct vent termination see Fig ures 19 and 20 Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be position...

Страница 8: ...AP 1 3 8 INCHES 34 93 mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Страница 9: ...erappearancemayvarybasedonthetype of fuel burned and the venting configuration used Termination Kits WARNING A 3 FOOT LENGTH OF STRAIGHT PIPE MINIMUM MUST BE THE FIRST VENT COMPONENT ATTACHED TO THE U...

Страница 10: ...WITH ONE 1 90 ELBOW V FT H FT 3 MIN 914 mm 6 MAX 1 9m 4 MIN 1 2m 8 MAX 2 4m 5 MIN 1 6m 10 MAX 3 1m 6 MIN 1 9m 12 MAX 3 6m V H 30 MAX 9 3 m Ratio V to H 1 2 Figure 7 Venting with One 90 Elbow H 20 MAX...

Страница 11: ...io V to H H1 1 2 Figure 8 Venting with two 90 elbows VENTING WITH TWO 2 90 ELBOWS V FT H FT 3 MIN 914 mm 6 MAX 1 9m 4 MIN 1 2m 8 MAX 2 4m 5 MIN 1 6m 10 MAX 3 1m 6 MIN 1 9m 12 MAX 3 6m V V1 H1 30 MAX 9...

Страница 12: ...MAXIMUM 9 3m H H1 20 MAXIMUM 6 2m H 10 MAXIMUM 3 1m VENTING WITH THREE 3 90 ELBOWS V FT H H1 FT 3 MINIMUM 914 mm 6 MAXIMUM 1 9 m 4 MINIMUM 1 2 m 8 MAXIMUM 2 4 m 5 MINIMUM 1 6 m 10 MAXIMUM 3 1 m 6 MIN...

Страница 13: ...locked position with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 11 Adding Venting Components 3 Install Support Brackets For Horizontal Runs The vent system must...

Страница 14: ...G NEW FRAMING MEMBERS EXISTING CEILING JOISTS CHIMNEY HOLE 11 280 mm 11 280mm For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes To install fi...

Страница 15: ...LEARANCES Figure 19 Round Trapezoid Termination Caps ROUND CAP TERMINATION PERFORATION CANNOT BE INSIDE THE WALL 7 1 2 191mm MINIMUM TRAPEZOID CAP TERMINATION 7 1 4 184mm Figure 17 Ceiling Firestop Ce...

Страница 16: ...PS IT IS STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 5 foot minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is loc...

Страница 17: ...OVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALLAND 2 FEET BELOW AHORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of the building...

Страница 18: ...gure 23 Proper Positioning Leveling and Securing of a Fireplace Figure 24 Gas Control System Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Intermittent Pilot Ignition...

Страница 19: ...ied installer approved and or licensed as required by the locality In the state of Massachusetts installation must be performed by a licensed plumber or gas fitter NOTE Before the first firing of the...

Страница 20: ...y cutting and removing cable tie Plug transformer into electric box terminal marked fan Check that antenna wire is held in place by two clips on the lower flange see Figure 35 Optional Fan Kits Fan ki...

Страница 21: ...SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE PLACE SURROUND SEE...

Страница 22: ...the top of the burner near front and center ports with a single layer of ember material Sprinkle GE 93 on top of the burner Save the remaining ember materials for use during fire place servicing Use o...

Страница 23: ...sembly GLASS CLIPS Step 11 Before Lighting the Fireplace BEFORE lighting the fireplace be sure to do the following Remove all paperwork from underneath the fireplace Review all cautions and Safety and...

Страница 24: ...eceiver can then be slid out and turned over without disconnecting wiring 6 Remove cover from receiver by removing 4 Phillips head screws 7 Locate code switches in receiver Slide the numbered switches...

Страница 25: ...surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the fl...

Отзывы: