Heat-N-Glo Grand-50-D Скачать руководство пользователя страница 13

15

!

B.  Installing Vent Components

!

STARTING

COLLAR

STOVE

SEALANT

BEAD

1 INCH

(25.4mm)

 FIRST VENT

COMPONENT

1.  Attach the First Vent Component to the
     Starting Collars

To attach the first vent component (3 foot straight pipe
minimum) to the starting collars of the fireplace:

• Apply a 3/8 inch (9.5mm) bead of stove cement around

the inner pipe fireplace starting collar.

• Make sure that the fireplace rope gasket supplied with

the fireplace seals between the first 8-5/8 inch (219mm)
vent component and the fireplace top.

• Lock the vent components into place by sliding the con-

centric pipe sections with four (4) equally spaced interior
beads into the fireplace collar or previously installed com-
ponent end with four (4) equally spaced indented sections.

• When the internal beads of each pipe line up, rotate the

pipe section clockwise about one-quarter (1/4) turn. The
vent pipe is now locked together.

3/8” (9.5mm)

2. Continue Adding Vent Components

• Continue adding vent components, locking each succeed-

ing component into place.

• Ensure that each succeeding vent component is secure-

ly fitted and locked into the preceding component in the
vent system.

• 90° elbows may be installed and rotated to any point

around the preceding component’s vertical axis. If an el-
bow does not end up in a locked position with the pre-
ceding component, attach with a minimum of two (2)
sheet metal screws.

Figure 11.  Adding Venting Components

3.  Install Support Brackets

For Horizontal Runs - 

The vent system must be supported

every five (5) feet of horizontal run by a horizontal pipe support.

To install support brackets for horizontal runs:

•  Place the pipe supports around the vent pipe.

•  Nail the pipe supports to the framing members.

For Vertical Runs -

 The vent system must be supported

every eight (8) feet (2.4m) above the fireplace flue outlet by
wall brackets.

To install support brackets for vertical runs:

• Attach wall brackets to the vent pipe and secure the wall

bracket to the framing members with nails or screws.

  Figure 10.  Attaching the First Vent Component
                   to the Starting Collars

WARNING: A 3/8 INCH (9.5MM) BEAD OF STOVE
CEMENT MUST BE PLACED AROUND THE INNER

PIPE FIREPLACE STARTING COLLAR BEFORE AT-
TACHING THE FIRST VENT COMPONENT. FAILURE TO
SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO
OPERATE IMPROPERLY. SEE THE DIAGRAM .

WARNING: ENSURE THAT THE FIBERGLASS
ROPE GASKET SUPPLIED WITH THE FIRE-

PLACE SEALS BETWEEN THE FIRST VENT COM-
PONENT AND THE FIREPLACE TOP.

!

WARNING: MODEL GRAND-50-D REQUIRES
SHIELD SRV570-290 ABOVE THE FIRST 90°

ELBOW IN THE SYSTEM IF CLEARANCE IS LESS
THAN 4 INCHES (102MM). SEE INSTALLATION SHEET
AND HEAT SHIELD SUPPLIED WITH FIREPLACE.

Figure 12.  Placement of SRV570-290 Heat Shield
                 First 90

0

 elbow in system.

3’ MIN.

 (914mm)

Heat Shield

Combustible

Surface

3” MIN.
(76mm)

Содержание Grand-50-D

Страница 1: ...IANCE FOR FUTURE REFERENCE Please contact your Heat N Glo dealer with any questionsorconcerns Forthenumberofyournearest Heat N Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2002 Hea...

Страница 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Страница 3: ...Approvals 11 B Installing Vent Components 15 C Vent Termination 17 Step 4 Positioning Leveling and Securing the Fireplace 20 Step 5 The Gas Control Systems 20 Step 6 The Gas Supply Line 21 Step 7 Gas...

Страница 4: ...22 1 Canadian Electric Code in Canada These models may be installed in a bedroom or bed sitting room in the U S A and Canada Approvals and Codes High Altitude Installations U L Listed gas fireplaces a...

Страница 5: ...ilure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following...

Страница 6: ...AL ACCESS VENT COLLARS 34 864mm 17 432mm 25 1 8 638mm 16 5 8 421mm 47 1 4 1200mm 44 1 8 1121mm 50 5 8 1286mm 56 1 2 1435mm 7 1 8 181mm 2 3 4 70mm GAS LINE ACCESS HOOD TOP STANDOFFS ELECTRICAL ACCESS G...

Страница 7: ...inimum clearances of direct vent termination see Fig ures 19 and 20 Step 2 Framing the Fireplace Fireplace framing can be built before or after the fireplace is set in place Framing should be position...

Страница 8: ...AP 1 3 8 INCHES 34 93 mm AT EACH JOINT DV 36D 5 3 4 146mm 8 3 4 222mm 11 3 4 298mm DV 12D DV 09D DV 06D DV 48D DV 90D 7 3 8 187mm 6 5 32 156mm 11 5 8 295mm 11 15 16 303mm 5 7 8 149mm 8 5 8 220mm 8 1 2...

Страница 9: ...erappearancemayvarybasedonthetype of fuel burned and the venting configuration used Termination Kits WARNING A 3 FOOT LENGTH OF STRAIGHT PIPE MINIMUM MUST BE THE FIRST VENT COMPONENT ATTACHED TO THE U...

Страница 10: ...WITH ONE 1 90 ELBOW V FT H FT 3 MIN 914 mm 6 MAX 1 9m 4 MIN 1 2m 8 MAX 2 4m 5 MIN 1 6m 10 MAX 3 1m 6 MIN 1 9m 12 MAX 3 6m V H 30 MAX 9 3 m Ratio V to H 1 2 Figure 7 Venting with One 90 Elbow H 20 MAX...

Страница 11: ...io V to H H1 1 2 Figure 8 Venting with two 90 elbows VENTING WITH TWO 2 90 ELBOWS V FT H FT 3 MIN 914 mm 6 MAX 1 9m 4 MIN 1 2m 8 MAX 2 4m 5 MIN 1 6m 10 MAX 3 1m 6 MIN 1 9m 12 MAX 3 6m V V1 H1 30 MAX 9...

Страница 12: ...MAXIMUM 9 3m H H1 20 MAXIMUM 6 2m H 10 MAXIMUM 3 1m VENTING WITH THREE 3 90 ELBOWS V FT H H1 FT 3 MINIMUM 914 mm 6 MAXIMUM 1 9 m 4 MINIMUM 1 2 m 8 MAXIMUM 2 4 m 5 MINIMUM 1 6 m 10 MAXIMUM 3 1 m 6 MIN...

Страница 13: ...locked position with the pre ceding component attach with a minimum of two 2 sheet metal screws Figure 11 Adding Venting Components 3 Install Support Brackets For Horizontal Runs The vent system must...

Страница 14: ...G NEW FRAMING MEMBERS EXISTING CEILING JOISTS CHIMNEY HOLE 11 280 mm 11 280mm For Vertical Runs One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes To install fi...

Страница 15: ...LEARANCES Figure 19 Round Trapezoid Termination Caps ROUND CAP TERMINATION PERFORATION CANNOT BE INSIDE THE WALL 7 1 2 191mm MINIMUM TRAPEZOID CAP TERMINATION 7 1 4 184mm Figure 17 Ceiling Firestop Ce...

Страница 16: ...PS IT IS STRONGLY RECOMMENDED WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT 5 foot minimum for vinyl clad soffits a vent shall not terminate directly above a sidewalk or paved driveway which is loc...

Страница 17: ...OVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICAL WALLAND 2 FEET BELOW AHORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of the building...

Страница 18: ...gure 23 Proper Positioning Leveling and Securing of a Fireplace Figure 24 Gas Control System Step 5 The Gas Control System WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL Intermittent Pilot Ignition...

Страница 19: ...ied installer approved and or licensed as required by the locality In the state of Massachusetts installation must be performed by a licensed plumber or gas fitter NOTE Before the first firing of the...

Страница 20: ...y cutting and removing cable tie Plug transformer into electric box terminal marked fan Check that antenna wire is held in place by two clips on the lower flange see Figure 35 Optional Fan Kits Fan ki...

Страница 21: ...SEALANT MATE RIAL MUST BE USED THESE JOINTS ARE NOT RE QUIRED TO BE SEALED ONLY NON COMBUSTIBLE MATERIAL USING 300 F MINIMUM ADHESIVE IF NEEDED CAN BE APPLIED AS FACING TO THE FIRE PLACE SURROUND SEE...

Страница 22: ...the top of the burner near front and center ports with a single layer of ember material Sprinkle GE 93 on top of the burner Save the remaining ember materials for use during fire place servicing Use o...

Страница 23: ...sembly GLASS CLIPS Step 11 Before Lighting the Fireplace BEFORE lighting the fireplace be sure to do the following Remove all paperwork from underneath the fireplace Review all cautions and Safety and...

Страница 24: ...eceiver can then be slid out and turned over without disconnecting wiring 6 Remove cover from receiver by removing 4 Phillips head screws 7 Locate code switches in receiver Slide the numbered switches...

Страница 25: ...surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patterns Make sure the fl...

Отзывы: