background image

49

Heat & Glo  •  SL-5, SL-7, SL-9 Installation Manual  •  2392-980 Rev. L  •  6/17

A.  General Information

WARNING! Risk of Shock or Explosion! DO NOT

 wire 

110-120 VAC to the valve or to the appliance wall switch. 

Incorrect wiring will damage controls.

NOTICE: 

This appliance must be electrically wired 

and grounded in accordance with local codes or, in the 

absence of local codes, with 

National Electric Code 

ANSI/NFPA 70-latest edition

 or the 

Canadian Electric 

Code CSA C22.1.

•  Wire  the  appliance  junction  box  to  unswitched  110-

120 VAC. This is required for proper operation of the 

appliance (Intellifire ignition).

•  A 110-120 VAC circuit for this product must be protected 

with ground-fault circuit-interrupter protection, in 

compliance with the applicable electrical codes, when 

it is installed in locations such as in bathrooms or near 

sinks.

•  Low voltage and 110-120 VAC voltage cannot be shared 

within the same wall box.

Accessories Requirements

•  This appliance may be used with a wall switch, wall 

mounted thermostat and/or a remote control.

Wiring for optional Hearth & Home Technologies approved 

accessories should be done now to avoid reconstruction. 

Follow instructions that come with those accessories.

Electrical Information 

WHT

WHT

BLK

BLK

GRN wire 

inside box

Copper

ground attached

to GRN screw with

GRN wire

14/2WG

Cover Plate

outside firebox

Romex 

Connector

Figure 8.1  Generic Junction Box Detail Shown

NOTICE:  DO NOT

 wire 

110-120 VAC to wall switch.

Electrical Service and Repair

WARNING! Risk of Shock! 

Label all wires prior to dis-

connection when servicing controls. Wiring errors could 

cause improper and dangerous operation. Verify proper 

operation after servicing.

WARNING! Risk of Shock! 

Replace damaged wire with 

type 105º C rated wire. Wire must have high temperature 

insulation.

B.  Wiring Requirements

Intellifire Ignition System Wiring

•  Wire  the  appliance  junction  box  to  110-120  VAC  for 

proper operation of the appliance.

WARNING! Risk of Shock or Explosion! DO NOT

 wire 

IPI controlled appliance junction box to a switched circuit. 

Incorrect wiring will override IPI safety lockout.

•  Refer to Figure 8.2, Intellifire Pilot Ignition (IPI) Wiring 

Diagram.

•  This appliance is equipped with an Intellifire control valve 

which operates on a 3 volt system.

•  Plug the 3-volt AC transformer into the appliance junction 

box to supply power to the unit OR install two D cell 

batteries (not included) into the battery pack before use.

NOTICE: 

Batteries should not be placed in the battery 

pack while using the transformer. Remove batteries before 

using the transformer, and unplug the transformer before 

installing the batteries. Battery polarity must be correct or 

module damage will occur.

Junction Box Installation

To wire the junction box:
•  Remove the screw attaching the junction box/receptacle 

to the outer shell, rotate the junction box inward to dis

-

engage it from the outer shell. See Figure 8.1.

•  Pull the electrical wires from outside the appliance through 

the opening into the valve compartment and secure wires 

with a Romex connector. See Figure 8.1.

•  Make all necessary wire connections to the  junction box/

receptacle and reattach the junction box/receptacle to 

the outer shell.

Содержание SL-5

Страница 1: ...y a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Models SL 5 SL 5LP SL 7 SL 7LP SL 9 This appliance may be installed as an OEM installation in manufactured home USA only or mobile home and must be installed in accordance with the manufacturer s instructions a...

Страница 2: ...m Clearances 15 B Chimney Diagram 16 C Approved Pipe 17 D Use of Elbows 18 E Measuring Standards 19 F Use of Flex Vent SLP FLEX Series 6 5 8 Inch 20 G Vent Diagrams 20 5 Vent Clearances and Framing A Pipe Clearances to Combustibles 35 B Wall Penetration Framing Firestops 36 C Ceiling Firestop Floor Penetration Framing 37 D Install Attic Insulation Shield 37 6 Appliance Preparation A Vent Collar Pr...

Страница 3: ...________ Gas Section 9 Pg 52 54 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure veri ed ___________________________ Veri ed proper air shutter setting for installation type ___________________________ Finishing Section 10 Pg 55 58 Combustible materials not installed in non combustible areas __...

Страница 4: ...bathrooms or near sinks NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE This appliance is tested and approved as either supplemen tal room heat or as a decorative appliance It should not be factored as primary heat in residential heating calculations NOTICE This installation must conform with local codes In the absence of local codes you must comply with the National Fuel Gas Code ANSI Z223 1 latest...

Страница 5: ...s fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed...

Страница 6: ...anometer Gloves Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws Caulking material 300 ºF minimum continuous exposure rating One 1 4 in female connection for optional fan Improper installation adjustment alteration service or maintenance ca...

Страница 7: ... impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth Home Technologies I...

Страница 8: ...36 1 8 918 43 1092 C 27 3 16 691 32 1 16 814 39 1 16 992 D 18 1 16 459 21 1 2 546 23 9 16 599 E 34 1 16 865 37 5 8 956 39 9 16 1005 F 3 9 16 90 3 9 16 90 3 9 16 90 G 6 7 8 175 6 7 8 175 6 7 8 175 H 23 3 8 594 26 7 8 683 28 7 8 733 I 34 3 8 873 37 7 8 962 39 7 8 1013 J 36 7 16 926 39 15 16 1014 41 15 16 1065 K 8 203 8 203 8 203 L 8 13 16 224 8 13 16 224 8 13 16 224 M 16 5 16 414 16 5 16 414 16 5 16...

Страница 9: ...7 41 67 689 730 SL 7 FS 7 in 34 28 3 4 35 15 16 1 5 8 2 5 8 30 5 8 32 1 4 mm 864 730 913 41 67 778 819 SL 9 FS 9 in 40 7 8 30 5 8 43 1 5 8 2 5 8 32 5 8 34 1 4 mm 1038 778 1092 41 67 829 870 A B C D E F G SL 5 CF 32 in 26 9 16 18 11 16 30 13 16 23 5 16 25 7 16 3 1 2 4 9 16 mm 675 475 783 592 646 89 116 SL 7 CF 36 in 31 1 2 22 3 16 35 13 16 26 13 16 28 15 16 3 1 2 4 9 16 mm 800 564 910 681 735 89 11...

Страница 10: ...1 1 4 37 3 16 1 1 8 6 1 4 32 7 8 37 3 8 34 3 8 mm 824 540 945 29 159 835 949 873 SL 9 HAL 42 in 39 7 16 23 1 8 44 3 16 1 1 8 6 1 4 34 3 4 44 3 8 36 3 8 mm 1002 587 1122 29 159 883 1127 924 Y B A C D E F X 1IN to 4 IN Overlap Fit Finishing Refer to Figure 10 9 A B C D E F X Y SL 5 CHA 32 in 27 7 16 18 1 8 32 1 16 1 1 8 5 13 16 29 3 8 32 3 4 30 13 16 mm 697 460 814 29 148 746 832 783 SL 7 CHA 36 in ...

Страница 11: ...32 20 3 4 37 1 8 1 3 16 7 9 16 32 7 8 37 3 8 34 3 8 mm 813 527 943 30 192 835 949 873 SL 9 CHAF 42 in 39 22 5 8 44 3 8 1 1 8 7 5 8 34 3 4 44 3 8 36 3 8 mm 991 575 1127 29 194 883 1127 924 A B C D E F Y X 1IN to 4 IN Overlap Fit Finishing Refer to Figure 10 9 A B C D E F X Y SL 5 ARC 32 in 27 7 16 16 7 8 32 1 4 1 1 8 6 1 2 29 3 8 32 3 4 30 13 16 mm 697 429 819 29 165 746 832 783 SL 7 ARC 36 in 32 7...

Страница 12: ...ue to individual design preference Figure 3 5 Appliance Locations Models A B C D E Min F G H I J K L SL 5 in 42 37 59 1 2 See Section 10 B for Alcove Instal lation 1 2 44 62 1 4 16 1 4 48 1 2 68 3 4 15 1 16 7 1 2 mm 1067 940 1511 13 1118 1581 413 1232 1746 383 191 SL 7 in 45 1 2 42 64 3 8 1 2 45 1 2 64 3 8 16 1 4 48 1 2 68 3 4 16 5 8 7 1 2 mm 1156 1067 1635 13 1156 1635 413 1232 1746 422 191 SL 9 ...

Страница 13: ...e Rough Opening Height DVP Pipe SLP Pipe Rough Opening Width Clearance to Ceiling Combustible Floor Combustible Flooring Behind Appliance Sides of Appliance Front of Appliance Rough Opening Width Rough Opening Width Rough Opening Depth Rough Opening Depth SL 5 in 10 8 5 8 34 3 4 16 1 4 16 1 4 37 32 0 0 1 2 1 2 36 mm 254 219 882 413 413 940 813 0 0 13 13 914 SL 7 in 10 8 5 8 38 1 4 16 1 4 16 1 4 42...

Страница 14: ...gions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped or an equivalent method may be used to achieve maximum air tightness To further prevent drafts the wall shield and ceiling fire stops should be caulked with caulk with a minimum of 300 ºF continuous exposure rating to seal gaps Gas line holes and other openings should be caulked with caulk with a min...

Страница 15: ...ARGE OPENING 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe could cause overheating and fire WARNING Figure 4 2 Staggered Termination Caps Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using decorati...

Страница 16: ...V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACTUAL Covered Alcove Applications Spaces op...

Страница 17: ... systems DO NOT mix pipe fittings or joining methods from differ ent manufacturers SLP FLEX and SLP FLEX7 venting cannot be interchanged SLP FLEX 6 5 8 Inch venting may be used in any venting configuration shown in the venting tables provid ed that the horizontal vent length is reduce by 25 SLP FLEX7 7 Inch Canada Only venting requires adapter collars to tranisition from the 6 5 8 in appliance sta...

Страница 18: ...C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 DVP12A 3 to 12 76 to 305 2 1 8 8 1 2 54 216 Vent Type X Inches Millimeters DVP 16 1 4 413 SLP 11 1 4 286 Figure 4 5 Vertical a...

Страница 19: ...e See Section 12 A for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 4 6 Vertical terminations are measured to top of last section of pipe See Figure 4 7 Horizontal pipe installed level with no rise MEASURE TO SHADED SURFACE OUTSIDE MOUNTING SURFACE Figure 4 6 Measure to Outside Mounting ...

Страница 20: ...l shield firestop must be installed When penetrating a combustible ceiling a ceiling firestop must be installed Horizontal runs of vent do not require vertical rise horizontal runs may be level Horizontal termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released See Figure 4 9 W A L L 1 4 in max 6 mm F Use of Flex Vent SLP FLEX Series 6 5 8 Inch The flex ven...

Страница 21: ...al vent section is required before installing first elbow When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical vent section is required before installing first elbow H1 V1 WARNING V1 Minimum H1 Maximum SL 5 SL 7 SL 9 90 Elbow 2 ft 610 mm 2 ft 610 mm 1 ft 305 mm 1 2 ft 152 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 3 ft 914 mm 3 ft 914 mm...

Страница 22: ...equired before installing first elbow When using DVP TB1 termination cap on top vented fireplaces a three foot minimum vertical vent section is required before installing first elbow INSTALLED HORIZONTALLY H1 H2 V1 WARNING V Minimum H1 H2 Maximum SL 5 SL 7 SL 9 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 0 ft 0 mm 1 2 ft 152 mm 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 ft 610 mm 2...

Страница 23: ...on top vented fireplaces a one foot minimum vertical vent section is required before installing first elbow WARNING V1 Minimum H1 H2 Maximum SL 5 SL 7 SL 9 V2 V1 V2 Min 90 Elbow 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 1 2 ft 152 mm 6 ft 1 8 m 6 ft 1 8 m 6 ft 1 8 m 1 1 2 ft 457 mm 10 ft 3 0 m 10 ft 3 0 m 10 ft 3 0 m 2 1 2 ft 762 mm 12 ft 3 7 m 12 ft 3 7 m 12 ft 3 7 m 3 1 2 ft 1 1 m 14 ft 4 3 m 14 ft 4 ...

Страница 24: ...restrictor installation Exhaust restrictor Instructions Exhaust restrictors are recommended for these verti cally terminated products which have excessive draft Exhaust restrictors will compensate for high draft and restore visual flame height If the vent configuration has a total vertical of 15 60 feet an exhaust restrictor may be needed The exhaust restrictor can be located in the appliance manu...

Страница 25: ...ontinued H1 V1 V2 V1 MIN SL 5 SL 7 SL 9 H MAX H MAX H MAX V2 V1 V2 MIN 90 Elbow 1 1 2 ft 457 mm 1 1 2 ft 457 mm 1 ft 305 mm 1 2 ft 152 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 1 1 2 ft 457 mm 3 ft 914 mm 3 ft 914 mm 3 ft 914 mm 2 1 2 ft 762 mm 5 ft 1 5 m 5 ft 1 5 m 5 ft 1 5 m 3 1 2 ft 1 1 m 7 ft 2 1 m 7 ft 2 1 m 7 ft 2 1 m 4 1 2 ft 1 4 m 15 ft 4 6 m 15 ft 4 6 m 15 ft 4 6 m H MAX 15 ft 4 6 m V1 V2 H ...

Страница 26: ...LED HORIZONTALLY H1 H2 V1 V2 V1 MIN SL 5 SL 7 SL 9 H MAX H MAX H MAX V2 V1 V2 MIN 90 Elbow 1 2 ft 152 mm 1 2 ft 152 mm 0 ft 0 mm 1 2 ft 152 mm 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 1 1 2 ft 457 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 2 1 2 ft 762 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 1 m 6 ft 1 8 m 6 ft 1 8 m 6 ft 1 8 m 4 1 2 ft 1 4 m 14 ft 4 3 m 14 ft 4 3 m 14 ft 4 3 m H MAX 14 ft 4 6 m V1 ...

Страница 27: ... 2 ft 457 mm 4 ft 1 2 m 4 ft 1 2 m 4 ft 1 2 m 3 1 2 ft 1 0 m V1 V2 V3 H1 H2 Maximum 40 ft 12 2 m Note Use SLP Series components only Note There MUST be a 25 reduction in total H when using flex vent except when using the simple up and out installation See Figure 4 8 Figure 4 17 Top Vent Vertical Termination continued V1 H1 V2 V3 H2 ...

Страница 28: ...mm SL 7 24 in 610 mm SL 9 18 in 457 mm CAUTION For SL 9 H1 Maximum can be up to 24 inches ONLY if the Optional Refractory Kit BRICK 9 is NOT used H1 9 in 229 mm Maximum Rear Vent Horizontal Termination One 45º Elbow For corner installation of models SL 5 and SL 7 ONLY Note Do not use a 45º elbow for SL 9 Use two 90º elbows for cor ner installation on SL 9 Note Use DVP Series components only H1 ...

Страница 29: ... Use DVP Series components only H1 H2 V1 H1 MAX V1 MIN H2 MAX H1 H2 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 6 ft 1 8 m 5 ft 1 5 m 3 ft 914 mm 5 ft 1 5 m 10 ft 3 0 m 7 ft 2 1 m 5 ft 1 5 m 7 ft 2 1 m 14 ft 4 3 m H1 MAX 7 ft 2 1 m H1 H2 MAX 14 ft 4 3 m V1 H1 H2 MAX 40 ft 12 2 m ...

Страница 30: ...1 MAX V1 MIN H2 H3 MAX H1 H2 H3 MAX 1 1 2 ft 457 mm Back to back elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 2 ft 610 mm 5 1 2 ft 1 7 m 5 1 2 ft 1 7 m 2 ft 610 mm 4 ft 1 2 m 9 1 2ft 2 9 m 7 1 2 ft 2 3 m 3 ft 914 mm 6 ft 1 8 m 13 1 2 ft 4 1 m H1 MAX 7 1 2 ft 2 3 m H1 H2 H3 MAX 13 1 2 ft 4 1 m V1 H1 H2 H3 MAX 40 ft 12 2 m INSTALLED HORIZONTALLY H3 H1 H2 V1 ...

Страница 31: ...mponents only V1 MIN H1 MAX 1 ft 305 mm 3 1 2 ft 1 1 m 2 ft 610 mm 5 1 2 ft 1 7 m 3 ft 914 mm 7 1 2 ft 2 3 m H MAX 7 1 2 ft 2 3 m V1 H1 MAX 40 ft 12 2 m INSTALLED HORIZONTALLY H1 H2 V2 H1 H2 MAX V1 MIN 1 2 ft 152 mm Back to back elbows 2 1 2 ft 762 mm 1 ft 305 mm 4 1 2 ft 1 4 m 2 ft 610 mm 6 1 2 ft 2 0 m 3 ft 914 mm H MAX 6 1 2 ft 2 m V H H1 MAX 40 ft 12 2 m H1 V1 ...

Страница 32: ...1 Maximum V1 Minimum H2 H1 H2 Maximum 1 1 2 ft 457 mm Back to Back Elbows 1 ft 305 mm 2 1 2 ft 762 mm 3 1 2 ft 1 1 m 1 ft 305 mm 3 ft 914 mm 6 1 2 ft 2 0 m 5 1 2 ft 1 2 m 2 ft 610 mm 5 ft 1 5 m 10 1 2 ft 3 2 m 7 1 2 ft 2 3 m 3 ft 914 mm 7 ft 2 1 m 14 1 2 ft 4 4 m H1 Maximum 7 1 2 ft 2 3 m V1 V2 H1 H2 Maximum 40 ft 12 2 m Note Use DVP Series components only ...

Страница 33: ... of Fire Coaxial to colinear venting con figuration may only be used in existing non combustible chimney Installation in any other venting application could cause fire Prior to installing the gas appliance Have the chimney and adjacent structure inspected and cleaned by qualified professionals Hearth Home Technologies recommends that NFI or CSIA certified professionals or technicians under the dir...

Страница 34: ...iance starting collar with 3 1 2 in self tapping screws See Figure 4 27 Rear Vent Remove the rear seal cap and insulation if equipped Connect the DVP 2SL adapter to the vertically positioned elbow Follow installation instructions included with DVP 2SLkit Secure DV 46DVA GCLadapter to DVP 2SLwith 3 1 2 in self tapping screws See Figure 4 27 Connecting the LINK DV30B to the DV 46DVA GCL adapter Inse...

Страница 35: ... Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in a DVP HSM B will be required SLP heat shield designed to be used on a wall 4 3 8 in to 7 5 8 in 111 mm to 194 mm thick If wall th...

Страница 36: ... firestop is included with the termination cap assembly For internal walls A wall shield firestop must be pur chased and installed The opening must be framed on all four sides using the same size framing materials as those used in the wall construction SLP pipe A wall shield firestop must be placed on each side of an interior wall A minimum 1 1 2 in 38 mm overlap of attached heat shields must be m...

Страница 37: ... Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Generic Fireplace Shown Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING ATTIC ABOVE A PIPE DVP SLP A 10 in 254 mm 9 in 229 mm A D Install Attic ...

Страница 38: ...nitial vertical requirements The following provisions must be followed 1 The elbow heat shield is not required if combustible materials or combustible chases are installed a mini mum of 6 inches above the top of the elbow See Fig ure 6 2 2 If the combustible materials are to be installed between 3 inches and 6 inches above the top of the elbow the elbow heat shield is required See Figure 6 2 For a...

Страница 39: ...ng component in the vent system 90 elbows may be installed and rotated to any point around the preceding component s vertical axis If an elbow does not end up in a locked position with the preceding component attach with a minimum of two 2 sheet metal screws CORRECT INCORRECT COMBUSTIBLE SURFACE DIRECTION UP HEAT SHIELD 90 ELBOW 0 Figure 6 3 Figure 6 6 Rotate the top heat shield to the vertical po...

Страница 40: ...nt pipe make sure to use the fiberglass gasket to seal between the first vent component and the outer fireplace wrap Use 2 self tapping screws to secure the gasket to the outer wrap Note Once the seal cap has been removed it cannot be reattached 2 SCREWS Figure 6 9 Remove the insulation basket and white insu lation from the center vent pipe Figure 6 8 Remove the seal cap ...

Страница 41: ...place Shown Cut the metal retaining band and fold the sides out Figure 6 11 Generic Fireplace Shown Fold the center parts of the retaining band out and use to remove the seal cap Figure 6 12 Generic Fireplace Shown Discard the seal cap remove and discard the insulation basket Note Once the seal cap has been removed it CANNOT be reattached Figure 6 13 Generic Fireplace Shown Attach the first vent s...

Страница 42: ...ms underneath the appliance Place a level on top sides and bottom as shown in Figure 6 15 Secure the appliance to the framing by using nails or screws through the nailing tabs Optional Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance Figure 6 15 Proper Positioning and Securing of an Appliance Figure 6 14 Heat Zone Locations HEAT ZONE ...

Страница 43: ... from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe WARNING Risk of Fire or Explosion DO NOT break silicone seals on slip sections Use care when remov ing termination cap from slip pipe If slip section seals are br...

Страница 44: ... the collar Align the seam of the pipe and seam of collar to allow engagement Rotate the vent component to lock into place Use this procedure for all vent components See Figure 7 5 Slide the gasket over the first vent section and place it flush to the appliance This will prevent cold air infiltration Caulk with a minimum of 300 ºF continuous exposure rating may be used to hold the part in place Co...

Страница 45: ...d every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizontal runs must be supported every 5 feet 1 52 m Vent supports or plumbers strap spaced 120º apart may be used to support vent sections See Figures 7 8 and 7 9 Wall shield firestops may be used to provide ...

Страница 46: ...OM ROOF TO LOWEST DISCHARGE OPENING Figure 7 14 insert Bolt into Brackets NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 7 13 Caulk the overlap seam of any exposed pipe sections that are located...

Страница 47: ...rlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 16 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall thickness is less than 4 in 102 mm DVP or 4 3 8 in 111 ...

Страница 48: ...r siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 4 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which ...

Страница 49: ...ING Risk of Shock Label all wires prior to dis connection when servicing controls Wiring errors could cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105º C rated wire Wire must have high temperature insulation B Wiring Requirements Intellifire Ignition System Wiring Wire the appliance junction box to 110 120 VAC f...

Страница 50: ...gnition module valve pilot and wall switch operate on 3 volts 110 120 VAC is required at junction box unless equipped with battery back up TRANSFORMER 3 VAC PLUG IN PLUG IN BLACK RED BATTERY PACK REMOTE WIRES TO BROWN ORANGE GREEN VALVE GROUND TO FIREPLACE CHASSIS HOT NEUTRAL WHITE ORANGE IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR I S Figure 8 3 Intellifire Ignition Wiring Diagram with Optio...

Страница 51: ...box connect the black hot wire and red switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1 4 in insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch connector 1 4 in male as shown Red Switch Switch ...

Страница 52: ...ipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure could cause explosion Verify inlet pressures Verify minimum pressures when other household gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig 9 Gas Infor...

Страница 53: ...be adjusted to a more closed position Natural Gas NG installations As a general rule it is acceptable to reduce the shutter opening to adjust for short horizontally terminating or vertically terminating vent configurations prior to the initial fire up Propane LP installations As a general rule if the flames appear blue after 30 minutes of operation it is acceptable to close the shutter slightly Re...

Страница 54: ...ation The burner may be accessed for identification and veri fication purposes This task should be performed by a qualified service technician The logs and burner must be removed to see these identification marks Disconnect the pilot from the burner before removal See Figure 9 2 for burner identification chart Notch patterns are located on bottom side of burner ...

Страница 55: ...rials must never overhang into the glass opening Observe all clearances when applying combustible materials Confirm that appliance is plum square and level See Section 6 Seal joints between the finished wall and appliance top and sides using a 300 ºF minimum sealant Refer to Figure 10 1 WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum cl...

Страница 56: ...in inches UNLIMITED TOP VIEW 5 7 8 IN MINIMUM 3 IN MINIMUM FIREPLACE OPENING See Dimension B on Appliance Dimension Diagram Figure 3 1 Figure 10 5 Wall Projection Acceptable on one side of opening Note Clearance from opening to perpendicular wall Figure 10 2 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles TOP OF HOOD OR FIREPLACE OPENING See Dimension V on Appliance Dimension Di...

Страница 57: ...2392 980 Rev L 6 17 Figure 10 6 Rear Vent Non Combustible Zone Above Appliance Figure 10 7 Top Vent Non Combustible Zone Above Appliance 3 1 2 IN MIN 12 IN MINIMUM WITH ELBOW HEAT SHIELD INSTALLED 15 INCH MINIMUM WITHOUT ELBOW HEAT SHIELD INSTALLED ...

Страница 58: ...MAXIMUM THICKNESS DECORATIVE FRONT Figure 10 9 Overlap Fit Decorative Front ARC CHA CHAF HAL Finishing material between 1 and 4 inches thick Refer to Section 3 for X and Y dimensions C Decorative Front Finishing Only decorative fronts certified for use with this appliance model may be used Contact your dealer for a list of dec orative fronts that may be used Once you have deter mined what kind of ...

Страница 59: ...tory installed or accompany the door of the unit depending on the fireplace model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in stalling the splatter guard to prevent accidental lighting Remove the splatter guard before lighting the appliance Pull the four glass assembly latches out of the groove on the glass frame Remove glass assemb...

Страница 60: ...nt While Placing Right Hearth Component 1 Locate the left hearth component shown in Figure 11 2 Place it as shown in Figure 11 3 ensuring that the outer edge of the hearth component firmly contacts the firebox side and the front edge contacts the firebox front lip Gently push down on the indentation to force the bottom side of the hearth component to engage the screw tips on the bottom of the fire...

Страница 61: ... 9 LOG PINS EMBERS Figure 1 Log Pin and Glowing Ember Locations CAUTION Logs are fragile handle with care Install Logs Figure 2 Example of Log Pin Holes Figure 3 Log Assembly Components Log Placement Tips The rear left log rear right log and small burner log utilize holes in the bottom side of the logs that correspond to the locator pins on the burner Reference Figure 1 and Figure 2 Additionally t...

Страница 62: ...NTATIONS INDENTATIONS SL 7 and SL 9 Models There will be about a 1 inch rear gap between the left rear log and the back wall of the firebox There will be about a 1 1 2 inch side gap between the left end of the log and the left side of the firebox See Figure 4 SL 5 Models There will be about a 1 inch rear gap from the left rear log to the back wall of the firebox There will be about a 1 inch side g...

Страница 63: ... as a complete assembly Replacing Fixed Glass Assembly Replace the glass door on the appliance Pull out and latch the four glass assembly latches into the groove on the glass frame GLASS ASSEMBLY LATCHES BOTH BOTTOM AND TOP 2392 935C 4 Remove top left log from packaging Place the log into the indentation on the left rear log The indenta tion is highlighted in Figure 6 The bottom two points of the ...

Страница 64: ...289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45º Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 124 mm 13 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm DVP WS Wall Shield Firestop Finished ...

Страница 65: ...n 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield A Vent Components Diagrams continued Figure 12 2 DVP Vent Components Term Cap Minimum Effective Length Maximum Effective ...

Страница 66: ...12 Roof Flashing Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield A Vent Components Diagrams continued Figure 12 3 DVP Vent Components ...

Страница 67: ... mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap 1 in 25 mm 14 in 356 mm 3 8 in 10 mm 1 in 25 mm 7 1 4 in 184 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap 6 in 152 mm A Vent Components Diagrams continued Figure 12 4 DVP Vent ...

Страница 68: ...0 FT PV Wire Harness PVI WH80 100 FT PV Wire Harness PVI WH100 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm 12 1 2 IN 318 mm 20 3 4 IN 527 mm 13 5 8 IN 346 mm EFFECTIVE LENGTH 32 IN 813 mm MIN 35 IN 889 mm MAX PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Approved for use with PVI SLP B only Note Wire h...

Страница 69: ... IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View PVLP BEK Brick Kit Note Wire harnesses required to power the PVLP SLP connect to the appliance and are ordered separately from PVLP SLP Contact your dealer to order Note The PVLP SLP requires a PV IPI CK be installed on t...

Страница 70: ...ngth SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36...

Страница 71: ... trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 133 mm 235 mm 8 in 203 mm 12 in 305 mm Max Effective Length 14 7 16 in 367 mm 14 7 16 in 367 mm 2 5 16 in 59 mm 3 15 16 in 101 mm 6 11 16 in 169 mm 8 in 203 mm 3 15 16 in 101 mm 3 1...

Страница 72: ...rizontal Termination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap DVP FBHT Horizontal Termination Cap 13 1 2 in 343 mm 28 1 2 in 724 mm 10 11 16 in 271mm 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Basement...

Страница 73: ...olinear Appliance Connector 768 380A Stainless Steel Flex Pipe DVP 2SL Adapter COAXIAL to COLINEAR VENTING Figure 12 11 Coaxial to Colinear Vent Components SLP HHW2 Horizontal High Wind Termination Cap 15 IN 381 mm 12 IN 305 mm 8 IN 203 mm Figure 12 10 SLP series Vent Components A Vent Components Diagrams continued ...

Страница 74: ...th the kit for operation Preparation of the appliance for installation of the kit is discussed in Section 6 B Contact your dealer if you have questions Printed in U S A Copyright 2017 Heat Glo a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www heatnglo com Please contact your Heat Glo dealer with any questions or concerns For the location of your nearest Heat Glo dea...

Отзывы: