![Heat & Glo SL-5 Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/heat-and-glo/sl-5/sl-5_installation-manual_2115417023.webp)
23
Heat & Glo • SL-5, SL-7, SL-9 Installation Manual • 2392-980 Rev. L • 6/17
H
2
H
1
V
2
V
1
Figure 4.12
Top Vent - Horizontal Termination - (continued)
Three Elbows
Note
: Use SLP Series
components only.
Note
: There MUST be a 25%
reduction in total H when
using flex vent except when
using the simple up and out
installation. See Figure 4.8.
Fire Risk.
• When using SLP-HRC-SS termination cap
on top vented fireplaces, a one foot minimum
vertical vent section is required before installing
first elbow.
WARNING **
V
1
Minimum
H
1
+ H
2
Maximum
SL-5
SL-7
SL-9
V
2
V
1
+ V
2
Min.
90 Elbow **
2 ft.
610 mm
2 ft.
610 mm
2 ft.
610 mm
*
*
1/2 ft.**
152 mm
6 ft.
1.8 m
6 ft.
1.8 m
6 ft.
1.8 m
*
*
1-1/2 ft.**
457 mm
10 ft.
3.0 m
10 ft.
3.0 m
10 ft.
3.0 m
*
*
2-1/2 ft.**
762 mm
12 ft.
3.7 m
12 ft.
3.7 m
12 ft.
3.7 m
*
*
3-1/2 ft.
1.1 m
14 ft.
4.3 m
14 ft.
4.3 m
14 ft.
4.3 m
*
*
H
1
+ H
2
MAX. =14 ft. (4.6 m)
V
1
+ V
2
+ H
1
+ H
2
MAX. = 40 ft. (12.2 m)
*No specific restrictions on this value EXCEPT V
1
+ V
2
+ H cannot exceed 40 ft. (12.2 m)
** See warning below