19
Heat & Glo • LUX36, LUX42 Installation Manual
•
• 2287-980 Rev. L
2287-980 Rev. L • 4/16
Top Vent - Horizontal Termination
H
1
V
1
One Elbow
LUX36
V
1
Minimum
H
1
Maximum
2 ft
610 mm
17 in*
432 mm
3 ft
914 mm
2 ft
610 mm
4 ft
1.2 m
4 ft
1.2 m
5 ft
1.5 m
9 ft
2.7 m
6 ft
1.8 m
12 ft
3.7 m
7 ft
2.1 m
14 ft
4.3 m
10 ft
3.0 m
20 ft
6.1 m
20 ft
6.1 m
40 ft
12.2 m
After V
1
= 6 ft then H
1
= 2 x V ft Maximum
V
1
+ H
1
= 60 ft Maximum
*when used with approved termination caps
Note:
Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
LUX42
V
1
Minimum
H
1
Maximum
4 ft
1.2 m
17 in*
432 mm
5 ft
1.5 m
2 ft
610 mm
6 ft
1.8 m
9 ft
2.7 m
7 ft
2.1 m
14 ft
4.3 m
10 ft
3.0 m
20 ft
6.1 m
20 ft
6.1 m
40 ft
12.2 m
After V
1
= 6 ft then H
1
= 2 x V ft Maximum
V
1
+ H
1
= 60 ft Maximum
*when used with approved termination caps
WARNING! Risk of Fire!
• LUX36 requires a minimum of 24 inches of vertical venting before
attaching any elbow to the appliance.
• LUX42 requires a minimum of 48 inches of vertical venting before
attaching any elbow to the appliance.
DO NOT attach elbow directly to the appliance.
Figure 4.6
F. Vent Diagrams
WARNING! Risk of Fire.
This appliance requires a minimum of 24 inches of vertical venting before attaching any elbow to
the appliance.
DO NOT
attach elbow directly to the appliance.
General Rules:
• This appliance is approved for use with Hearth & Home Technologies DVP venting systems ONLY.
• When penetrating a combustible wall, a wall shield
fi
restop must be installed.
• When penetrating a combustible ceiling, a ceiling
fi
restop must be installed.
• This appliance requires a minimum of 24 inches of vertical pipe attached directly to the appliance starting collar before
attaching a 90 degree or 45 degree elbow.
• Horizontal termination cap should have a 1/4 inch downward slant to allow any moisture in cap to be released.