Heat & Glo  •  LUX36, LUX42 Installation Manual  

  •  

•  2287-980 Rev. L

2287-980 Rev. L  •  4/16

C.  Constructing the Appliance Chase

A chase is a vertical box-like structure built to enclose the 
gas appliance and/or its vent system. In cooler climates 
the vent should be enclosed inside the chase.

NOTICE: 

Treatment of ceiling 

fi

 restops and wall shield 

fi

 restops and construction of the chase may vary with the 

type of building. These instructions are not substitutes 
for the requirements of local building codes. Therefore, 
you MUST check local building codes to determine the 
requirements to these steps.

Chases should be constructed in the manner of all out-
side walls of the home to prevent cold air drafting prob-
lems. The chase should not break the outside building 
envelope in any manner.
Walls, ceiling, base plate and cantilever 

fl

 oor of the chase 

should be insulated. Vapor and air in

fi

 ltration  barriers 

should be installed in the chase as per regional codes for 
the rest of the home. Additionally, in regions where cold 
air in

fi

 ltration may be an issue, the inside surfaces may be 

sheetrocked and taped for maximum air tightness. 
To further prevent drafts, the wall shield and ceiling 

fi

 re-

stops should be caulked with caulk with a minimum of 

Figure 3.7  Clearances to Combustibles (2 X 4 Construction)

NOTICE: 

Install appliance on hard metal or wood surfaces 

extending full width and depth. 

DO NOT

 install directly 

on carpeting, vinyl, tile or any combustible material other 
than wood.

WARNING! Risk of Fire! 

Maintain speci

fi

 ed air space 

clearances to appliance and vent pipe:

•  Insulation and other materials must be secured to prevent 

accidental contact.

•  The chase must be properly blocked to prevent blown 

insulation or other combustibles from entering and 
making contact with 

fi

 replace or chimney.

•  Failure to maintain airspace may cause overheating and 

fi

 re.

300ºF continuous exposure rating to seal gaps. Gas 
line holes and other openings should be caulked with 
caulk with a minimum of 300ºF continuous exposure rating 
or stuffed with unfaced insulation. If the appliance is being 
installed on a cement surface, a layer of plywood may be 
placed underneath to prevent conducting cold up into the 
room.

* MINIMUM FRAMING DIMENSIONS USING 2 X 4 CONSTRUCTION

A

B

C

D

E

F

G

H

I

J

Rough

Opening

(Vent Pipe)

Rough

Opening

(Height)

Rough

Opening

(Depth)

Rough

Opening

(Width)

Clearance

to Ceiling

Combustible

Floor

Hearth 

Extension

Behind

Appliance

Sides of

Appliance

Front of

Appliance

LUX36

Inches

10

56

24

59-1/2

52

0

See 

Section  

3.D.

1

1

36

Millimeters

254

1422

610

1511

1321

0

25

25

914

LUX42

Inches

10

61

24

65-9/16

52

0

1

1

36

Millimeters

254

1549

610

1665

1321

0

25

25

914

* Adjust framing dimensions for interior sheathing (such as sheetrock)

F

H

E

G

I

J

(FROM APPLIANCE 
OPENING TO CEILING)

NOTE: 

 2 X 4 Header positioned vertically. See also Figure 10.11.

C

B

D

A

Содержание LUX36

Страница 1: ...e is not convertible for use with other gases unless a certified kit is used Pour demander un exemplaire en fran ais de ce Manuel du propri taire visitez www heatnglo com translations DO NOT store or...

Страница 2: ...Vent Termination Minimum Clearances 16 B Chimney Diagram 17 C Approved Pipe 18 D Use of Elbows 18 E Measuring Standards 18 F Vent Diagrams 19 G PVLP SLP and PVI SLP Information 25 5 Vent Clearances a...

Страница 3: ...installed if applicable ___________________ Veri ed Exterior wall Roof ashing is installed and sealed ___________________ Veri ed termination cap is installed and sealed ___________________ Electrica...

Страница 4: ...E Non Combustible Materials Specification Material which will not ignite and burn Such materials are those consisting entirely of steel iron brick tile concrete slate glass or plasters or any combina...

Страница 5: ...ed gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or loc...

Страница 6: ...ation DO NOT install damaged in complete or substitute components Keep appliance dry B Tools and Supplies Needed Before beginning the installation be sure that the following tools and building supplie...

Страница 7: ...410 Location Inches Millimeters A 61 1549 B 35 7 8 911 C 39 7 8 1013 D 31 1 16 789 E 57 5 8 1464 F 54 15 16 1395 G 41 3 8 1051 H 24 610 A B D C E G J K L M N P O GAS ACCESS ELECTRICAL ACCESS H I HEAT...

Страница 8: ...llimeters I 23 1 2 597 J 65 5 16 1659 K 16 406 L 32 11 16 830 M 3 7 8 98 N 2 3 4 70 O 10 7 8 276 P 16 1 8 410 Location Inches Millimeters A 67 1702 B 41 7 8 1064 C 45 7 8 1165 D 36 1 16 916 E 62 5 8 1...

Страница 9: ...ENSION DIAGRAM LUX36 See Section 10 for facing and finishing detail Figure 3 3 Decorative Front Dimensions LUX36 41 5 8 IN 1057 mm 1 1 4 IN 32 mm 4 1 2 IN 114 mm 37 1 16 IN 941 mm 38 3 8 IN 975 mm LMO...

Страница 10: ...SION DIAGRAM LUX42 See Section 10 for facing and finishing detail Figure 3 4 Decorative Front Dimensions LUX42 47 5 8 IN 1210 mm 1 1 4 IN 32 mm 4 1 2 IN 114 mm 42 1 16 IN 1068 mm 43 3 8 IN 1102 mm LMO...

Страница 11: ...ccess Due to high temperatures the appliance should be lo cated out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY...

Страница 12: ...3 6 Non Combustible Zone NO COMBUSTIBLES IN HATCHED AREA 1 2 IN BUILDING MATERIAL MAY BE COMBUSTIBLE FACTORY SUPPLIED 1 2 IN NON COMBUSTIBLE BOARD PIPE IS FOR VISUAL REFERENCE ONLY 1 IN COMBUSTIBLES...

Страница 13: ...ard metal or wood surfaces extending full width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space...

Страница 14: ...h Opening Height Rough Opening Height Rough Opening Depth Rough Opening Width Clearance to Ceiling LUX36 Inches 10 56 80 3 8 24 59 1 2 52 Millimeters 254 1422 2042 610 1511 1321 LUX42 Inches 10 61 85...

Страница 15: ...IN 3 IN MIN BOTTOM OF FIREPLACE 1 2 IN MAX THICKNESS COMBUSTIBLE BUILDING MATERIAL Figure 3 11 Appliance Raised a Minimum of 3 Inches Above Combustible Surface Non Combustible Hearth Extension NOT REQ...

Страница 16: ...re Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause overhe...

Страница 17: ...serves both dwellings N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches clearance below an unventilated ventilated soffit with non vinyl siding 18 inches clearance below an unventil...

Страница 18: ...igure 4 4 Figure 4 5 shows the vertical and horizontal offsets for DVP or SLP elbows Figure 4 4 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run In...

Страница 19: ...NING Risk of Fire LUX36 requires a minimum of 24 inches of vertical venting before attaching any elbow to the appliance LUX42 requires a minimum of 48 inches of vertical venting before attaching any e...

Страница 20: ...5 5 m 10 ft 3 0 m 20 ft 6 1 m V1 H1 H2 60 ft Maximum H1 H2 20 ft Maximum LUX42 V1 Minimum H1 H2 4 ft 1 2 m 17 in 432 mm 5 ft 1 5 m 2 ft 610 mm 6 ft 1 8 m 9 ft 2 7 m 7 ft 2 1 m 14 ft 3 7 m 8 ft 2 4 m 1...

Страница 21: ...V2 has no specific restrictions EXCEPT Vtotal Htotal cannot exceed 60 ft Maximum LUX42 V1 H1 Maximum V2 H2 4 ft 1 2 m 17 in 432 mm H2 Max 2 X V2 5 ft 1 5 m 2 ft 610 mm H2 Max 2 X V2 6 ft 1 8 m 9 ft 2...

Страница 22: ...t Vertical Termination No Elbow V1 50 ft Max 15 2 m V1 2 ft Min 610 mm LUX36 V1 4 ft Min 1 2 m LUX42 NOTE Flue Restrictor ships in manual bag assembly Note Flue restrictor is permit ted ONLY on 30 ft...

Страница 23: ...e Flue restrictor is permit ted ONLY on 30 ft minimum vertical runs with no elbows H1 V1 V2 2 ELBOWS LUX42 V1 H1 Maximum V2 4 ft 1 2 m 17 in 432 mm 5 ft 1 5 m 2 ft 610 mm 6 ft 1 8 m 9 ft 2 7 m No spec...

Страница 24: ...12 ft 3 7 m No specific restrictions on this value EXCEPT V1 V2 H1 H2 50 ft 15 2 m Max After V1 6 ft then H1 Max V1 x 2 LUX42 V1 H1 Maximum V2 4 ft 1 2 m 17 in 432 mm 5 ft 1 5 m 2 ft 610 mm 6 ft 1 8...

Страница 25: ...er vent draft flow must be adjusted and set per the specifications in Table 4 2 Refer to the instructions provided with the PVLP SLP and PVI SLP for more specific information Setting the PVLP SLP Baff...

Страница 26: ...Section 7 F for information for regarding the instal lation of a horizontal termination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by non com bustible materials su...

Страница 27: ...pe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield 3 FASTENERS PER SIDE INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTE...

Страница 28: ...appliance See Figure 5 6 Remove the knockouts from the appliance with a tin snips Center the duct collar around the exposed hole and attach it to the appliance with 3 screws Note Do this BEFORE final...

Страница 29: ...he glass refractory and media Section 11 2 Remove seal cap from top of appliance by removing one screw which is included to prevent construction material from getting into appliance Remove seal cap wh...

Страница 30: ...Keep side nailing tabs flush with the framing Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims underneath the appliance Positi...

Страница 31: ...ce in a large protective cover See Figure 6 1 Install lower left and right non combustible legs and top non combustible with screws supplied in the manual bag assembly See Figure 6 6 Use fasteners fro...

Страница 32: ...For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotatin...

Страница 33: ...rted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizon...

Страница 34: ...ermine the length of pipe to extend through the roof Slide the roof flashing over the pipe sections extending through the roof as shown in Figure 7 10 Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to...

Страница 35: ...elds on the cap and wall shield firestop must be trimmed A minimum 1 1 2 in 38 mm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 7 1 4 in 184 mm...

Страница 36: ...en connecting vent 1 1 2 38 mm minimum overlap of flue telescoping section is required Failure to maintain overlap may cause overheating and fire Vent termination must not be recessed in the wall Sidi...

Страница 37: ...voltage cannot be shared within the same wall box 8 8 Electrical Information Junction Box Installation The electrical junction box can be accessed three ways during installation 1 Through the side ele...

Страница 38: ...reless controls be used for their features and functionality with the IntelliFireTM Plus ignition sys tem Figure 8 2 Junction Box Detail Electrical Service and Repair WARNING Risk of Shock Label all w...

Страница 39: ...as a power source the 6 volt transformer must be unplugged from the receptacle Do not store batteries in the battery pack when the appliance is powered by the 6 volt transformer connected to permanent...

Страница 40: ...k check solution DO NOT use open flame Fittings and connections could have loos ened during shipping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the fa...

Страница 41: ...nger vertical vent runs See Figure 9 1 Loosen the screw on the burner assembly Rotate the air shutter to the correct setting Push the air handle in to close the air shutter Tighten the screw NOTICE If...

Страница 42: ...thick The required decorative front will overlap finish materials less than one inch thick Refer to section 13 E for more information Template installation instruction 1 Refer to Section 10 E for deco...

Страница 43: ...anual Overlapping materials could ignite and will interfere with proper operation of decorative fronts and louvers Figure 10 5 Non combustible Facing Diagram 0 in NON COMBUSTIBLE BOARD A B COMBUSTIBLE...

Страница 44: ...be made in order to secure the mantel to the adjacent framing materials For example lintel brackets or lag bolts may be considered for this purpose FIREPLACE OPENING COMBUSTIBLE OR NON COMBUSTIBLE WAL...

Страница 45: ...ance have been designed to be installed by two methods Overlap Fit or Inside Fit Before beginning the installation it is important to determine which method will be used Overlap Fit Decorative Fronts...

Страница 46: ...ol 1 Glass clip removal installation tool is fastened to the lower right corner of the fireplace Remove tool by removing one screw See Figure 11 1 If glass clip re moval tool becomes misplaced a cotte...

Страница 47: ...as four tabs If the glass is not centered it can not be installed properly See Figure 11 5 4 Install fixed glass assembly by lifting it up and sliding it into the top retaining rail Grasp the fixed gl...

Страница 48: ...of Cuts Abrasions or Flying Debris Wear protective gloves and safety glasses during instal lation CAUTION Glass is fragile Handle with care 1 Remove rear and side glass retainer brackets as shown in...

Страница 49: ...e media in area in front of pilot or between burner tracks Do NOT place media in a position that they may fall into area in front of pilot Do NOT use any media other than the media supplied with this...

Страница 50: ...e Figure 11 20 Remove three outside burner tubes by removing two screws on each tube It will be necessary to remove two screws from the pilot assembly and two screws from the pilot shield on the rear...

Страница 51: ...25 mm 12 in 305 mm 14 in 356 mm 1 in 25 mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP...

Страница 52: ...mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thicknes...

Страница 53: ...Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8...

Страница 54: ...P LPC SLP Low Profile Cap Note Wire harnesses required to power the PVI SLP connect to the appliance and are ordered separately from PVI SLP Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 1...

Страница 55: ...e ordered separately from PVLP SLP Contact your dealer to order Note The PVLP SLP requires a PVLP CK be installed on this appliance The PVLP CK is ordered separately from the PVLP SLP Contact your dea...

Страница 56: ...ation of Heat Zone Gas Kit is discussed in Section 5 E See your dealer if you have questions Printed in U S A Copyright 2016 Heat Glo a brand of Hearth Home Technologies 7571 215th Street West Lakevil...

Отзывы: