Heat & Glo • SLR • 2143-900 Rev. B • 7/08
24
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
Figure 7.5
1. Top Vent - Horizontal Termination - (continued)
Top Vent - Horizontal Termination
Venting with 2 elbows
Note
: Use SLP Series
components only.
V Minimum
H
1
+ H
2
MAXIMUM
SLR
90° Elbow
1 ft.
305 mm
1 ft.
305 mm
2 ft.
610 mm
2 ft.
610 mm
4 ft.
1.2 m
3 ft.
914 mm
6 ft.
1.8 m
4 ft.
1.2 m
14 ft.
4.3 m
H + H
1
MAX. =14 ft. (4.3 m)
V + H + H
1
MAX. = 40 ft. (12.2 m)
Note
: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 7.3).
Note
: The SLP-HRC-SS and
SLP-HRC-ZC-SS termination
caps are not approved for use
with propane (LP) fuel.