7
Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP-AU) Instructions • 4052-902 Rev. C • 10/19
H
1
H
2
V
2
V
1
NOTICE:
If pipe configuration includes a vertical component that goes
downward, a vertical component going back upward is not allowed.
A DVP-2SL or DVP-SLP24
is required in any position
after the first 90 degree
elbow on certain models.
See Table 2.1.
Figure 2.3 Horizontal PVLP Orientation
WARNING! Risk of Fire!
Minimum 2 ft. ( 610 mm) straight vertical DVP pipe directly off appliance followed by 90 degree
elbow and DVP-2SL adapter on these models:
MEZZO1000-AUB, MEZZO1300-AUB, MEZZO1300ST-AUB, MEZZO1600-AUB
Combustibles surrounding pipe may overheat.
Top Vent - Horizontal Termination con't.
Minimum Vent Run
Maximum Vent Run
A minimum of 2 ft. (610 mm) of vertical
piping is required between the appliance
and the PVLP-SLP-AU with certain appli-
ance models. See Table 2.1.
See Chart in Section 2.C: "Venting Length - Model Categories and
Length Requirements by Termination Type."
Note
: For every 1 ft. (305 mm) of vertical drop the total
allowable length must be reduced by 2 ft. (610 mm).