Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP-AU) Instructions • 4052-902 Rev. C • 10/19
B. Wall Switch and Timer Control Junction
Box Installation
2. Wall switch must be located a minimum of 1 meter away
from the closest edge of the fireplace appliance. See
Figure 4.3.
WALL
SWITCH
MININMUM
1 METER
Figure 4.3
3. Allow Timer Control Junction Box to hang inside the wall
behind the wall switch. This will allow for access to the
junction box through the wall switch hole if service is
required.
Note:
A strain relief must be placed behind the wall
switch to prevent the junction control box from
pulling on the wiring going to the wall switch.
4. Connect extension cord lead from termination cap to
female plug (number 2 in Figure 4.2).
5. Unplug 6V transformer from fireplace power cord.
Run plug for 6V from timer control junction box inside
the fireplace and plug 6V transformer in (number 4 in
Figure 4.2).
6. Plug in power input cord from timer control junction box
into fireplace power cord where the 6V transformer was
(number 5 in Figure 4.2).
C. Time Delay Relay Settings
1. Time on Delay Relay should be set as shown in Figure
4.4.
Figure 4.4
NOTE
: Relays come pre-set to desired pre and post
purge time as shown below.
2. Time off delay relay should be set as shown in Figure
4.5.
Figure 4.5
NOTE
: Figure 4.4 shows two different time on delay
relays that can be used. See relay instructions
for more details.
NOTE
: Figure 4.5 shows two different time off delay
relays that can be used. See relay instructions
for more details.
WARNING! Risk of Shock!
1. Disconnect power to fireplace appliance.