Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP-AU) Instructions • 4052-902 Rev. C • 10/19
MAXIMUM
VERTICAL
DROP
MAXIMUM
VERTICAL
DROP
FROM
APPLIANCE
NOTE
: Maximum total vent run= Total vertical vent run + Total horizontal vent run
DIRECT VENT WITH 4 in. / 6-5/8 in. (102 mm / 168 mm)
DIAMETER SLP PIPE
MAX. ELBOWS
(45° & 90°)
MAX. TOTAL VENT
RUN (FT.)
MAX. VERT.
DROP (FT.)
12-45° or 6-90°
90 ft. (27.43 m)
12 ft. (3.66 m)
See table in Section 2.C
DIRECT VENT WITH 5 in. / 8 in. (127 mm / 203 mm)
DIAMETER DVP PIPE
MAX. ELBOWS
(45° & 90°)
MAX. TOTAL VENT
RUN (FT.)
MAX. VERT.
DROP (FT.)
12-45° or 6-90°
90 ft. (27.43 m)
12 ft. (3.66 m)
See table in Section 2.C
ADAPTER KITS
PART NUMBER
PART DESCRIPTION
DVP-SLP24
Adapts from 5 in./ 8 in. (127 mm / 203 mm) DVP-series starting collars to 4 in. / 6-5/8 in.
(102 mm / 168 mm) SLP-series vent pipe.
DVP-2SL
Adapts from 5 in./ 8 in. (127 mm / 203 mm) DVP-series starting collars to 4 in. / 6-5/8 in.
(102 mm / 168 mm) SLP-series vent pipe.
NOTICE:
If a pipe configuration includes a
vertical component that goes downward, a
vertical component going back upward is not
allowed.
Note
: For every 1 ft. (305 mm) of vertical drop the total
allowable length must be reduced by 2 ft. (610 mm).