Hearth & Home Technologies • Power Vent Low Profile (PVLP-SLP-AU) Instructions • 4052-902 Rev. C • 10/19
A. Installation Inspection
1. Follow safety inspection procedures recommended by
national, provincial, and/or local codes.
2. Be certain all electrical connections are properly made
and secure.
3. Visually inspect the vent system and determine that
there is no flue gas spillage, blockage or restriction,
leakage, corrosion or other unsafe deficiencies.
4. Check timings set on time on and time off delay relays.
Time on Delay: 100-120 sec
·
This can be measured by taking the time from when
the wall switch is turned on until the time at which
the module beeps.
Time off Delay: 18-22 minutes
·
This can be measured by taking the time from when
the wall switch is turned off until the time when the
fan turns off.
5
Operating Instructions
CAUTION! Risk of electrical shock! DO NOT
allow
240VAC
wires to contact hot metal surfaces. Use sup-
plied wire ties to bundle wires away from flue pipe, fan
housing and other metal surfaces.
B. Power Vent Operating Instructions
After installation of the power vent, follow the operation
instructions below.
IPI Plus/RC300
1. Turn the wall switch "ON".
NOTE
: A 100-120 second pre-purge will begin. Once this
is complete, power is supplied to the appliance. This can
be verified by a beep sound from the module.
2. Turn the remote "ON".
NOTE
: After turning the remote to the "ON" position, if the
appliance does not turn on, turn the remote to "OFF" refer
to the troubleshooting section.
3. Turn the remote to "OFF" to turn off the burner. Turn
the wall switch to "OFF" to turn off the power vent.
NOTE:
The power vent will continue to run for 20 minutes.
To operate the power vent and fireplace appliance with only
the wall switch, connect the red and brown wires together
coming from the control module wiring harness, see Figure
5.1. This will automatically start the fireplace appliance
after the pre-purge is complete. Allow customer to set
desired flame height and fan setting on remote before red
and brown wires are jumped together.
8K1 WIRE
HARNESS
GROUND
CONTROL MODULE
CONNECT RED
AND BROWN
WIRES TOGETHER
RED
BROWN
Figure 5.1
NOTE:
If relays are set incorrectly refer to section 4.C.
for the correct relay settings.