16
X. Basic Service and Troubleshooting
10.3 Air Purification System Power is On but Fan Inoperable
If the unit powers on but the fan fails to operate, the issue may be the result of
a faulty motor and will require service by the manufacturer or a professionally
licensed electrician.
Possible Cause
Solution
Fan/Motor malfunction
Replace the Fan/Motor
PCB Board malfunction
Replace the PCB Board
10.4 Reduced Airflow/Reduced Dust Collection Efficiency
If the fan/motor is properly functioning, but the unit exhibits reduced airflow the
issue may be the result of the following cause and may require filter change.
Possible Cause
Solution
Integrated Filter is fully loaded
Clean or Replace Integrated Filter
10.5 Filter Change Indicator Light Flashing
If the unit is properly functioning and the Filter Change indicator light is flashing,
the default filter change timer has expired, and the filter should be replaced.
Possible Cause
Solution
Filter change cycle timer expired
Replace filter and reset timer