53
Table 25.
Airflow Balancing - Reference ERV5-175-TPD
Speed 5 (factory setting)
Speed 4
Speed 3
Pressure Drop
Fresh AIr
Stale Air
Pressure Drop
Fresh AIr
Stale Air
Pressure Drop
Fresh AIr
Stale Air
1.220
304
85
40
72
34
1.110
277
43
20
1.230
306
82
39
69
33
1.120
279
42
20
1.240
309
80
38
67
32
1.130
282
40
19
1.250
311
77
36
64
30
1.260
314
75
35
61
29
1.270
316
72
34
58
27
1.280
319
70
33
56
26
1.290
321
68
32
53
25
1.300
324
65
31
50
24
1.310
326
63
30
47
22
1.320
329
60
28
45
21
1.330
331
58
27
42
20
1.340
334
55
26
39
18
1.350
336
53
25
1.360
339
51
24
1.370
341
48
23
1.380
344
46
22
1.390
346
43
20
1.400
349
41
19
Sequence of Operations
Check
connections &
confirm 12VAC
on red & green
wires
LED
OFF
LED
ON
ON/OFF
LED status &
Dehumidistat
LED.
NO
LED
Wall control 80% LED (top
LED) flashes to indicate
revision, then flashes until
communications is
established
SYSTEM
POWER ON
HRV fan running
according to
dehumidistat
setting, otherwise
low speed
No
communications;
check yellow
wire connections
Press ON/OFF
fan button
Failed wall control
LED
OFF
LED
ON
ERV/ HRV fan operation,
either high or low
speed
Failed ERV/HRV
controller/ Auto
Transformer
NONE
Dehumidistat
override
Normal
operation
LOW
SPEED
HIGH
SPEED
Dehumidistat
LED flashing
NO
FAN
OFF
FAN
ON
Normal operation
YES
Press ON/OFF
fan button
Normal
operation
STROBING
operation
verified
issue detected;
action required
KEY
Figure 52. ERV /HRV Operational Flowchart
NO
YES
NO
Refer to interface
operation instructions.
Fan may operate based
on interface settings.
Interface
control with ON/OFF
connected
Jumper ON to
RED plus LOW
Standby mode
jumper ON toRED
2
Jumper ON to
RED plus HI
Jumper ON to
RED plus BLK
No fan
operation. Damper
in recirculation
position
FAN
ON
FAN
OFF
YES
Fan override
to a higher speed from
interface control
Is
Humidity Disable
activated by outdoor
temperature
YES
NO
YES
3
Low Fan operation can be overridden to higher speeds by an external control setting or function such as:
A) Y2169 20/40/60 minute timer manually activated − running speed 5
B) Y2168 20 minute timer manually activated − running speed 5
C) Y2166 climate control with dehumidistat activated by humidity level − running speed 5
D) Defrost mode auto-activated function − running speed 4 (HRV only)
Standby mode ˘ Jumper 2 (ON) to 3 (RED)
Low speed fan ˘ Jumper 2 (ON) to 3 (RED) to 1 (LOW)
HI speed fan ˘ Jumper 2 (ON) to 3 (RED) to 6 (BLK)
High Speed Overrides
Fan in
LOW speed
ventilation
Fan in
HIGH speed
ventilation
NO
Normal
operation
Failed
HRV/ERV
controller
No FAN
operation
NO
NO
YES
YES
YES
NO
YES
NO
NOTES − Operation of HRV/ERV
without external control:
Terminal 1 LOW
Terminal 2 ON
Terminal 3 RED
Terminal 4 YEL
Terminal 5 GND
Terminal 6 HIGH
Terminal 7 COM
Terminal 8 NO
Terminal 9 NC
Terminal 10 BLK
issue detected;
action required
KEY
operation
verified
Figure 53. Terminal Block Operation