Table 21. 

Airflow Balancing - Reference HRV5-200-TPD

Speed 5 (factory setting)

Speed 4

Speed 3

Pressure Drop

Fresh Air

Stale Air

Pressure Drop

Fresh Air

Stale Air

Pressure Drop

Fresh Air

Stale Air

in. w.g.

Pa

cfm

L/s

cfm

L/s

in. w.g.

Pa

cfm

L/s

cfm

L/s

in. w.g.

Pa

cfm

L/s

cfm

L/s

0.500

125

220

104

233

110

0.400

100

174

82

188

89

0.300

75

167

79

175

83

0.510

128

217

102

230

109

0.410

103

171

81

185

87

0.310

78

163

77

172

81

0.520

130

214

101

227

107

0.420

105

168

79

182

86

0.320

80

160

76

169

80

0.530

133

210

99

224

106

0.430

108

164

77

179

84

0.330

83

156

74

165

78

0.540

135

207

98

221

104

0.440

110

161

76

176

83

0.340

85

153

72

162

76

0.550

138

204

96

218

103

0.450

113

158

75

173

82

0.350

88

149

70

159

75

0.560

140

201

95

215

101

0.460

115

155

73

171

81

0.360

90

146

69

156

74

0.570

143

197

93

213

101

0.470

118

152

72

168

79

0.370

93

143

67

153

72

0.580

145

194

92

210

99

0.480

120

149

70

165

78

0.380

95

140

66

151

71

0.590

148

191

90

207

98

0.490

123

146

69

162

76

0.390

98

136

64

148

70

0.600

150

188

89

204

96

0.500

125

143

67

160

76

0.400

100

133

63

145

68

0.610

153

185

87

201

95

0.510

128

140

66

157

74

0.410

103

130

61

142

67

0.620

155

182

86

198

93

0.520

130

137

65

154

73

0.420

105

127

60

139

66

0.630

158

179

84

195

92

0.530

133

134

63

152

72

0.430

108

124

59

136

64

0.640

160

176

83

192

91

0.540

135

131

62

149

70

0.440

110

121

57

134

63

0.650

163

173

82

190

90

0.550

138

128

60

146

69

0.450

113

118

56

131

62

0.660

165

170

80

187

88

0.560

140

125

59

144

68

0.460

115

115

54

128

60

0.670

168

167

79

184

87

0.570

143

122

58

141

67

0.470

118

112

53

125

59

0.680

170

164

77

181

85

0.580

145

120

57

139

66

0.480

120

109

51

123

58

0.690

173

161

76

179

84

0.590

148

117

55

136

64

0.490

123

107

50

120

57

0.700

175

158

75

176

83

0.600

150

114

54

134

63

0.500

125

104

49

118

56

0.710

178

155

73

173

82

0.610

153

112

53

131

62

0.510

128

101

48

115

54

0.720

180

152

72

171

81

0.620

155

109

51

129

61

0.520

130

99

47

113

53

0.730

183

149

70

168

79

0.630

158

106

50

126

59

0.530

133

96

45

110

52

0.740

185

146

69

165

78

0.640

160

104

49

124

59

0.540

135

93

44

108

51

0.750

188

144

68

163

77

0.650

163

101

48

121

57

0.550

138

91

43

105

50

0.760

190

141

67

160

76

0.660

165

99

47

119

56

0.560

140

88

42

103

49

0.770

193

138

65

158

75

0.670

168

96

45

117

55

0.570

143

86

41

100

47

0.780

195

135

64

155

73

0.680

170

94

44

114

54

0.580

145

84

40

98

46

0.790

198

133

63

152

72

0.690

173

91

43

112

53

0.590

148

81

38

96

45

0.800

200

130

61

150

71

0.700

175

89

42

110

52

0.600

150

79

37

93

44

0.810

203

127

60

147

69

0.710

178

87

41

107

50

0.610

153

77

36

91

43

0.820

205

125

59

145

68

0.720

180

84

40

105

50

0.620

155

74

35

89

42

0.830

208

122

58

142

67

0.730

183

82

39

103

49

0.630

158

72

34

87

41

0.840

210

119

56

140

66

0.740

185

80

38

101

48

0.640

160

70

33

85

40

0.850

213

117

55

138

65

0.750

188

78

37

99

47

0.650

163

68

32

82

39

0.860

215

114

54

135

64

0.760

190

76

36

96

45

0.660

165

66

31

80

38

0.870

218

112

53

133

63

0.770

193

73

34

94

44

0.670

168

64

30

78

37

0.880

220

109

51

130

61

0.780

195

71

34

92

43

0.680

170

62

29

76

36

0.890

223

107

50

128

60

0.790

198

69

33

90

42

0.690

173

60

28

74

35

0.900

225

104

49

126

59

0.800

200

67

32

88

42

0.700

175

58

27

72

34

0.910

228

102

48

123

58

0.810

203

65

31

86

41

0.710

178

56

26

70

33

0.920

230

99

47

121

57

0.820

205

63

30

84

40

0.720

180

55

26

68

32

0.930

233

97

46

119

56

0.830

208

61

29

82

39

0.730

183

53

25

66

31

0.940

235

95

45

116

55

0.840

210

59

28

80

38

0.740

185

51

24

65

31

0.950

238

92

43

114

54

0.850

213

57

27

78

37

0.750

188

49

23

63

30

0.960

240

90

42

112

53

0.860

215

56

26

76

36

0.760

190

48

23

61

29

0.970

243

88

42

110

52

0.870

218

54

25

74

35

0.770

193

46

22

59

28

Refer to “Installer Selectable High Speed Settings” on page 37 in this manual for more information. 

Содержание ERV5-130

Страница 1: ...ATORS INSTALLATION INSTRUCTIONS AND HOMEOWNER GUIDE FOR HEALTHY CLIMATE ENERGY RECOVERY VENTILATOR ERV AND HEAT RECOVERY VENTILATOR HRV HRV5 150 HRV3 195 HRV3 150 TPD HRV5 200 TPD HRV6 HEX095 TPD HRV5...

Страница 2: ...Methods Fully Dedicated 26 Unit Installation Location 27 Suspending the Unit 27 Installing the ERV5 130 28 Installing the Drain Connection 28 Installing Optional Plug ERV5 150 TPD and ERV5 175 TPD Un...

Страница 3: ...ation HRV5 150 17Y58 Heat Recovery Ventilation HRV5 200 TPD 17Y62 Heat Recovery Ventilation HRV6 HEX095 TPD 17Y52 Heat Recovery Ventilation HRV5 270 TPD ECM 17Y53 Heat Recovery Ventilation ERV5 130 17...

Страница 4: ...rovide fresh air while ex hausting an equal amount of stale air Refer to Application Map ERV HRV Ventilators on page 59 ENERGY RECOVERY VENTILATOR ERV The ERV unit is equipped with an enthalpic core T...

Страница 5: ...114 108 51 108 51 104 49 129 61 0 8 200 89 42 121 57 49 23 235 111 83 39 102 48 93 44 117 55 0 9 225 76 36 108 51 227 107 57 27 95 45 83 39 106 50 1 0 250 57 27 93 44 220 104 87 41 74 35 93 44 Adjuste...

Страница 6: ...upply Exhaust MERV6 or MERV13 To be ordered separately Comes in a set of 4 and is installed in the Fresh Side only When a MERV 13 filter is installed for the first time airflow will need to be balance...

Страница 7: ...114 54 144 68 161 76 95 46 209 100 142 67 100 48 100 48 128 60 0 2 50 105 50 130 61 141 67 90 43 198 95 136 64 96 46 98 47 115 55 0 3 75 92 43 120 57 123 58 80 38 185 89 127 60 92 44 90 43 101 49 0 4...

Страница 8: ...wer Duct Connections 7 in 178 mm Duct Connections 6 in 152 mm RECIRCULATING DEFROST DAMPER FILTERS STALE AIR FROM INSIDE CONDENSATE DRAINS BALANCING DAMPER FRESH AIR TO INSIDE STALE AIR TO OUTSIDE NOT...

Страница 9: ...NDENSATE DRAINS CORE FILTERS BLOWER Figure 2 ERV 175 TPD HRV5 200 TPD AND HRV5 270 TPD ECM 17 1 4 in 438 mm in 3 mm Front View Top View Fresh Air From Outside Stale Air To Outside Fresh Air To Inside...

Страница 10: ...636 mm is recommended for servicing unit 25 3 4 654 All duct connections are oval collars for use with 5 in 150 mm ductwork 9 3 4 248 MOTORIZED IMPELLERS CORE FILTERS DEFROST DAMPER Figure 4 ERV5 130...

Страница 11: ...s in defrost for 4 5 min utes and runs in ventilation for 17 minutes At 31 F 35 C ERV HRV runs in defrost for 7 min utes and runs in ventilation for 15 minutes No remote device can override this defro...

Страница 12: ...not applicable if your HRV is con nected to a forced air system This mode is useful when Continuous Ventilation mode is providing too much ventilation 20 Minutes On 40 Minutes Standby This mode of op...

Страница 13: ...E 62 2 compliant mode Non ASHRAE compliant mode Environmental over rides uses outdoor temperature and outdoor dew point within a set parameter range Timed mode Runs ventilation equipment for a timed a...

Страница 14: ...Wire Jumper required between ON and RED terminals 2 ACC1 is high speed for single speed units 3 Wiring connections between E30 and non communicating indoor unit will be application specific Figure 9 i...

Страница 15: ...ration set up for a ASHRAE Compliant CFM rate at low speed VENTILATION CONTROL MODES The following tables provides a quick reference to which parameters are applicable to specific equipment Table 1 Ve...

Страница 16: ...ts is Whole House Ventilation which is exhausting stale indoor air and replacing it with fresh outdoor air The exhaust fan dilutes the air in the main living spaces with outside air to remove unavoida...

Страница 17: ...ilation does not run When locked out due to high outdoor temperature it will become unlocked when either the outdoor temperature is missing or when the temperature reported is 1 F less than the Ventil...

Страница 18: ...arameter range is 60 to 115 F Default is 100 F Can be adjusted in increments of 5 F While the outdoor temperature is equal to or higher than the setting for Ventilation High Outdoor Temperature Limit...

Страница 19: ...next to the item just set How the Dehumidistat Works When using either an H C ERV HRV Ventilation Push But ton Control Y8249 or H C ERV HRV Deluxe Ventilation Control Y8250 a built in dehumidistat is...

Страница 20: ...cription Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After a few seconds the Dehumid istat light will either flash or be o...

Страница 21: ...nstruction for a detailed description of the Dehumidistat function Reset Button RESET The RESET button will clear the current Fan Timer Mode and Dehumidistat settings and set the unit into LOW fan spe...

Страница 22: ...lation Meth ods Partially Dedicated on page 24 Fully dedicated installation See Installation Methods Fully Dedicated on page 25 SIZING THE DUCTWORK The installer must ensure all ductwork is sized and...

Страница 23: ...nit specifications for exact port locations Unit is normally balanced on HIGH speed with the furnace blower ON A minimum separation of 40 one meter is recommended between the two direct connections Th...

Страница 24: ...ERV HRV operation be interlocked with the furnace blower to evenly distribute the fresh air throughout the house Refer to building code The duct configuration may change depending on the ERV HRV model...

Страница 25: ...distribute the fresh air throughout the house Refer to Interlocking ERV HRV Blower to Air Handler Furnace Blower on page 33 Key Points The ERV HRV must be balanced The duct configuration may change de...

Страница 26: ...ed Suspending the Unit This is a procedure for suspending the unit using adjustable hanging straps Use four screws and washers field provid ed to attach the hanging straps The washer must be wider tha...

Страница 27: ...d below the HRV door with a minimum of per foot downward slope away from unit All ERV HRV cabinets except ERV5 130 have pre punched holes for the drain as illustrated in Figure 28 Drain Holes and P Tr...

Страница 28: ...xible or rigid insulated duct must be clamped to the sleeve of the weatherhoods as close to the outside as possible and the appropriate port on the ERV HRV It is very important that the fresh air inta...

Страница 29: ...ollar to belt 3 Slide insulated flexible or rigid ducting over the galvanized sleeve of the weatherhood and fasten to the thermal collar 4 Hood is hinged to allow for easy access for cleaning screen H...

Страница 30: ...e of the control in the desired location on the wall and pencil mark the top and bottom screw holes Figure 34 Boxes E or F For mounting the control without a decorative plate break off top and bottom...

Страница 31: ...mode Figure 35 Box E 4 Keep the timer within 16 406 mm of the main wall control when pairing 5 Install the battery in the wireless timer All four lights on the Timer will immediately flash five times...

Страница 32: ...he repeater may now be unplugged and moved to its permanent location To pair additional repeaters with the same wall control re peat steps 1 5 until all repeaters have been paired When installed in it...

Страница 33: ...Electrical Connections Plug the ERV HRV directly into a standard designated 120VAC electrical outlet Use of an extension cord is NOT RECOMMENDED for this appliance If further wiring is required then a...

Страница 34: ...or timers and or dry contact controls 1 2 3 4 5 6 7 8 9 10 LOW RED YEL GRN HI COM NO NC BLK LOW SPEED OR HIGH SPEED DEHUMIDISTAT Figure 41 Adding Dry Contact Controls IMPORTANT The ERV HRV must have a...

Страница 35: ...D AUTO TRANSFORMER NOTE If any of the original wire supplied with the unit must be replaces use only TEW certified wire IMPORTANT Control low voltage is 12VAC DO NOT CONNECT EXTERNAL POWER SOURCE TO T...

Страница 36: ...36 Figure 43 Wiring Diagram HRV5 270 TPD ECM...

Страница 37: ...nual for the air flow rates for speeds 5 4 and 3 The factory setting is high speed 5 NOTE Low speed is not adjustable Table 18 High Speed Settings Description Switch Position 1 Switch Position 2 Switc...

Страница 38: ...ng Gauge Attachments Common gauge attachments for measuring ERV HRV air flows are The Pitot Tube This will measure the airflow in the ductwork for any ERV HRV Door Port Gauge Tube Set This will measur...

Страница 39: ...ntil both ducts show identical readings 5 Upon completion of balancing seal the holes foil tape recommended Damper Figure 48 Balancing Damper BALANCING DAMPERS Balancing Dampers are located in the rou...

Страница 40: ...nd of a large drill bit etc 4 Close the HRV Door Initiate power and operate the HRV on high speed Operate the forced air system on high speed if the HRV is connected to the forced air system 5 Measure...

Страница 41: ...56 0 53 132 87 41 0 72 179 146 69 0 53 132 116 55 0 54 135 85 40 0 73 182 144 68 0 54 135 114 54 0 55 137 83 39 0 74 184 142 67 0 55 137 113 53 0 56 140 126 60 81 38 0 75 187 140 66 0 56 140 111 52 0...

Страница 42: ...88 219 43 20 1 07 267 116 126 77 36 0 88 219 74 35 56 26 0 89 222 42 20 1 08 269 113 127 75 35 0 89 222 71 34 54 26 0 90 224 41 19 1 09 272 109 128 73 34 0 90 224 69 33 52 25 0 91 227 40 19 1 10 274 1...

Страница 43: ...36 131 62 0 110 28 78 37 129 61 0 110 28 79 37 140 66 0 115 29 79 37 135 64 0 115 29 80 38 133 63 0 115 29 82 39 145 68 0 120 30 81 38 138 65 0 120 30 83 39 137 65 0 120 30 84 40 149 70 0 125 31 84 40...

Страница 44: ...70 0 290 73 156 74 0 290 73 165 78 0 295 74 150 71 0 295 74 158 75 0 295 74 167 79 0 300 75 152 72 0 300 75 160 76 0 300 75 170 80 0 305 76 154 73 0 305 76 162 76 0 305 76 173 82 0 310 78 156 74 0 31...

Страница 45: ...5 104 49 118 56 0 710 178 155 73 173 82 0 610 153 112 53 131 62 0 510 128 101 48 115 54 0 720 180 152 72 171 81 0 620 155 109 51 129 61 0 520 130 99 47 113 53 0 730 183 149 70 168 79 0 630 158 106 50...

Страница 46: ...2 18 32 15 43 20 1 080 2 70 64 30 86 41 0 980 2 45 36 17 54 25 0 880 2 20 31 15 42 20 1 090 2 73 62 29 84 40 0 990 2 48 34 16 52 25 0 890 2 23 30 14 40 19 1 100 2 75 60 28 82 39 1 000 2 50 33 16 51 2...

Страница 47: ...172 81 170 80 1 540 384 290 137 277 131 1 080 269 223 105 215 101 0 870 217 170 80 168 79 1 560 389 287 135 275 130 1 090 272 221 104 214 101 0 880 219 168 79 165 78 1 580 394 283 134 272 128 1 100 2...

Страница 48: ...5 factory setting Speed 4 Speed 3 Pressure Drop Fresh Air Stale Air Pressure Drop Fresh Air Stale Air Pressure Drop Fresh Air Stale Air in w g Pa cfm L s cfm L s in w g Pa cfm L s cfm L s in w g Pa c...

Страница 49: ...2 0 550 137 55 26 53 25 0 560 139 80 38 81 38 0 560 139 67 32 65 31 0 560 139 54 25 52 25 0 570 142 79 37 80 38 0 570 142 65 31 64 30 0 570 142 52 25 51 24 0 580 144 78 37 79 37 0 580 144 64 30 63 30...

Страница 50: ...232 118 56 0 710 177 94 0 680 169 88 42 65 31 0 940 234 115 54 0 720 179 93 0 690 172 85 40 64 30 0 950 237 113 53 0 730 182 127 60 91 0 700 174 82 39 62 29 0 960 239 162 76 111 52 0 740 184 124 59 89...

Страница 51: ...970 242 64 30 48 1 200 299 78 37 59 28 0 980 244 62 29 46 1 210 302 76 36 57 27 0 990 247 60 28 44 1 220 304 73 34 55 26 1 000 249 59 28 42 1 230 306 70 33 53 25 1 010 252 57 27 40 1 240 309 68 32 50...

Страница 52: ...48 0 650 162 89 42 86 41 0 940 234 153 72 149 70 0 830 207 104 49 98 46 0 660 164 87 41 84 40 0 950 237 150 71 146 69 0 840 209 101 48 96 45 0 670 167 85 40 81 38 0 960 239 148 70 143 67 0 850 212 99...

Страница 53: ...operation STROBING operation verified issue detected action required KEY Figure 52 ERV HRV Operational Flowchart NO YES NO Refer to interface operation instructions Fan may operate based on interface...

Страница 54: ...nces and resets upon power up of HRV ERV 3 4 YES NO Is external control operating HRV ERV fan at HIGH speed YES Humidity sampling may execute during HIGH speed override or extend HIGH speed override u...

Страница 55: ...ehumidistat at the desired level Humidity levels are too high condensa tion is appearing on windows Dehumidistat set too high ERV HRV unit is undersized to handle a hot tub indoor pool etc Occupant Li...

Страница 56: ...Y9956 Y2162 Y2162 MERV 13 Filter Set 4 20A91 20A91 21V13 20A90 29A91 29A91 Motor Capacitor N A Y2145 Y5437 N A N A N A Y9951 N A N A Motor Top Port Models Y5438 N A N A Y6450 Y9952 Y9953 N A Y6450 Y54...

Страница 57: ...cuit board leading to the motor and pull wires to remove from the electrical box 7 Remove assembly blower motor blower panel by sliding left and down 1 2 3 4 6 5 7 Figure 58 Removing Blower Assembly I...

Страница 58: ...a damp cloth to remove dirt bugs and any debris 4 Install clean core as follows a A Install the bottom flange of the core guide into the bottom H channel approximately 1 4 6 mm b Install the left or...

Страница 59: ...and temperature are moderated by HRV or ERV ZONE 5 Arid Climate Hot and Dry HRV HRV will transfer energy summer and winter With little moisture to transfer an ERV is not needed ZONE 6 Gulf Region Hot...

Страница 60: ...60...

Отзывы: