H B X Z O N - 0 5 0 0 Z o n e C o n t r o l
V e r s i o n 2 . 2 0
Zone-0500 Manual Page 5
DIN RAIL INSTALLATION
1 x Terminal
Screwdriver (3.0mm)
The ZON-0500 is designed to be wall mounted, DIN rail mounted, or installed inside a separate electrical enclo-
sure. The unit should be mounted inside and be protected from falling water and high humidity conditions. With
all the covers in place it is designed to protect any individual from accidental electrical shock.
INSTALLATION PROCEDURE
Place the CPU-1000 (or ECO-1000) and desired Expansion Modules on a flat surface. Align the 32-Pin connec
-
tor into the holes on the Expansion Module and gently push into place. Next slide the CPU-1000 onto the 32-Pin
connection by carefully matching up the holes and pins. When installed correctly there is virtually no gap be-
tween units. With power applied to the assembly, the first (green) LED should be illuminated on each Expansion
Module. This lit, green LED serves as confirmation of both electrical and communications continuity.
When used as an expansion module, the ZON-0500 must be enabled in the ‘Control Options’ menu.
32-Pin Connector
P / N 033-0037
(Included)
(Included)
Certified to CSA C22.2 No 24
Conforms to UL Standard 873
CAUTION,
RISK OF ELECTRICAL SHOCK -
DISCONNECT POWER PRIOR TO SERVICING
Relays: 240VAC 10A
Output: 4-20mA/1-10V/PWM
Demand Signal: 20-240V
Model: MOD-0100
MOD-0100
Modulating Module
ZON-0500
Zone Module
ZON-0500
Input: 120VAC 16A Max
Output: 24VAC 6w Max
Zone Relays: 120VAC 5A
Demand Signal: Dry/24VAC
Demand Relays: 24VAC 2A
ZON-0500
Zone Module
ZON-0500
Input: 120VAC 16A Max
Output: 24VAC 6w Max
Zone Relays: 120VAC 5A
Demand Signal: Dry/24VAC
Demand Relays: 24VAC 2A
on
on
Front
Rear