H B X   Z O N - 0 5 0 0   Z o n e   C o n t r o l

V e r s i o n   2 . 2 0

 

  Zone-0500 Manual Page 3

Specifications:

4 x Thermostat Input Dry or 24VAC

2 x 24VAC output power 6VA Max

2 x Demand output relays 24VAC 2A

4 x Zone Relay 120VAC 5A

      

Input 120VAC 16A Max

1 x Pump Relay 120VAC 5A

Combined relay power should not exceed 20A

Weight:

0.408Kg

Dimensions:

100mm W x 168mm H x 70mm D

ETL Listings:

Meets CSA C22.2 No. 24

Meets UL Standard 873

ETL Control No. 3068143

Storage:

10ºC to 40ºC

on 

on

70mm

(2.76’’)

66mm

(2.60’’)

17

Side View

Front View

Rear View

Top View

168mm

(6.61’’)

100mm 
(3.94’’)

63.2mm

(2.49’’)

86mm 
(3.39’’)

Bottom View 

TECHNICAL DATA AND DIMENSIONS

TECHNICAL DATA

DIMENSIONS

Содержание ZON-0500

Страница 1: ...HBX Control Systems Inc Installation Manual ZON 0500 Version 2 30 ZON 0500 Zone Control...

Страница 2: ...o n t r o l V e r s i o n 2 2 0 Table of Contents TABLE OF CONTENTS Introduction 1 3 Safety Symbols Warnings 1 Receipt Inspection 1 Description 2 Technical Data and Dimensions 3 Wiring Installation 4...

Страница 3: ...h caution Moderate Hazard This action may cause personal injury or have adverse effects on the installation process if handled incorrectly Disconnect Power Source The presence of low voltage 24VAC or...

Страница 4: ...alone unit Expandable to 36 zones Provides pump or valve control Boiler enable TT contacts 2 demand outputs Heat Cool or TT DHW Multiple priority selections see page 7 Heating zones will not open or...

Страница 5: ...Input 120VAC 16A Max 1 x Pump Relay 120VAC 5A Combined relay power should not exceed 20A Weight 0 408Kg Dimensions 100mm W x 168mm H x 70mm D ETL Listings Meets CSA C22 2 No 24 Meets UL Standard 873...

Страница 6: ...se outputs are used to power the thermostats and are rated for 24VAC at 6VA Zone 4 Thermostat Zone 3 Thermostat Zone 2 Thermostat Zone 1 Thermostat Demand Output DHW or Heating Demand Output Boiler TT...

Страница 7: ...and pins When installed correctly there is virtually no gap be tween units With power applied to the assembly the first green LED should be illuminated on each Expansion Module This lit green LED ser...

Страница 8: ...zone post purge time Dip switches 2 5 on the right set of dip switches correspond to zones 1 4 and dipswitch 1 is used to modify the type of demand signal sent to the main controller when used as an...

Страница 9: ...er a period of 60 seconds OFF No dual zone priority ON Dual Zone Priority This dip switch position allows the user to set dual zone priority for zones 1 and 2 over zones 3 and 4 NOTE Dip switchs 2 and...

Страница 10: ...es Dip Switch 2 5 Use As Heating OR Cooling Demands Use this configuration with ECO units Dip Switch 2 5 Use As Low Temp OR High Temp Demands Use this configuration with CPU units OFF This position wi...

Страница 11: ...ter DHW Priority Dip Switch 2 5 Heat Demand Zone Dip Switch 2 5 Low High Temperature Zone OFF No DHW priority ON This Dip Switch allows the zone controls to receive a DHW priority from the CPU 1000 If...

Страница 12: ...e zone for heating ON This setting will allow the user to set up the zone for cooling WWSD will shut off heating zones CWSD will shut off cooling zones OFF This setting will allow the user to set up t...

Страница 13: ...RL 8 7 1 RL 1 RL 6 5 1 RL 1 RL 4 3 1 RL 1 RL 2 1 1 2 2 1 2 TT CD 2 4 3 2 DHW HD 2 TH 6 5 2 TH 2 TH 8 7 2 TH 2 TH 10 9 2 TH 2 TH 12 11 2 TH 2 24V AC 14 13 2 2 3 4 1 2 3 4 5 1 Demand Outputs Thermostat...

Страница 14: ...5 2 TH 2 TH 4 3 3 Thermostat RL 1 RL 2 1 1 2 A DO NOT CONNECT POWER HERE THM 0100 HBX 2 24V AC 6 5 2 TH 2 TH 4 3 3 Thermostat RL 1 RL 2 1 1 2 A DO NOT CONNECT POWER HERE System Pump Zone 1 Zone 2 Zone...

Страница 15: ...A 24 VAC out to thermostats 6VA Max 2 24V AC 16 15 2 GR 120 15 N L 14 13 RL 1 RL 12 11 1 RL 1 RL 10 9 1 RL 1 RL 8 7 1 RL 1 RL 6 5 1 RL 1 RL 4 3 1 RL 1 RL 2 1 1 2 2 1 2 TT CD 2 4 3 2 DHW HD 2 TH 6 5 2...

Страница 16: ...ZON 0500 HBX Zone Control DO NOT CONNECT POWER HERE 5A 5A 5A 5A 5 A 24 VAC out to thermostats 6VA Max 2 24V AC 16 15 2 GR 120 15 N L 14 13 RL 1 RL 12 11 1 RL 1 RL 10 9 1 RL 1 RL 8 7 1 RL 1 RL 6 5 1 R...

Страница 17: ...HD 2 TH 6 5 2 TH 2 TH 8 7 2 TH 2 TH 10 9 2 TH 2 TH 12 11 2 TH 2 24V AC 14 13 2 2 3 4 1 2 3 4 5 1 Demand Outputs Thermostat Imputs 1 2 DS 1 DS 1 3 4 DS 2 DS 2 5 6 DS 3 DS 3 GR 120 28 N L 27 26 GR 120 2...

Страница 18: ...HP 2 1 2 DS 1 DS 1 3 4 DS 2 DS 2 5 6 DS 3 DS 3 GR 120 28 N L 27 26 GR 120 25 N L 24 23 GR 120 22 N L 21 20 GR 120 19 N L 18 17 RL 2 RL 16 15 2 RL 1 RL 14 13 1 TM 3 TM 12 11 3 TM 2 TM 10 9 2 TM 1 TM 8...

Страница 19: ...chasers sole remedy shall be at HBX s option repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by ope...

Страница 20: ...HBX Control Systems Inc 2016 Phone 1 403 720 0029 Fax 1 403 720 0054 Email info hbxcontrols com Web www hbxcontrols com HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2...