H B X   E C O - 0 5 5 0   G e o t h e r m a l   C o n t r o l

V e r s i o n   1 . 1 1

Table of Contents

HBX ECO-0550 GEOTHERMAL CONTROLLER

INTRODUCTION

This manual will help with the installation, parameter setting, troubleshooting 

and general maintenance requirements for the controller. To guarantee the 

safe and reliable operation of this control, you must first read this manual in 

detail and take particular note to any and all warnings or caution directives 

prior to connecting to AC power.

Please consult and install the geothermal appliance in accordance with 

manufacture’s recommendations.

DESCRIPTION

The ECO-0550 is designed to be a stand-alone Outdoor Reset Control 

device.  The purpose and function of the ECO-0550 is to provide control for 

Geothermal applications. It can manage single tank applications as well as 

applications with seperate hot and cold tanks.

SAFETY SYMBOLS & WARNINGS

Extreme Hazard

This action poses a serious threat that could 

result in personal injury or death, as well as 

permanent damage to the equipment.  

 

 

  Proceed with caution.

Moderate Hazard

This action may cause personal injury or have 

adverse effects on the installation process if 

handled incorrectly.

Disconnect Power Source

The presence of low voltage(24VAC) or high 

voltage(120VAC) could result in personal injury 

or permanent damage to components or 

equipment.

Point of Interest

This  point  clarifies  pertinent  information,  or 

brings your attention to an action that may 

have adverse effects on the installation 

process.

Drawing Reference

Refer to the specified electrical or mechanical 

drawing at the back of the manual.

Only  suitably  qualified  individuals  with  formal 

training in electrical and Geothermal controls 

should attempt the installation of this equipment.  

Incorrect wiring and installation will affect the 

warranty provided with this unit.  Wiring must be 

completed in accordance with the codes and 

practices applicable to the jurisdiction for the  

           actual installation.

Use only copper conductor supply wire suitable 

for at least 105 °C

The HBX ECO-0550 is a microprocessor based 

controller and as such is not to be regarded as a 

safety (limit) control.  Please consult and install 

the heating or cooling appliance in accordance 

with the manufacturer’s recommendations.

RECEIPT & INSPECTION

After receiving, inspect the unit for any possible 

physical damage that may have occurred during 

transportation.

After unpacking the unit make sure the box contains:

•  

1 x Remote Outdoor sensor

 (Part #OUT-0100)

•  

2 x Universal sensors 

(Part #029-0022)

•  

1 x Terminal Screwdriver (2.5mm)

•  

2 x Cable ties

•  

1 x Manual

WARNING:

 This product can expose you to chemicals 

including lead, which is known to the State of California to 

cause cancer and birth defects or other reproductive harm. 

For more information go to www.P65Warnings.ca.gov.

!

Содержание ECO-0550

Страница 1: ...HBX Control Systems Inc Installation Manual Central Processing Unit 0550 Version 2 00 ECO 0550 ...

Страница 2: ...s 1 Receipt Inspection 1 Description 1 QR Code 1 Technical Data and Dimensions 2 Wiring Installation 3 Wiring 3 Installation 3 Programming ECO 0550 4 5 Navigating the ECO 0550 4 Control Mode 4 Setup Menu 5 Geothermal Mode Programming 6 13 Multicolour backlit display 6 Screen Colours 6 Status Screen 6 Heat Pump Setup 7 Tank Setup 8 11 Backup Setup 12 EcoSwitch Energy Clock 13 15 Priority Setup 15 W...

Страница 3: ...ge 24VAC or high voltage 120VAC could result in personal injury or permanent damage to components or equipment Point of Interest This point clarifies pertinent information or brings your attention to an action that may have adverse effects on the installation process Drawing Reference Refer to the specified electrical or mechanical drawing at the back of the manual Only suitably qualified individu...

Страница 4: ...CC ID 2AHMR ESP12S Weight 0 408Kg Dimensions 100mm W x 168mm H x 70mm ETL Listings Meets CSA C22 2 No 24 Meets UL Standard 873 ETL Control No 3068143 Storage 50 F to 104 F 10ºC to 40ºC ECO 0550 Central Processing Unit Relays 240VAC 5A Max Input 120VAC 15A Max ENTER ECO Input Signals 4 Heat Pump Outdoor Sensor 120 VAC Relay Outputs 2 Reversing Valve Tank Sensor 2 66 mm 2 60 in 2 76 in 70 19 mm Side...

Страница 5: ...12 11 1 1 TM 3 2 8 TM TM 7 9 10 BL 1 BL 6 5 1 2A 1 10v DO NOT CONNECT POWER HERE 1 2 DS 1 2 2 DS DS 1 3 4 DO NOT CONNECT POWER HERE DS 5 A RL 2 RL 19 18 2 ECO 0550 Central Processing Unit Demand Input 1 Demand Input 2 Heat Pump Contacts Sensor Inputs Relay 3 Relay 2 Relay 1 Supply Power 120 VAC WIRING AND INSTALLATION Wiring All signal wiring must be with a minimum of 18AWG wire at a maximum of 50...

Страница 6: ...ntrol mode you would like your ECO 0550 to operate in To select your control mode simply use the or buttons to select the correct mode then wait five seconds to accept your selection NAVIGATING THE ECO 0550 All programming steps within the ECO 0550 are achieved by using the three buttons and combination thereof located below the screen The button is used to scroll down in menu screens and decrease...

Страница 7: ...that a parameter has been selected Adjust the setting to the desired value with the or buttons Once the correct value is set push the ENTER button This will deselect the parameter To go to the previous screen push and hold the ENTER button If the SETUP menu is left for more than 90 seconds the display will change to the STATUS screen and the control will resume operation SETUP MENU 2 00 1 HEAT PUM...

Страница 8: ...n is selected the screen color will change to indicate information about the status of the system Screen Colors Light Blue No Heat Demand Red Demand and heat pumps running Heating Mode Green Demand ON no heat pumps running Dark Blue Demand ON and heat pumps running Cooling Mode Purple Demand ON and Backup Only running EcoSwitch Mode 5 A RL 1 RL 15 14 1 5 A RL 2 RL 17 16 2 HBX GR 120 13 N L 12 11 1...

Страница 9: ...STAGING 6 C OR F 1 3m OFF OFF ON F HEAT PUMP SETUP 1 HP STAGES 2 LAG TIME 3 ROTATE TIME 4 ROT CYCLES 5 OFF STAGING 6 C OR F 1 3m OFF OFF ON F HEAT PUMP SETUP 1 HP STAGES 2 LAG TIME 3 ROTATE TIME 4 ROT CYCLES 5 OFF STAGING 1 3m OFF OFF ON HEAT PUMP SETUP Stages This setting will allow you to select the number of heat pump stages that are attached to the control If Backup is being used you can only ...

Страница 10: ...k Setup This setting is used to set the desired temperature in the hot tank when there is a heat demand present Outdoor Temperature Design This is used in the outdoor reset design calculation This option should be set to reflect your specific city or region With this option enabled the Tank Temperature setting will be replaced by Min Tank and Max Tank Temperature settings OFF 0 F to 119 F Default ...

Страница 11: ...n which the ECO 0550 will go into WWSD If the system rises above this temperature the system will be shut off In WWSD the heat pumps and backup boiler will shut off OFF 35 F to 119 F Default 65 F Outdoor Temperature Design This is used in the outdoor reset design calculation This option should be set to reflect your specific city or region OFF 40 F to 120 F Default OFF Hot Tank Differential Set th...

Страница 12: ...NK SETUP 1 CWSD 2 OUTDOOR 3 COLD DIFF 4 MIN TANK TEMP 5 MAX TANK TEMP 75 F 90 F 8 F 45 F 60 F COLD TANK SETUP 1 CWSD 2 OUTDOOR 3 COLD DIFF 4 MIN TANK TEMP 5 MAX TANK TEMP 75 F 90 F 8 F 45 F 60 F COLD TANK SETUP WITHOUT OUTDOOR RESET Cold Weather Shut Down This setting is used to set the temperature in which the ECO 0550 will go into CWSD If the system goes below this temperature the system will be...

Страница 13: ...D DIFF 4 MIN TANK TEMP 5 MAX TANK TEMP 75 F 90 F 8 F 45 F 60 F TANK SETTINGS 1 HOT TANK 2 COLD TANK 3 CWSD WWSD TIME 0H COLD TANK SETUP WITH OUTDOOR RESET COLD WARM WEATHER SHUT DOWN TIME SETUP Cold Weather Shut Down This setting is used to set the temperature in which the ECO 0550 will go into CWSD If the system goes below this temperature the system will be shut off In CWSD the heat pumps will s...

Страница 14: ...me on OFF 2 F to 100 F Default OFF Backup Differential This setting can be used with the backup temperature and backup time or on its own to bring the backup on This setting is used to set a differential on the tank at which you would like the backup to come on This setting will override the backup temperature and backup time settings eg Tank temperature of 115 F and a backup differential of 10 F ...

Страница 15: ... TIME 1 YEAR 2 MONTH 3 DAY 4 DOW 5 HOUR 6 MIN 2017 JUL 5 FRI 10AM 00 SET TIME 1 YEAR 2 MONTH 3 DAY 4 DOW 5 HOUR 6 MIN 2017 JUL 5 FRI 10AM 00 SET TIME 1 YEAR 2 MONTH 3 DAY 4 DOW 5 HOUR 6 MIN 2017 JUL 5 FRI 10AM 00 SET TIME 1 YEAR 2 MONTH 3 DAY 4 DOW 5 HOUR 6 MIN 2017 JUL 5 FRI 10AM 00 SET TIME 1 YEAR 2 MONTH 3 DAY 4 DOW 5 HOUR 6 MIN 2017 JUL 5 FRI 10AM 00 SET TIME 1 YEAR 2 MONTH 3 DAY 4 DOW 5 HOUR ...

Страница 16: ...D SETUP 10 00 am MOUNTAIN ENERGY CLOCK 1 SET TIME 2 TIME ZONE 3 WEEKDAY SETUP 4 WEEKEND SETUP 10 00 am MOUNTAIN ENERGY CLOCK 1 SET TIME 2 TIME ZONE 3 WEEKDAY SETUP 4 WEEKEND SETUP 10 00 am MOUNTAIN ENERGY CLOCK 1 SET TIME 2 TIME ZONE 3 WEEKDAY SETUP 4 WEEKEND SETUP 10 00 am MOUNTAIN ENERGY CLOCK 1 SET TIME 2 TIME ZONE 3 WEEKDAY SETUP 4 WEEKEND SETUP 10 00 am MOUNTAIN ENERGY CLOCK 1 SET TIME 2 TIME...

Страница 17: ... boiler only for weekends Device Set Time 1 4 Adjust the schedule times for your heating devices Time can be adjusted in 15 minute increments Heating Device Options Set which devices will activate at set times Heat Pumps If Heat Pumps selected control will operate Heat Pumps and Backup Boiler Normal Operation as programmed by user until next scheduled time Backup Only If Backup Only selected contr...

Страница 18: ...EADY SETUP WIFI OPEN PHONE SETTINGS AND CONNECT TO THERMOLINX002 NETWORK ONCE CONNECTED OPEN THE APP SYNC CODE AECO 1234 SETUP WIFI 1 PASSWORD 2 SETUP WIFI 3 CONNECTION AB12 READY SYNC CODE AECO 1234 SYNC CODE AECO 1234 SETUP MENU 2 00 1 HEAT PUMPS 2 TANKS 3 BACKUP 4 ENERGY CLOCK 5 PRIORITY 6 WIFI COLD SETUP WIFI 1 PASSWORD 2 SETUP WIFI 3 CONNECTION AB12 READY CHANGE PASSWORD 1 NO 2 YES SETUP WIFI...

Страница 19: ...tacting ThermoLinx and direct you to Wi Fi setup 5 In Wi Fi setup select the Wi Fi network you would like to connect to and enter the password for the Wi Fi network Network name cannot contain more than 30 characters The password should not contain any special characters If using WEP 64bit or 128bit security must not be in Shared Mode If using WEP 128bit the password key must be 26 characters long...

Страница 20: ... 3 Start the HBX ThermoLinx App It will display Contacting ThermoLinx and direct you to Wi Fi setup 4 In Wi Fi setup manually enter personal hotspot device name in network SSID and enter your personal hotspot password Select Connect to WiFi Now Hotspot name will not appear in network list 5 Exit the app and go back into your personal hotspot settings and wait for the ThermoLinx Network to connect ...

Страница 21: ...This is the name of the system location not the ECO 0550 you added Symbols and numbers cannot be used in location name 6 After you have entered the system location name select the location so it is highlighted and select save 100 9 41 AM Devices Locations 83 F No devices None Room Temp Target 100 9 41 AM Add Device 83 Room Name Select Location Add Name Here Leave Blank if device already named Sync...

Страница 22: ...ntral Processing Unit ECO 0550 HBX GR 120 13 N L 12 11 1 1 TM 3 2 8 TM TM 7 9 10 BL 1 BL 6 5 1 2A DO NOT CONNECT POWER HERE 1 2 DS 1 2 2 DS DS 1 3 4 DO NOT CONNECT POWER HERE DS 5 A RL 2 RL 19 18 2 Outdoor THM 0200 HBX RL 2 RL 3 2 2 2 24V AC 10 9 2 TH 2 TH 8 7 3 Thermostat RL 1 RL 5 4 1 2 A DO NOT CONNECT POWER HERE TH 1 6 RL 1 2 A 1 HP 1 Backup Rev Valves System Pump 24VAC MAX Hot Tank Notes Titl...

Страница 23: ...eplaced with the HBX WiFi Zoning System See ZON 0550 Installation Manual at hbxcontrols com resources php Notes This is not an engineered drawing and does not necessarily include all the components for an entire system It is intended as a representative sample of how the control may be wired for a sample application It is the responsibility of the installer to seek professional advice and or insta...

Страница 24: ...ECT POWER HERE TH 1 6 RL 1 2 A 1 HP 1 Backup Rev Valves 24VAC MAX NOTE The THM 0200 Thermostat can be replaced with the HBX WiFi Zoning System See ZON 0550 Installation Manual at hbxcontrols com resources php Hot Tank Cooling Load Cold Tank Cold Tank Sensor Heating Load gineered drawing and does not necessarily include all the components for an entire system It is intended ve sample of how the con...

Страница 25: ...d recommend heat pump limits Heat pumps cycling to frequently Check tank differiental on page 8 10 Check heat pump lag time Backup boilers not coming on Check wiring Check backup settings on page 12 Ensure one backup setting is not set to off Backup boiler taking too long to come on Check backup settings on page 12 No heat or Cool call Check demand inputs on pins 1 2 or pins 3 4 Make sure control ...

Страница 26: ...Check wiring on page 14 Control is WWSD CWSD System pump is not turning on Check wiring on page 14 No heat cool demand Reversing valve is not turning on Check wiring on page 14 Control is WWSD CWSD ECO 0550 TROUBLESHOOTING GUIDE For additional assistance with the ECO 0550 please contact our Technical Support Department toll free at 1 855 410 2341 ...

Страница 27: ...above the purchasers sole remedy shall be at HBX s option repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by operation of law statutory or otherwise including warranties of merchantability and fitness for a particular purpose application HBX neither assumes nor authorizes any other person to assume...

Страница 28: ...tems Inc 2018 Toll Free Technical Support 1 855 410 2341 Phone 1 403 720 0029 Fax 1 403 720 0054 Email info hbxcontrols com Web www hbxcontrols com HBX Control Systems Inc 4516 112th Avenue SE Calgary AB Canada T2C 2K2 ...

Отзывы: