3) BACKUP SETUP
BACKUP SETUP
Backup Time
This setting will be set for the minimum lag time between heat pump stages and the
backup boiler. This is a time delay between the heat pump stages and the backup
boiler. Even if the differential has been exceeded this time must elapse before that
stage can come on.
(
OFF/1m to 240m
) Default:
OFF
Backup Temperature
Set this temperature to the desired outdoor temperature that will allow the backup
to come on. When the temperature resides above this value, the backup will not be
allowed to come on. Only when the Outdoor Temperature falls below this value can
the backup come on.
(
OFF/2°F to 100°F
) Default:
OFF
Backup Differential
This setting can be used with the backup temperature and backup time or on its
own to bring the backup on. This setting is used to set a differential on the tank at
which you would like the backup to come on. This setting will override the backup
temperature and backup time settings.
(eg. Tank temperature of 115°F and a backup differential of 10°F. The backup boiler
will come on at 105°F providing all of the heat pumps are already on.)
(
OFF/2°F to 100°F
) Default:
OFF
SETUP MENU
2.00
1) HEAT PUMPS
2) TANKS
3) BACKUP
4) ENERGY CLOCK
5) PRIORITY
6) WIFI
COLD
BACKUP SETUP
1) BACKUP TIME
2) BACKUP TEMP
3) BACKUP DIFF
OFF
OFF
OFF
BACKUP SETUP
1) BACKUP TIME
2) BACKUP TEMP
3) BACKUP DIFF
OFF
OFF
OFF
BACKUP SETUP
1) BACKUP TIME
2) BACKUP TEMP
3) BACKUP DIFF
OFF
OFF
OFF
Backup Setup
This setting is used to configure the boiler backup component in your system.