Temperature Sensors

The Aqua Plus 16v utilizes 10K ohm thermistor type sensors.  Three sensors (water temperature, air temperature

and solar or dual equipment spa temperature) are included.  If the Aqua Plus 16v is being used to control a solar

heating system, the solar sensor is required.  If dual equipment will be used, the dual equipment spa sensor (spa

temperature for “Pool and Spa-Dual”) is required.   If both solar and dual equipment are desired, another tempera-

ture sensor must be purchased separately. The sensors are provided with a 15 ft. cable.  If a longer cable is

required, contact the Hayward service dept. (908-355-7995) for information on suitable cable types and splices.

See Temperature Sensors on page 6 for directions on installing sensors.

AIR

SENSOR

SOLAR

SENSOR

DUAL EQUIPMENT

SPA SENSOR

POOL/SPA

SENSOR

optional

optional

Wired Remote Display/Keypad

The Aqua Plus 16v main unit can connect to a maximum of 3 remote wired display/keypads.  Wired display/

keypads must be ordered separately.

Use four conductor cable (typically phone cable) to connect the wired remote display/keypad with the Aqua Plus

16v Control Center as shown below.  The maximum wiring distance is 500ft. (160m).  Note that the terminals on

both the Aqua Plus 16v main unit and the wired remote display/keypad are numbered:  Connect 1 to 1, 2 to 2, etc.

Refer to diagram below.

If multiple remote display/keypads are installed:

  Never connect more than 2 wires to any terminal block.  Two

remotes can be wired back to the Aqua Plus 16v main unit or the second display/keypad (and third, if applicable)

can be “daisy chained” with one display/keypad wired to the next.  The maximum wire run from the Aqua Plus 16v

main unit to the furthest remote display/keypad is 500 ft (160m).

19

Accessing the Configuration Menus

Configuring the Aqua Plus 16v requires that you navigate through the Configuration Menu and input various infor-

mation.  For more detailed information about using the Aqua Plus 16v menu system, refer to the Operation Manual.

To access the Configuration Menus

Configuration

Menu-Unlocked

Configuration
Menu-Locked

Press repeatedly until “Configuration Menu” is displayed

 

Move to configuration menu items

Press BOTH buttons SIMULTANEOUSLY for 5 seconds to unlock

NOTE: The configuration menu automatically “locks” after 2 minutes of no buttons being pressed to
prevent unauthorized people from changing the control logic inadvertently and possibly damaging
the pool equipment or causing a “call back” to fix the configuration.

Configuration Menus

Each item needs to be programmed and may contain additional sub-menu items.  Refer to the following pages for

information on programming.

Cell Type

T-CELL-15

Rotates between available Cell types
Move to next menu item

Move to next menu item

Chlorinator

Enabled

Display

Salt

Chlor. Config.

+ to view/change

Toggle between Display Salt (default) and Minerals 

Toggle between Chlorinator Enabled and Disabled (default) 

Move to previous/next configuration menu

Move to next configuration menu

Push to access Chlorinator option

Cell Type

T-CELL-15

Chlorinator

Enabled

Display

Salt

Chlor. Config.

+ to view/change

Chlorinator

The Aqua Plus 16v is shipped with the chlorinator enabled. The cell and flow switch must be installed
and the Aqua Plus 16v will automatically chlorinate both the pool and spa according to the desired
output setting (see Settings Menu in the Operation manual).  If disabled, all displays relating to the
chlorinator will be suppressed.

When the chlorinator is enabled, the Pro Logic will automatically detect and control any Aqua Rite(s)
that is installed in the system.

Display

Allows for the display of salt (default) or mineral values.

Cell Type Selection

The Cell Type Menu appears after “Display Salt/Minerals” in the Chlorinator Configuration Menu.
The options are T-CELL-15 (default), T-CELL-9, T-CELL-5 or T-CELL-3.  Make the proper selection
based on the chlorinator cell that is used in your system. Refer to the information below.

"T-CELL-3" = T-CELL-3, GLX-CELL-3-W
"T-CELL-5" = GLX-CELL-5, GLX-CELL-5-W
"T-CELL-9" = T-CELL-9, GLX-CELL-9-W
"T-CELL-15" = T-CELL-15, GLX-CELL-15-W

Chemistry Config.

 to enter

Press to access Chemistry Config. Wizard
Move to previous/next menu item

Chemistry Configuration Wizard

Requires use of the optional AQL-CHEM Sensing Kit. 

 Following the steps of the Chemistry Config.

Wizard will set up the AQL-CHEM to sense ORP and pH levels and, if the chlorination function is
used, can configure the Pro Logic to generate the correct amount of chlorine to properly sanitize the
pool. Refer to the AQL-CHEM manual for more detailed information.

Wired Remote

Display unit

500 ft max

Connect screw terminals
 “1” to “1”, “2” to “2”, etc.

1

2

3

4

Содержание Aqua Plus 16v PL-PLUS-16V

Страница 1: ...ach wireless remote wireless channel maintenance menu pH calibration wizard clean probe wizard timers menu pool filter 1 or hi speed 1 pool filter 2 or lo speed 1 pool filter 3 or hi speed 2 pool filt...

Страница 2: ...ytotheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Страница 3: ...tion 7 Optional ValveActuators 7 3 Plumbing Standard Pool Spa Configuration 8 Dual Equipment Pool Spa Separate Heaters 9 Dual Equipment Pool Spa Shared Heaters 10 Turbo Cell 11 Flow Switch 11 4 Electr...

Страница 4: ...product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation specialist should be con...

Страница 5: ...olar thermostat settings Chlorinatorsettings DayandTime Timers Menu Timeclockand orCountdowntimersettings Heater Checkout FollowtheseinstructionstoverifythattheAquaPlus16visproperlycontrollingtheheate...

Страница 6: ...the pool per manufacturer s instructions Thisensuresaquick troublefreetransfertotheAquaPlus16vsystem 40 Reset ColorLogic to Default Press Are you sure to proceed ColorLogic reset Confirmed Initiate re...

Страница 7: ...peciallyimportantforretrofitinstallationtoolderpoolswhereallofthe chlorineaddedtothepoolovertimeisendingupassalt Ifthelevelislow determinethenumberofgallonsinthe pool and add salt according to the cha...

Страница 8: ...4 3 0 1 4 3 5 1 6 2 5 1 6 4 5 2 0 5 5 2 5 8 0 3 6 6 5 2 9 9 0 4 1 7 0 3 2 9 5 4 3 7 5 3 4 10 0 4 5 2 0 91 1 3 91 2 0 91 2 8 1 3 2 3 1 1 1 7 1 1 2 7 1 2 3 3 1 5 3 7 1 7 5 3 2 4 4 3 2 0 4 7 2 1 6 3 2 8...

Страница 9: ...r Valve3 Name Waterfall Push to access Valve3 options Rotates between Manual On Off default Countdown Timer Timeclock Solar In floor Cleaner Group and Super Chlorinate Move to previous next configurat...

Страница 10: ...theAQL2 BASE RFforallAQL2wirelessremotecontrols Toinstallthebasestation removetheknockout on the upper left side of theAqua Plus 16v main control unit insert the base station and then tighten the nut...

Страница 11: ...sing kit Aux1 Relay This feature allows the user to select either Standard default Dimmer ColorLogic or VSP type relay for the Aux1 output The optionalAQL DIM dimmer kit must be installed if Dimmer is...

Страница 12: ...ff countdown timer and timeclock functions Move to next menu item Rotates between Manual On Off default Countdown Timer Low Speed Filter Timeclock Solar Low Speed Spa Filter Group Super Chlorinate and...

Страница 13: ...et water flowing when the pool spa suction return valves are in any position other than pool only or for the first 3 minutes after solar turns on allows air in the solar panels to be purged Interlock...

Страница 14: ...e Aux relays If pool lights are wired to the lights relay some options including Solar function Low Speed of a 2 Speed Filter Pump Lights Interlock and Lights Freeze Protection are not applicable and...

Страница 15: ...e between Open and Closed default Move to next menu item or previous next configuration menu External Input The external input device can either be normally open or normally closed In this menu select...

Страница 16: ...ove to next menu item Move to next menu item if Solar is enabled if Solar is enabled Allow Low Speed Disabled Toggle between Enabled and Disabled default Move to next menu item or previous next config...

Страница 17: ...ext configuration menu if Heater1 is enabled if Heater1 is enabled if Heater1 is enabled display for Heater2 if Heater2 is enabled Heater1 Name Gas Heater Rotates between all available names Move to n...

Страница 18: ...Lowest Speed 10 Highest Speed 100 Rotates between 1 speed default 2 speed and variable speed options Toggle between Enabled default and Disabled Freeze Protection Toggle between high speed default and...

Страница 19: ...irst 3 minutes of operation anytime the pump has been off for more than 30 seconds Set highest speed from 20 to 100 default Flow Monitor This feature will help protect the filter pump from damage due...

Страница 20: ...ver the Pool Spa valves are turning The pump will NOT shut off when the heater has Cooldown enabled and is either on or in the Heater Cooldown mode Filter Config to view change Filter Name Pool Filter...

Страница 21: ...actuators should be connected to the Pro Logic Pressing the POOL SPAbutton on the display keypad will allow the homeowner to alternate between pool and spa operation If Pool and Spa Dual is selected...

Страница 22: ...ically locks after 2 minutes of no buttons being pressed to prevent unauthorized people from changing the control logic inadvertently and possibly damaging the pool equipment or causing a call back to...

Страница 23: ...while the Group is running will make the Group release the alternate setpoint control and revert back to the normal heater setting Any changes that are made at that point will affect the normal heater...

Страница 24: ...d dim the patio lights turn on the music etc all at the same time This convenient feature is offered on allAux buttons bothValve buttons and the Lights button TheAqua Plus 16v can be programmed to con...

Отзывы: