4.  Electrical Wiring

The Aqua Plus 16v Control Center.  Low voltage connections will be made to actuators, sensors, remote keypad,

etc.  High voltage connections will be made to pumps, lights, etc., as well as providing direct input power to the

Control Center.  Always:

-Ensure that Power is disconnected prior to doing any wiring

-Follow all local and NEC (CEC if applicable) codes

-Use copper conductors only

Main Service (Power to the Circuit Breaker Subpanel)

The Aqua Plus 16v circuit breaker subpanel is rated for 100A service.  Run properly rated conductors (L1, L2, N,

and ground) from the primary house electrical panel to the main power connections on the Aqua Plus 16v circuit

breaker base.  The connection at the main house panel should be to a 240VAC circuit breaker rated at 100A

maximum.

Grounding and Bonding

Connect a ground wire from the primary electrical panel to the Aqua Plus 16v ground bus bar.  Also ground each

piece of high voltage (120 or 240VAC) equipment that is connected to the Aqua Plus 16v control relays or circuit

breakers.  The Aqua Plus 16v should also be connected to the pool bonding system by an 8AWG (6AWG for

Canada) wire.  A lug for bonding (2 for Canada) is provided on the outside/bottom of the Aqua Plus 16v enclo-

sure.

Circuit Breaker Installation and Wiring

Circuit breakers are to be supplied by the installer.  See the chart below for a list of suitable circuit breakers that

can be used.  Follow the code and the circuit breaker manufacturer’s rating requirements regarding the size and

temperature rating for wiring.  Note that some pool equipment may be required to be connected to ground fault

circuit breakers—check local and NEC (CEC) codes.

General Purpose Outlet

If desired, a duplex receptacle with weatherproof cover (supplied by installer) may be installed in the knockouts on

the lower right side of the Aqua Plus 16v enclosure.  Per code, the receptacle should be a GFCI type.  Alterna-

tively, connect a standard receptacle to a GFCB.

12

Allow Low Speed

This menu only appears if the pool filter is configured for 2-speed operation.  During default operation,
high speed mode is used whenever the solar heater is on.  If Allow Low Speed is enabled, low speed
pump operation will be allowed during solar heating except for the first 3 minutes after solar heat turns
on.

only if optional ColorLogic Network

Module is detected at power up

ColorLogic Config.

+ to view/change

Push to activate ColorLogic options

Move to previous/next configuration menu

ColorLogic Config.

This menu appears if the optional ColorLogic Network Module is installed and detected at power up.
Refer to the AQL-COLOR-MODHV manual for detailed installation and operation instructions.

External Input

Active Closed

Toggle between Open and Closed (default) 
Move to next menu item or previous/next configuration menu

External Input

The external input device can either be normally open or normally closed.  In this menu, select the state
of the external input device when active. For example, if the switch is normally open and closes when
active, set External Input to “Active Closed”.

NOTE: If an AQL-COLOR-MODHV ColorLogic Network Module is detected at startup, only the Lights Name menu will appear

under Lights Configuration. Refer to the AQL-COLOR-MODHV manual for more information.

Lights Config.

+ to view/change

Lights Function

Manual On/Off

Lights Name

Pool Light

Lights Relay

Standard

Push to access Lights options

Rotates between 

Manual On/Off (default), Countdown Timer, Low Speed- Filter,

Timeclock, Solar, Low Speed-Spa Filter, Group, Super Chlorinate, and pH Dispense

Rotates between all available names 

Toggle between Standard (default), Dimmer and VSP 

Move to previous/next configuration menu 

Move to next menu item

Move to next menu item or previous/next configuration menu

Move to next menu item or previous/next configuration menu

Lights Interlock

Disable

Lights Freeze

Disable

Toggle between Enabled and Disabled (default) Lights Interlock

Toggle between Enabled and Disabled (default) Lights Freeze

Move to next menu item

Move to previous/next configuration menu 

for all functions except solar, dimmer relay, super chlorinate
pH dispense, low speed, and group

for all functions except solar, dimmer relay, super chlorinate
pH dispense, low speed, and group

f

 

pH dispense, low speed, and group

or all functions except dimmer relay, super chlorinate

if filter pump is set to variable speed

and the relay type is set to standard

for manual on/off, countdown
timer and timeclock functions

Lights Group

Filter: Unaffected

Lights Group

Timer: None(Manual)

Options available depend on the function that is selected

Rotates between Manual On/Off (default),Countdown Timer and Timeclock

Move to previous/next menu item or next configuration menu

Move to next menu item

for group function only

for group function only

Lights Ext Input

Disabled

Toggle between Enabled and Disabled (default)
Move to previous/next configuration menu

Lights Pump Spd

Settings Menu

Select Settings Menu (default) or desired pump speed (Filter Lowest to Highest)
Move to previous/next configuration menu 

31

Siemens

Murray

Manufacturer

Single Double

Quad

Twin

GFCB Filler Plates

QP

QP

QT

QT

QPF

QF3

SUITABLE LISTED BREAKERS

Tightening

Torque

MP-T

MP-T

MH-T

MH-T MP-GT

LX100FP

25lb-in

25lb-in

8 High Voltage Relays

Control Power Input

Bonding Lug(s)

“Local” Display

Subpanel

Ground Bus Bar

pH Dispense

Output

L2

N

L1

4 Valve Connectors

2 Heater Outputs

External Input Interlock

4 Temp

Sensor Inputs

Flow Switch

Connector

Cell Connector

Wireless Base

Receiver Connector

Remote Display/Keypad

Connector

AQL-CHEM

Connector

Содержание Aqua Plus 16v PL-PLUS-16V

Страница 1: ...ach wireless remote wireless channel maintenance menu pH calibration wizard clean probe wizard timers menu pool filter 1 or hi speed 1 pool filter 2 or lo speed 1 pool filter 3 or hi speed 2 pool filt...

Страница 2: ...ytotheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Страница 3: ...tion 7 Optional ValveActuators 7 3 Plumbing Standard Pool Spa Configuration 8 Dual Equipment Pool Spa Separate Heaters 9 Dual Equipment Pool Spa Shared Heaters 10 Turbo Cell 11 Flow Switch 11 4 Electr...

Страница 4: ...product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation specialist should be con...

Страница 5: ...olar thermostat settings Chlorinatorsettings DayandTime Timers Menu Timeclockand orCountdowntimersettings Heater Checkout FollowtheseinstructionstoverifythattheAquaPlus16visproperlycontrollingtheheate...

Страница 6: ...the pool per manufacturer s instructions Thisensuresaquick troublefreetransfertotheAquaPlus16vsystem 40 Reset ColorLogic to Default Press Are you sure to proceed ColorLogic reset Confirmed Initiate re...

Страница 7: ...peciallyimportantforretrofitinstallationtoolderpoolswhereallofthe chlorineaddedtothepoolovertimeisendingupassalt Ifthelevelislow determinethenumberofgallonsinthe pool and add salt according to the cha...

Страница 8: ...4 3 0 1 4 3 5 1 6 2 5 1 6 4 5 2 0 5 5 2 5 8 0 3 6 6 5 2 9 9 0 4 1 7 0 3 2 9 5 4 3 7 5 3 4 10 0 4 5 2 0 91 1 3 91 2 0 91 2 8 1 3 2 3 1 1 1 7 1 1 2 7 1 2 3 3 1 5 3 7 1 7 5 3 2 4 4 3 2 0 4 7 2 1 6 3 2 8...

Страница 9: ...r Valve3 Name Waterfall Push to access Valve3 options Rotates between Manual On Off default Countdown Timer Timeclock Solar In floor Cleaner Group and Super Chlorinate Move to previous next configurat...

Страница 10: ...theAQL2 BASE RFforallAQL2wirelessremotecontrols Toinstallthebasestation removetheknockout on the upper left side of theAqua Plus 16v main control unit insert the base station and then tighten the nut...

Страница 11: ...sing kit Aux1 Relay This feature allows the user to select either Standard default Dimmer ColorLogic or VSP type relay for the Aux1 output The optionalAQL DIM dimmer kit must be installed if Dimmer is...

Страница 12: ...ff countdown timer and timeclock functions Move to next menu item Rotates between Manual On Off default Countdown Timer Low Speed Filter Timeclock Solar Low Speed Spa Filter Group Super Chlorinate and...

Страница 13: ...et water flowing when the pool spa suction return valves are in any position other than pool only or for the first 3 minutes after solar turns on allows air in the solar panels to be purged Interlock...

Страница 14: ...e Aux relays If pool lights are wired to the lights relay some options including Solar function Low Speed of a 2 Speed Filter Pump Lights Interlock and Lights Freeze Protection are not applicable and...

Страница 15: ...e between Open and Closed default Move to next menu item or previous next configuration menu External Input The external input device can either be normally open or normally closed In this menu select...

Страница 16: ...ove to next menu item Move to next menu item if Solar is enabled if Solar is enabled Allow Low Speed Disabled Toggle between Enabled and Disabled default Move to next menu item or previous next config...

Страница 17: ...ext configuration menu if Heater1 is enabled if Heater1 is enabled if Heater1 is enabled display for Heater2 if Heater2 is enabled Heater1 Name Gas Heater Rotates between all available names Move to n...

Страница 18: ...Lowest Speed 10 Highest Speed 100 Rotates between 1 speed default 2 speed and variable speed options Toggle between Enabled default and Disabled Freeze Protection Toggle between high speed default and...

Страница 19: ...irst 3 minutes of operation anytime the pump has been off for more than 30 seconds Set highest speed from 20 to 100 default Flow Monitor This feature will help protect the filter pump from damage due...

Страница 20: ...ver the Pool Spa valves are turning The pump will NOT shut off when the heater has Cooldown enabled and is either on or in the Heater Cooldown mode Filter Config to view change Filter Name Pool Filter...

Страница 21: ...actuators should be connected to the Pro Logic Pressing the POOL SPAbutton on the display keypad will allow the homeowner to alternate between pool and spa operation If Pool and Spa Dual is selected...

Страница 22: ...ically locks after 2 minutes of no buttons being pressed to prevent unauthorized people from changing the control logic inadvertently and possibly damaging the pool equipment or causing a call back to...

Страница 23: ...while the Group is running will make the Group release the alternate setpoint control and revert back to the normal heater setting Any changes that are made at that point will affect the normal heater...

Страница 24: ...d dim the patio lights turn on the music etc all at the same time This convenient feature is offered on allAux buttons bothValve buttons and the Lights button TheAqua Plus 16v can be programmed to con...

Отзывы: