6.APPENDIX
Cable specification
1. Single phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more than 10A
2x1,5 mm
2
1,5 mm
2
20 A
30mA less than 0.1 sec
nx0.5mm
2
10~16 A
2x2,5 mm
2
2,5 mm
2
32 A
30mA less than 0.1 sec
16~25 A
2x4 mm
2
4 mm
2
40 A
30mA less than 0.1 sec
25~32 A
2x6 mm
2
6 mm
2
40 A
30mA less than 0.1 sec
32~40 A
2x10 mm
2
10 mm
2
63 A
30mA less than 0.1 sec
40 ~63 A
2x16 mm
2
16 mm
2
80 A
30mA less than 0.1 sec
63~75 A
2x25 mm
2
25 mm
2
100 A
30mA less than 0.1 sec
75~101 A
2x25 mm
2
25 mm
2
125 A
30mA less than 0.1 sec
101~123 A
2x35 mm
2
35 mm
2
160 A
30mA less than 0.1 sec
123~148 A
2x50 mm
2
50 mm
2
225 A
30mA less than 0.1 sec
148~186 A
2x70 mm
2
70 mm
2
250 A
30mA less than 0.1 sec
186~224 A
2x95 mm
2
95 mm
2
280 A
30mA less than 0.1 sec
2. Three phase unit
Nameplate
maximum
current
Phase line
Earth line
MCB
Creepage protector
Signal line
No more than 10A
3x1,5 mm
2
1,5 mm
2
20 A
30mA less than 0.1 sec
nx0.5mm
2
10~16 A
3x2,5 mm
2
2,5 mm
2
32 A
30mA less than 0.1 sec
16~25 A
3x4 mm
2
4 mm
2
40 A
30mA less than 0.1 sec
25~32 A
3x6 mm
2
6 mm
2
40 A
30mA less than 0.1 sec
32~40 A
3x10 mm
2
10 mm
2
63 A
30mA less than 0.1 sec
40 ~63 A
3x16 mm
2
16 mm
2
80 A
30mA less than 0.1 sec
63~75 A
3x25 mm
2
25 mm
2
100 A
30mA less than 0.1 sec
75~101 A
3x25 mm
2
25 mm
2
125 A
30mA less than 0.1 sec
101~123 A
3x35 mm
2
35 mm
2
160 A
30mA less than 0.1 sec
123~148 A
3x50 mm
2
50 mm
2
225 A
30mA less than 0.1 sec
148~186 A
3x70 mm
2
70 mm
2
250 A
30mA less than 0.1 sec
186~224 A
3x95 mm
2
95 mm
2
280 A
30mA less than 0.1 sec
When the unit will be installed at outdoor, please use the cable which can against UV.
24