17
D5:
Set up the dust cleaning parameter and mode
(
Fig. 10-8
)
Fig.10-8
Set up the dust cleaning parameter and select the dust cleaning mode by clicking the “Cleaning
Set” button (Fig.10-8).
Set up the dust cleaning parameter
:
Click the input area of the filter pressure difference threshold value to enter the set pressure
difference threshold parameter (The system default pressure threshold value is 1000pa, the
recommended input range: 500-2000).After entering and confirming, click the D1 button back to
main interface.
Set up the dust cleaning mode
:
1
)
Dust cleaning allowed in running
:
This mode allows that the machine cleans dust while running.
This mode is the factory default setting.
2
)
Dust cleaning forbidden in running
:
This mode forbids the machine to clean dust while running
3
)
Automatic dust cleaning
:
This mode allows that if the pressure difference is higher than the
setting value, the dust cleaning system functions until the pressure difference is lower than the
setting value.
4
)
Manual dust cleaning
:
This mode allows that the user clicks the “Filter dust cleaning” to clean
the dust while the machine is running or stopped.