MODU-FIRE® Forced Draft Gas-Fired Boiler
8
2.5.6 General Hazards
•
Tripping hazard! Do not install piping on floor surfaces. Maintain clear path around boi-
ler.
•
Slip and fall hazard! Use drip pan to catch water while draining the boiler. Maintain dry
floor surfaces.
•
Slip and fall hazard! Through-the-wall vents shall not terminate over public walkways or
over an area where condensate or vapor could create a nuisance or hazard.
•
Fall hazard! Do not stand on any part of the boiler.
•
Catch hazard! Do not wear rings, jewelry, long hair, loose clothing while working on the
boiler.
3.0 INSTALLATION
Installation and service must be performed by a qualified installer or service
agency.
3.1 R
ECEIVING AND
S
TORAGE
3.1.1 Initial Inspection
Upon receiving the boiler, inspect it for signs of shipping damage. Since some damage may be hidden, we
recommend unpacking the boiler, removing the top, front, and side covers and inspect the boiler. Verify that the
total number of pieces shown on the packing slip agrees with those actually received.
3.1.2 Storage Prior to Installation
If the boiler is not installed immediately, it must be stored in a location adequately protected from the weather and
freezing conditions, preferably indoors. If this is not possible, then it should remain in the shipping container and
be covered by a tarpaulin or other waterproof covering.
NOTICE! Controls and other equipment that are damaged or fail due to weather exposure are not
covered by warranty.
3.2 C
OMPLIANCE WITH
C
ODES
The MODU-FIRE
®
Forced Draft boiler with standard components and many options complies with American Na-
tional Standard/CSA Standard ANSI Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers, lat-
est edition. The heat exchanger is constructed and stamped in accordance with ASME Boiler and Pressure Ves-
sel Code, Section IV for 160 psig maximum operating pressure and/or 250º F maximum operating temperature.
General Warning
NOTICE! Note any damage, suspected potential damage, or shortage of materials on the freight bill
and immediately notify the carrier. File all claims for shortage or damage with the carrier. Claims for
hidden damages must be filed with your carrier within 7 days. The boiler carton is equipped with a
“Tip (N) Tell”. If "Tip (N) Tell” arrow point is blue, that indicates that the package has been on its
side or tipped over in transit.
Содержание MODU-FIRE FORCED DRAFT N750
Страница 45: ...MODU FIRE Forced Draft Gas Fired Boiler 45 6 1 5 Main Control Panel Point to Point Left Side Alarm Flame Enable...
Страница 46: ...MODU FIRE Forced Draft Gas Fired Boiler 46 6 1 6 Main Control Panel Point to Point Right Side...
Страница 47: ...MODU FIRE Forced Draft Gas Fired Boiler 47 6 1 7 Junction Box Point to Point and Customer Connections...
Страница 48: ...MODU FIRE Forced Draft Gas Fired Boiler 48 6 1 8 Customer Connections Details...