MACH® Gas-Fired Boiler
Page 7
Gas may lose its odor. Proper gas sensing equipment and procedures should
be used for leak checks.
2.5.3 Crush Hazards
Lifting hazards! Use properly rated lifting
equipment to lift and position the boiler. The
load is unbalanced. Test balance before lifting
3 ft. above the floor. Do not allow personnel
beneath the lifted load. Refer to approximate
weights in the table below:
Bump hazard from overhead ductwork and piping. Install components with adequate vertical
clearance.
2.5.4 Chemical Hazards
Chemical hazards from cleaning products. Use caution when cleaning the system. The
use of professional assistance is recommended. Use safe procedures for the disposal of
all cleaning solutions.
Combustion Condensate
– an acidic pH of approximately 3.0 to 5.0 can be expected.
Use PVC, CPVC, or other corrosion resistant piping for drainage. Collection and disposal
must be in accordance with all applicable regulations. A condensate neutralization kit is
available. Please contact your local Harsco Industrial, Patterson-Kelley representative.
2.5.5 Pressure Hazards
Pressure hazard! Hot fluids. Install isolation valves on boiler water inlet and outlet.
Make sure isolation valves are closed before servicing boiler.
Pressure hazard! Hot fluids. Annually test safety relief valve for proper operation. Do
not operate boiler with faulty relief valve.
2.5.6 Slip, Fall Hazards
Tripping hazard! Do not install piping on floor surfaces. Maintain clear path around boiler.
Slip and fall hazard! Use drip pan to catch water while draining the boiler. Maintain dry floor
surfaces.
Slip and fall hazard!
Do not
locate intake or exhaust terminations directly above a walkway;
dripping of condensation can cause icing of the walking surface. (see section 3.6.3)
Fall hazard! Do not stand on any part of the boiler.
Catch hazard! Do not wear rings, jewelry, long hair, loose clothing while working on the boiler.
Boiler Size
Weight in Pounds
C1500GG
1200
C2000GG
1400
General Warning
General Warning
General Warning
General Warning
Содержание MACH C1500GG
Страница 49: ...MACH Gas Fired Boiler Page 49 6 1 3 MACH Boiler C1500GG C2000GG Wiring Diagram ...
Страница 50: ...MACH Gas Fired Boiler Page 50 6 1 4 Dual Fuel Control Wiring MACH C1500GG C2000GG ...
Страница 58: ...MACH Gas Fired Boiler 58 8 3 MAINTENANCE LOG Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By ...