MACH® Gas-Fired Boiler
Page 38
4.2.3 Normal Shut Down Procedures
1. Turn the on/off switch to the off position.
2. Close all manual gas valves. (if shutdown for extended period.)
4.2.4 Emergency Shut-Off
4.3
T
YPICAL
B
OILER
U
TILITY
R
EQUIREMENTS
MACH®
Boiler
Model
Input
Rating
(BTU/Hr)
Total
Amperage
Natural Gas
(1030 Btu/cu. ft.*)
Gas Rate
(CFH)
Output
Capacity
(Btu/hr)
C1500GG
1,500,000
Less than
15
1456*
1,440,000
C2000GG
2,000,000
Less than
15
1942*
1,920,000
Note:
The heat exchanger is constructed and stamped for 100 psig maximum operating pressure and 200º F
maximum temperature.
If overheating occurs or the gas
supply fails to shut off, do not turn off or disconnect the
electrical supply to the pump. Instead, shut off the gas
supply at a location external to the boiler.
Emergency Gas Shutoff
Close Both Valves
Содержание MACH C1500GG
Страница 49: ...MACH Gas Fired Boiler Page 49 6 1 3 MACH Boiler C1500GG C2000GG Wiring Diagram ...
Страница 50: ...MACH Gas Fired Boiler Page 50 6 1 4 Dual Fuel Control Wiring MACH C1500GG C2000GG ...
Страница 58: ...MACH Gas Fired Boiler 58 8 3 MAINTENANCE LOG Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By ...