background image

Harman®  •  PF-120 Installation Manual_R1  •  2014 -___  •  03/14

14

3-90-08121i

F.  Avoiding Smoke and Odors

Negative Pressure, Shut-down, and Power Failure:

T

o reduce the probability of back-drafting or burn-back in 

the pellet burning appliance during power failure or shut-

down conditions, the stove must be able to draft naturally

 

without exhaust blower operation. Negative pressure in the 

building will resist this natural draft if not accounted for in the 

pellet appliance installation.
Heat rises and leaks out at upper levels. This air must be 

replaced with cold air from outdoors, which flows into lower 

levels of the building.

Vent Pipe

Be sure to use approved pellet vent pipe wall and ceiling 

pass- through fittings to go through combustible walls and 

ceilings. Be sure to use a starting collar to attach the venting 

system to the furnace. The starting collar must be secured 

to the flue stub with at least three screws, and sealed with 

high temp silicone caulking.
Pellet venting pipe (also known as PL vent) is constructed 

of  two  layers  with  air  space  between  the  layers. This  air 

space acts as an insulator and reduces the outside surface 

temperature to allow a clearance to combustibles of only 1 

inches. The sections of pipe lock together to form an air tight 

seal in most cases; however, in some cases a perfect seal 

is not achieved. For this reason and the fact that the PF-120 

operates with a positive vent pressure, we specify that the 

joints also be sealed with silicone.
Where passing through an exterior wall or roof, be sure to use 

the appropriate pass-through device providing an adequate 

vapor barrier. Venting manufacturers generally provide these 

pas-through devices.

D. Draft

Draft is the pressure difference needed to vent appliances 

successfully. When an appliance is drafting successfully, all 

combustion by products are exiting through the chimney.
Considerations for successful draft include:

•  Preventing negative pressure
•  Location of appliance and chimney
To measure the draft or negative pressure on your appliance 

use  a  magnahelic  or  a  digital  pressure  gauge  capable  of 

reading 0 - 1 inches of water column (W.C.). 
The  appliance  should  be  running  on  high  for  at  least  30 

minutes for the test of high burn draft.
With the furnace running on high you should have a negative 

pressure equal to or greater than the number given in the 

chart below. If you have a lower reading than you find on the 

chart, your appliance does not have adequate draft to burn 

the fuel properly.
Cold draft test should be done prior to lighting unit. Minimum 

should be:

Minimum Vacuum Requirements:

.35

INSPECT FLUE PIPES, FLUE PIPE JOINTS, AND 

FLUE PIPE SEALS REGULARLY TO ENSURE THAT 

SMOKE AND FLUE GASES ARE NOT DRAwN INTO, 

AND CIRCULATED BY, THE AIR-CIRCULATION 

SYSTEM.

WARNING

!

E. Negative Pressure

Negative pressure results from the imbalance of air available 

for the appliance to operate properly. It can be strongest in 

lower levels of the house.
Causes include:

•  Combustion air requirements for furnaces, water heaters 

and other combustion appliances

•  Location of return-air vents to furnace or air conditioning
•  Imbalances of the HVAC air handling system
•  Upper level air leaks such as: 
  -  Recessed lighting
To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion appliances 

and exhaust equipment

Risk of Asphyxiation!

 

Negative  pressure  can  cause 

spillage of combustion fumes and soot. 

WARNING

!

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design
•  Attic hatches weather stripped or sealed
•  Attic mounted duct work and air handler joints and seams 

taped or sealed

NOTICE: 

Hearth  &  Home  Technologies  assumes  no 

responsibility for the improper performance of the chimney 

system caused by:

•  Inadequate draft due to environmental conditions
•  Downdrafts
•  Tight sealing construction of the structure
•  Mechanical exhausting devices

Содержание PF-120

Страница 1: ...allation Installation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspection requirements in y...

Страница 2: ...s Specifications 4 C Electrical Rating 4 D Mobile Home Approvals 4 E BTU Efficiency Specifications 4 2 Getting Started A Tools and Supplies Needed 5 B Inspect Appliance and Components 5 3 Clearances A...

Страница 3: ..._________ Electrical Section 1 Pg 4 120VAC unswitched power provided to the appliance ________________________________ Finishing Sections 3 4 Pg 8 14 Combustible materials not installed in non combust...

Страница 4: ...to the frame of the mobile home and use only listed pellet vent Class PL connector pipe A Harman Outside Air Kit must be installed in a mobile home installation MODEL Pellet Furnace PF 120 LABORATORY...

Страница 5: ...g the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged incomplete or substitute components Keep appl...

Страница 6: ...iagram Dimensions are actual appliance dimensions Use for reference only 14 18 25 966 62 474 15 883 9 743 37 961 18 11 00 65 525 20 065 25 254 16 802 3 215 44 478 WITHOUT BLOWER BOX INSTALLED 27 238 2...

Страница 7: ...sh pan door The 18 clearance from the hopper end is a manufacturer s recommendation for adding pellets and or servicing the feeder mechanism The minimum clearance to the top of the plenum is 4 Fig 3 3...

Страница 8: ...The United States J Floor Protection Requirements US Sides 8 K Front 18 C Floor Protection The shaded area indicates the required floor protection area The furnace requires 48 x 52 of floor protectio...

Страница 9: ...onfiguration Graph under Section B Locating Your Appliance Chimney Each Vertical 90 or T subtract 2 5 feet Each Vertical 45 subtract 1 5 feet Each Horizontal 90 or T subtract 5 0 feet Each Horizontal...

Страница 10: ...intain specified clearances to windows doors and air inlets including air conditioners Vents should not be placed below ventilated soffits Avoid venting into alcove locations Vents should not terminat...

Страница 11: ...fsets Consider the appliance location relative to floor and ceiling and attic joists DO NOT CONNECT THIS UNIT TOACHIMNEY FLUE SERVICING ANOTHER APPLIANCE May allow flue gases to enter the house CAUTIO...

Страница 12: ...regulator assembly when measured from the horizontal center line of the regulator I The clearance to service regulator vent outlet must be a minimum of 6 feet J The clearance to a non mechanical air s...

Страница 13: ...ombine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flue lining When...

Страница 14: ...nd chimney To measure the draft or negative pressure on your appliance use a magnahelic or a digital pressure gauge capable of reading 0 1 inches of water column W C The appliance should be running on...

Страница 15: ...NOT install damaged components Do NOT install incomplete components Do NOT install substitute components Report damaged parts to dealer WARNING WARNING Do not relocate or bypass any of the safety cont...

Страница 16: ...y the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume some air needed for the stove especially during a power failure It may be neces...

Страница 17: ...is access to the combustion blower and flue area 1 Place the bottom on the floor The edge closest to the knockouts will be the edge towards the furnace See Figure 5 1 2 Place the desired vertical pan...

Страница 18: ...bottom middle hole under the filter opening NOTE Do not put any screws into any of the top holes at this time Filter Frame Panel Filter opening must be up 4 Place the remaining panel in this case the...

Страница 19: ...sure that the setscrew on the flex connector is not pointing toward the furnace end of the box when the locknut is fully tightened The filter box is now ready to install onto the furnace Note The blo...

Страница 20: ...Y DUCT WORK OR IN FREE AIR WILL CAUSE MOTOR OVERLOAD AND PREMATURE FAILURE 3 Mount the filter box on the furnace with 6 10 x 3 4 Tek screws 3 on each side Figure 5 10 Visually locate these holes so yo...

Страница 21: ...Orange Blue White Orange White Blue This section is not used on this unit CAUTION With this small gauge of wire care must be taken not to over tighten the terminal screws thus breaking the wire There...

Страница 22: ...dampers 2 should be installed in the ductwork 1 in the warm air supply duct for the existing furnace and 1 in the warm air supply duct of the pellet furnace after or downstream of the high limit fan c...

Страница 23: ...ct system can be installed to fit the customers needs Velocity 500fpm 700fpm 900fpm Static In W C 3 Minimum to 6 Maximum 1638 cfm 470 in 360 in 290 in These duct sizes are only recommendations The Ret...

Страница 24: ...blower size is 75 to 1 CFM for each square foot of conditioned space standard 8 ceiling height This furnace can be fitted with an air conditioning coil mounted in the supply air plenum HHT is not resp...

Страница 25: ...t the WHITE and SKY BLUE wires to the LIMIT switch It doesn t matter which wire is on which screw Figure 5 17 8 Make sure that all of the wires are out of the way when closing the cover Excess twistin...

Страница 26: ...ply 120 VAC 60Hz power stable enough to operate the control board properly Control board damage could occur Checking Recording the Low Draft After the venting is completed the firebox low draft will n...

Страница 27: ...shall comply with CSA B139 The installation of a gas furnace shall comply with the applicable requirements of CSA B365 and if changes are made to the installation of the gas furnace including clearanc...

Страница 28: ...WHITE GREEN N L BROWN DRK BLUE VIOLET BROWN BLACK RED BROWN G R E E N WHITE WHITE GREEN WHITE BROWN SKY BLUE WHITE RED BROWN WHITE BLACK SKY BLUE YELLOW HIGH VOLTAGE YELLOW VIOLET SKY BLUE WHITE 3 8...

Страница 29: ...Harman PF 120 Installation Manual_R1 2014 ___ 03 14 29 3 90 08121i...

Страница 30: ...n U S A Copyright 2012 Harman a brand of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstove com Please contact your Harman dealer with any questions or concerns For...

Отзывы: