background image

Harman®  •  P-Series Installation Manual_R3  •  2018 - ___  •  09/20

19

8390-044I

E. Locating Your Appliance & Chimney

Location of the appliance and chimney will affect performance. 

•  Install through the warm airspace enclosed by the 

building envelope. This helps to produce more draft, 

especially during lighting and die-down of the fire.

•  Penetrate the highest part of the roof. This minimizes the 

effects of wind loading.

•  Locate termination cap away from trees, adjacent 

structures, uneven roof lines and other obstructions.

•  Minimize the use of chimney offsets. 
•  Consider  the  appliance  location  relative  to  floor  and 

ceiling and attic joists.

G. Negative Pressure

F. Draft

Draft is the pressure difference needed to vent appliances 

successfully. When an appliance is drafting successfully, all 

combustion by products are exiting the home through the 

chimney.
Considerations for successful draft include:

•  Preventing negative pressure
•  Location of appliance and chimney

To measure the draft or negative pressure on your appliance 

use a magnahelic or a digital pressure gauge capable of 

reading 0 - 1 inches of water column (W.C.).

 

The appliance should be running on high for at least 15 

minutes for the test.
With the stove running on high you should have a negative 

pressure equal to or greater than the number given in the 

chart below. If you have a lower reading than you find on the 

chart, your appliance does not have adequate draft to burn 

the fuel properly.

Minimum Vacuum Requirements:

.35 - .55

Prior to installing the flue pipe, connect a draft meter. (The 

draft meter must have a minimum range of 0 - .5”) Record the 

first reading. Connect flue pipe to stove and be sure all doors 

and windows in the home are closed. Record the second draft 

reading _______. If the second reading is more than .05” 

lower than the first reading, check for possible restrictions 

or the need for outside air.

 For more information on the draft 

test procedure, refer to Page 21

•  DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 

SERVICING ANOTHER APPLIANCE.

•  DO  NOT  CONNECT  TO ANY AIR  DISTRIBUTION 

DUCT OR SYSTEM.

May allow flue gases to enter the house

CAUTION

Negative pressure results from the imbalance of air available 

for the appliance to operate properly. It can be strongest in 

lower levels of the house.
Causes include:

•  Exhaust fans (kitchen, bath, etc.)

•  Range hoods
•  Combustion air requirements for furnaces, water heaters 

and other combustion appliances

•  Clothes dryers

•  Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system
•  Upper level air leaks such as: 

  - Recessed lighting
  - Attic hatch
  - Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion 

appliances and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design
•  Attic hatches weather stripped or sealed
•  Attic mounted duct work and air handler joints and 

seams taped or sealed

NOTICE: 

Hearth & Home Technologies assumes no 

responsibility for the improper performance of the chimney 

system caused by:

•  Inadequate draft due to environmental conditions
• Downdrafts
•  Tight sealing construction of the structure
•  Mechanical exhausting devices

Risk of Asphyxiation!

 

Negative pressure can cause 

spillage of combustion fumes and soot.

WARNING

Содержание P43-C

Страница 1: ...y ignite clothing or other flammable materials Keep clothing furniture draperies and other flammable materials away HOT SURFACES Glass and other surfaces are hot during operation AND cool down WARNING...

Страница 2: ...n Combustible Materials Specification 5 G Combustible Materials Specification 5 H Electrical Codes 5 2 Getting Started A Design and Installation Considerations 6 B Tools and Supplies Needed 7 C Inspec...

Страница 3: ..._______________________ Electrical Section 1 120 VAC unswitched power provided to the appliance ________________________________ Check outlet with multi meter for proper voltage 115 120 VAC __________...

Страница 4: ...135PS023E 0135PS023S TYPE Pellet Fueled Supplementary For Residential Use STANDARD s ASTM E 1509 04 ULC S627 00 ASTM E 2515 11 ASTM E 2779 10 MODEL P61 C Pellet Stove LABORATORY OMNI Test Laboratories...

Страница 5: ...any component not approved by Hearth Home Technologies Install parts or components not Listed or approved Disable safety switches Improper installation adjustment alteration service or maintenance ca...

Страница 6: ...r Intakes Air Conditioner Overhang soffits porch roofs adjacent walls Landscaping vegetation Marginal Location Below peak Location NOT recommended Not the highest point of the roof Wind loading possib...

Страница 7: ...be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth H...

Страница 8: ...tual appliance dimensions Use for reference only Figure 3 1 20 3 4 22 10 33 1 2 5 1 8 13 3 4 28 5 16 Outside Air Intake P43 C Freestanding Pellet Stove 23 1 2 10 36 1 2 5 1 8 13 3 4 29 3 8 Outside Air...

Страница 9: ...placed on or near this unit B Clearances to Combustibles When selecting a location for the appliance it is important to consider the required clearances to walls Figure 3 2 CAUTION THIS APPLIANCE MUST...

Страница 10: ...ipe Figure 3 3 J K L Floor Protector D Mobile Home Installation When installing this unit in a mobile home several requirements must be followed 1 The unit must be bolted to the floor This can be done...

Страница 11: ...vent of a power failure Do not place joints within wall pass through 2 Preferred method Figure 4 2 This method also provides excellent venting for normal operation but requires the stove to be install...

Страница 12: ...sting fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is quest...

Страница 13: ...this method a cap should also be installed on the chimney to keep out rain Be sure to use approved pellet vent pipe fittings Pipe size should be increased to 4 using this method 6 Installing into an...

Страница 14: ...wall pass through Figure 4 7 Figure 4 8 Figure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses 12 min above ground level...

Страница 15: ...ide corner is 11 from center of pipe G The clearance to an inside corner is 12 H A vent must not be installed within 3 feet 90 cm above a gas meter regulator assembly when measured from the horizontal...

Страница 16: ...ositive static pressure Negative static pressure O Figure 4 11 Example First Floor Installation A unit is to be installed using 3 Pellet Pipe with 3 feet of horizontal pipe a Tee 10 feet of vertical p...

Страница 17: ...10 Ft 15 Ft 20 Ft 25 Ft 30 Ft 5 Ft 0 Ft 15 Ft Equivalent Vent Length EVL Maximum Horizontal Run Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more freque...

Страница 18: ...he stove especially during a power failure It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determin...

Страница 19: ...windows in the home are closed Record the second draft reading _______ If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air Fo...

Страница 20: ...pass through fittings to go through combustible walls and ceilings Be sure to use a starting collar to attach the venting system to the stove The starting collar must be secured to the flue stub with...

Страница 21: ...pliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any component part not approved by Hearth Home Technologies Operating...

Страница 22: ...t contact with hot or moving parts If needed install the 2 5 16 18 X 3 4 leveling bolts located in the hardware kit Figure 5 1 C Firebrick The P43 C Pellet Stove has a single 1 firebrick that gets ins...

Страница 23: ...stment should be done by the installer during set up because a draft meter reading is required to insure proper set up If the unit is not adjusted properly it does not cause a safety concern If the un...

Страница 24: ...HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED CAUTION Due to high temperatures this stove should be placed out of traffic and away from furniture and draperies Children and adults should be aler...

Страница 25: ...E PRESSURE SWITCH NO CONTACTS COMBUSTION MOTOR FEED MOTOR IGNITER ELEMENT P43 P61 P68 DISTRIBUTION BLOWER WHITE OR LT BLUE GREEN USED ON ACCENTRA ONLY DK BLUE OR BLACK ACCENTRA P35i P40i XXV DISTRIBUT...

Страница 26: ..._ 09 20 26 8390 044I 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For the location of your nearest Harman dealer pleas...

Отзывы: