B.  Chimney Diagram

V

=Vent Terminal

A

=Air Supply Inlet

=Area where termination is not permitted

Door

Sidewalk

Fixed

Closed

Openable

Openable

Fixed

Closed

Inside Corner

Detail

Porch or

Openable

Deck 
or Fixed

Requirements for Terminating the Venting

•  Venting terminals must not be recessed into a wall 

or siding.

•  Only PL vent pipe wall pass-through and fire stops 

should be used when venting through combustible 

materials.

•  Always take into consideration the effect the 

prevailing wind direction or other wind currents will 

cause with flyash and /or smoke when placing the 

termination.

In addition, the following must be observed:

A.  The clearance above grade must be a minimum of 12".
B.  The clearance to a window or door that may be opened 

must be a minimum of 48" to the side and 48" below the 

window/door, and 12" above the window/door.

 

(

with 

outside air installed, 12” to side and below

)

C.  A 12" clearance to a permanently closed window is 

recommended to prevent condensation on the window.

D.  The vertical clearance to a ventilated soffit located above 

the terminal within a horizontal distance of 2 feet (60 cm) 

from the center-line of the terminal must be a minimum 

of 18".

E.  The clearance to an unventilated soffit must be a 

minimum of 12".

F.  The clearance to an outside corner is 11" from center of 

pipe.

G.  The clearance to an inside corner is 12".
H.  A vent must not be installed within 3 feet (90 cm) above 

a gas meter/regulator assembly when measured from 

the horizontal center-line of the regulator.

Figure 4.10

I.  The clearance to service regulator vent outlet must be a 

minimum of 6 feet.

J.  The clearance to a non-mechanical air supply inlet to the 

building or the combustion air inlet to any other appliance 

must be a minimum of 48”.

K.  The clearance to a mechanical air supply inlet must be a 

minimum of 10 feet. (

with outside air installed, 6 feet

)

L.  The clearance above a paved sidewalk or a paved 

driveway located on public property must be a minimum 

of 7 feet.

M.  The clearance under a veranda, porch, deck or balcony 

must be a minimum of 12 inches.

 (B. also)

Note: The clearance to vegetation and other exterior 

combustibles such as mulch is 36” as measured from 

the center of the outlet or cap. This 36” radius continues 

to grade.

Certain Canadian and or Local codes or regulations may 

require different clearances.
A  vent  shall  not  terminate  directly  above  a  side-walk  or 

paved driveway which is located between two single  family 

dwellings and serves both dwellings.

Only permitted if veranda, porch, deck, or balcony is fully 

open on a minimum of 2 sides beneath the floor.

See NFPA 211 for more installation clearance reductions 

when using outside air. 

 Where passage through a wall, 

or partition of combustible construction is desired, 

the installation shall conform to CAN/CSA-B365. (if in 

Canada)

Содержание P43-C

Страница 1: ...y ignite clothing or other flammable materials Keep clothing furniture draperies and other flammable materials away HOT SURFACES Glass and other surfaces are hot during operation AND cool down WARNING...

Страница 2: ...n Combustible Materials Specification 5 G Combustible Materials Specification 5 H Electrical Codes 5 2 Getting Started A Design and Installation Considerations 6 B Tools and Supplies Needed 7 C Inspec...

Страница 3: ..._______________________ Electrical Section 1 120 VAC unswitched power provided to the appliance ________________________________ Check outlet with multi meter for proper voltage 115 120 VAC __________...

Страница 4: ...135PS023E 0135PS023S TYPE Pellet Fueled Supplementary For Residential Use STANDARD s ASTM E 1509 04 ULC S627 00 ASTM E 2515 11 ASTM E 2779 10 MODEL P61 C Pellet Stove LABORATORY OMNI Test Laboratories...

Страница 5: ...any component not approved by Hearth Home Technologies Install parts or components not Listed or approved Disable safety switches Improper installation adjustment alteration service or maintenance ca...

Страница 6: ...r Intakes Air Conditioner Overhang soffits porch roofs adjacent walls Landscaping vegetation Marginal Location Below peak Location NOT recommended Not the highest point of the roof Wind loading possib...

Страница 7: ...be voided by the following actions Installation and use of any damaged appliance or vent system component Modification of the appliance or vent system Installation other than as instructed by Hearth H...

Страница 8: ...tual appliance dimensions Use for reference only Figure 3 1 20 3 4 22 10 33 1 2 5 1 8 13 3 4 28 5 16 Outside Air Intake P43 C Freestanding Pellet Stove 23 1 2 10 36 1 2 5 1 8 13 3 4 29 3 8 Outside Air...

Страница 9: ...placed on or near this unit B Clearances to Combustibles When selecting a location for the appliance it is important to consider the required clearances to walls Figure 3 2 CAUTION THIS APPLIANCE MUST...

Страница 10: ...ipe Figure 3 3 J K L Floor Protector D Mobile Home Installation When installing this unit in a mobile home several requirements must be followed 1 The unit must be bolted to the floor This can be done...

Страница 11: ...vent of a power failure Do not place joints within wall pass through 2 Preferred method Figure 4 2 This method also provides excellent venting for normal operation but requires the stove to be install...

Страница 12: ...sting fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is quest...

Страница 13: ...this method a cap should also be installed on the chimney to keep out rain Be sure to use approved pellet vent pipe fittings Pipe size should be increased to 4 using this method 6 Installing into an...

Страница 14: ...wall pass through Figure 4 7 Figure 4 8 Figure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses 12 min above ground level...

Страница 15: ...ide corner is 11 from center of pipe G The clearance to an inside corner is 12 H A vent must not be installed within 3 feet 90 cm above a gas meter regulator assembly when measured from the horizontal...

Страница 16: ...ositive static pressure Negative static pressure O Figure 4 11 Example First Floor Installation A unit is to be installed using 3 Pellet Pipe with 3 feet of horizontal pipe a Tee 10 feet of vertical p...

Страница 17: ...10 Ft 15 Ft 20 Ft 25 Ft 30 Ft 5 Ft 0 Ft 15 Ft Equivalent Vent Length EVL Maximum Horizontal Run Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more freque...

Страница 18: ...he stove especially during a power failure It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determin...

Страница 19: ...windows in the home are closed Record the second draft reading _______ If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air Fo...

Страница 20: ...pass through fittings to go through combustible walls and ceilings Be sure to use a starting collar to attach the venting system to the stove The starting collar must be secured to the flue stub with...

Страница 21: ...pliance Modification of the appliance Installation other than as instructed by Hearth Home Technologies Installation and or use of any component part not approved by Hearth Home Technologies Operating...

Страница 22: ...t contact with hot or moving parts If needed install the 2 5 16 18 X 3 4 leveling bolts located in the hardware kit Figure 5 1 C Firebrick The P43 C Pellet Stove has a single 1 firebrick that gets ins...

Страница 23: ...stment should be done by the installer during set up because a draft meter reading is required to insure proper set up If the unit is not adjusted properly it does not cause a safety concern If the un...

Страница 24: ...HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED CAUTION Due to high temperatures this stove should be placed out of traffic and away from furniture and draperies Children and adults should be aler...

Страница 25: ...E PRESSURE SWITCH NO CONTACTS COMBUSTION MOTOR FEED MOTOR IGNITER ELEMENT P43 P61 P68 DISTRIBUTION BLOWER WHITE OR LT BLUE GREEN USED ON ACCENTRA ONLY DK BLUE OR BLACK ACCENTRA P35i P40i XXV DISTRIBUT...

Страница 26: ..._ 09 20 26 8390 044I 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For the location of your nearest Harman dealer pleas...

Отзывы: