12

A combustion blower is used to extract the com-

bustion gases from the firebox. This causes a nega-
tive pressure in the firebox and a positive pressure
in the venting system as shown in fig. 19. The longer
the vent pipe and more elbows used in the system,
the  greater the  flow  resistance.  Because of  these
facts we recommend using as few elbows as pos-
sible and 15 feet or less of vent pipe. The maximum
horizontal run should  not exceed 48". If  more than
15  feet  of pipe  is  needed,  the diameter  should  be
increased from 3" to 4" because a larger pipe causes
less  flow  resistance. 

Be  sure  to  use  approved

pellet vent pipe wall and ceiling pass- through
fittings  to  go  through  combustible  walls  and
ceilings. 

Be sure to use a starting collar to attach

the venting system to the stove. 

The starting col-

lar must be sealed to the stove with high temp
silicone caulking.

  + = Positive static pressure
     =  Negative static pressure

Outside air flex pipe
goes here

Inlet Cover part#
1-10-08542

Flex pipe part#
2-00-08543

HRV

When installing in a house with a Heat Reclaim-

ing Ventilation System (HRV) be sure the system is
balanced and is not creating a negative pressure in
the house.

Outside  Air

Outside air is optional except in mobile homes

and  where  building  codes  require.    The  benefit  of
outside  air  is  mainly  noticed  in  small,  very  tight
houses.

To  install  outside  air  use  2  3/8"  I.D.  flex  pipe

part number 2-00-08543. There is a break-away hole
on  the  rear  panel  which  must  be  removed  before
connecting the flex pipe. The pipe should be run out-
side and terminate to the side or below the vent pipe
outlet  so  the  flue  outlet  is  more  than  12"  from  the
inlet cover. The maximum length run of this pipe is
15 feet. If a longer run is needed, the size must be
increased to 3". Inlet cover part number 1-10-08542
should  be  used  to  keep  birds,  rodents,  etc.  out  of
pipe.

Fig.19

Room Sensor
Connection Ports

Venting

Vent  Pipe

Pellet venting pipe ( also known as PL vent ) is

constructed  of  two  layers  with  air  space  between
the layers. This air space acts as an insulator and
reduces the outside surface temperature to allow a
clearance  to  combustibles  of  only  3  inches.  The
sections  of  pipe  lock  together  to  form  an  air  tight
seal in most cases; however, in some cases a per-
fect  seal  is not  achieved.  For  this reason  and  the
fact that the Advance operates with a positive vent
pressure, 

we  specify  that  the  joints  also  be

sealed with  clear silicone.

Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.

Содержание Advance Pellet Stove

Страница 1: ...AFETY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDIN...

Страница 2: ...dvance Igniter Automatic Ignition System allow the unit to burna large variety of biomass fuels with varyingash content The Advance feed systemhas a maximum feed rate of 6 lbs per hour and a minumum m...

Страница 3: ...lly on 4 can be increased if higher burn rates are necessary The unit s maximum burn rate should not create less than 1 of ash on the burn pot front edge See Fig 2 Page 4 Overfeeding is not a safety c...

Страница 4: ...ed rate setting that works well use that setting Remember if your feed rate is too high you may waste fuel 5 This is usually a weekly maintence procedure Cleaning the burn pot with the scraper with a...

Страница 5: ...at the fire willnot go out as the roomtemperature goes above the control board setting The unit can only go to low burn and will remain there until it runs out of fuel or until more heat is needed and...

Страница 6: ...n With the unit burning in AUTO turn to Stove Mode and putthe fan on H Set the Temperature Dial to 7 Allow the unit to burn for about 30 minutes andcheck ash on frontof burn pot Fig 5 If the ash line...

Страница 7: ...e Troubleshooting section for more details A six blink status may be set if the stove is allowed to run out of pellets To reset turn mode selector to OFF then back on to the desired mode If the unit w...

Страница 8: ...icing Please take this into account when plac ing the stove Mobile Home Installation AFTER THE INSTALLATION IS COMPLETED Before the first fire is lit check and record the high and low draft reading nu...

Страница 9: ...s holding each rear shield Using a 5 16 nut driver or socket loosen the 2 screws about 4 or 5 turns Figure 12 Slide the rear shields straight outward until the ends come out of the rear retaining clip...

Страница 10: ...on fan blade change can be made by an authorized Harman Dealer These changes must be done with the use of a draft meter These changes affect the low and high burn rate air to fuel ratios A simple draf...

Страница 11: ...25 feet from the unit or in another room are not recommended It is recommended that the room sensor be installed even if only installed on the rear of the unit as a return air sensor The roomsensor i...

Страница 12: ...nd is not creating a negative pressure in the house Outside Air Outside air is optional except in mobile homes and where building codes require The benefit of outside air is mainly noticed in small ve...

Страница 13: ...his method provides excellent venting for nor mal operation and allows the stove to be installed clos est to the wall One inch from the wall is safe how ever two or three inches allows better access t...

Страница 14: ...s in method 6 4 Installing into an existing fireplace chimney US only This method can be used for normal operation This method also provides natural draft in the event of a power failure The damper ar...

Страница 15: ...vent pipe fittings Seal pipe joints with silicone in addition to the sealing system used by the manufac turer Pipe size should be increased to 4 using this method 6 Installing into an existing chimne...

Страница 16: ...nt pipe 7 Installing through the ceiling vent Through the ceiling vent follow PL vent manufacturer s recommendations when using wall and ceiling pass through Flashing Stormcollar 12 min 3 min 3 min Fi...

Страница 17: ...from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearance to a non mechanical air sup ply inlet to the building...

Страница 18: ...should be done in accordance with the Manufactured Home and Safety Standard HUD CFR 3280 Part 24 DO NOT INSTALL IN SLEEPING ROOM WARNING KEEP COMBUSTIBLES AWAY FROM FLUE OUTLET CAUTION CAUTION THE ST...

Страница 19: ...ash fines behind the ash pan This space behind the ash pan was designed to allow the fines to fall out of the vertical heat exchangers and collect where they are easily cleaned out rather than going...

Страница 20: ...end of the door while in the open position If thedoor is goingto be openedfor anextendedperiod of time it is suggested that it be removed see Fig 36 and set safely aside 3 Inspect the door gasket and...

Страница 21: ...hese connections between the hot leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the rear of the feeder body Not coiled inside the burn pot...

Страница 22: ...of the burn pot Figure 44 Slide the brick panel into the left corner of the fireboxwith the panel resting on the top edges of theburn pot Rotatetheright sideofthe brick panel through the dooropening...

Страница 23: ...rearflue tube Figure 46 Rotate the retainercoverhandle counter clockwise upward as far as it will go approximately90o Figure 47 Hold the intake coverhandle and pull until the side of thecover at ther...

Страница 24: ...ng Lift baffle up and out The right and left baffle are interchangeable 6 Now remove the heat exchanger baffle plates See Fig 51 52 To remove the left plate slide the center lock to the right To remov...

Страница 25: ...s too low for proper combustion the switch opens cuttin power to the feeder mo tor and the igniter element This switch is connected into the AC high voltage wires therefore the control may show the fe...

Страница 26: ...too low 3 Something is restricting fuel flow 4 Feed motor or draft motor has failed 5 Power failure or blown fuse SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fuel ratio is too rich A Feed rate too high...

Страница 27: ...nches Fuse Rating 6 amp BTU Range 0 to 48 000 Feed Rate 1 0 lbs hr on minimum 6 lbs hr on maximum Flue Size 3 inch Pellet Vent Pipe Maximum Wattage 480 Watts Start cycle and test Start Cycle Wattage 3...

Страница 28: ...28 Advance Wiring Diagram...

Страница 29: ...29 Advance Feeder Assembly...

Страница 30: ...l 3 00 06641 Front Glass 3 40 08728 Side Glass 2 3 40 08729 Hopper Lid Knob 3 43 02000 View Door Frame 3 43 06613 Gold 4 Black Nickel 5 Grill 3 43 06642 Gold 4 Black Nickel 5 Glass Divider Trim Black...

Страница 31: ...but not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filter...

Отзывы: