background image

10

These  units  are  pre-tested  at  the  factory  with

exactly  120  Volts A.C.,  60 Hz.  They  are  checked  and
adjusted    for  firebox  tightness,  gasket  leakage,  motor
operation  and  igniter  operation.    The Advance  is  then
factory set at a mid-point adjustment and in most cases
will not need any adjustments.  

NOTE: The factory low

draft  setting  may  not  be  correct  for  the  unit's
permanent installation conditions.

The  control  board  on the Advance  is  equipped

with a low draft adjustment port.  Located on the control
face just to the right of the igniter light. See Figure 14.
This voltage adjustment  is provided to allow  the unit to
be adjusted for the household voltage where the unit is
going  to  be  in  permanent  operation.  NOTE:  The  line
voltage  varies  from  area  to  area  and  often  home  to
home.

The  low  draft  voltage  should  be  adjusted  to

a chie ve   the   mos t  ef ficient  burn  o n  lo w  burn  o r
"maintenance".  This  voltage  adjustment  allows  the
installer to change the low voltage set point approximately
15 volts.  This adjustment should be done by the installer
during set up because a draft meter reading is 

required

to insure proper set up.

If  the  unit  is  not    adjusted  properly,  it  does  not

cause a safety concern. If the unit is adjusted too high,
only effiency is lost. If the unit is adjusted too low, the low
draft pressure switch will not allow the feeder motor or
the igniter to operate.

Fig.1

MODIFICATIONS

High Altitude 

(7,000 - 10,000 ft.)A  combustion

fan  blade  change  can  be  made  by  an  authorized
Harman  Dealer.  These  changes  must  be  done  with
the use of a draft meter. These changes affect the low
and high burn rate air to fuel ratios.

A simple draft test should be performed after

completing  the  flue  pipe  installation.  To  record  the
results for future reference:
1.  Plug unit into a 120VAC, 60 HZ outlet.
2.  Close the hopper lid, front view door, and the ash
pan. Neither pellets or a fire are required for this test.
3.  With the mode selector in the "OFF" position, turn
the feed adjuster to "TEST".
4.  Record the high draft_____in W.C. (Normal is -.50
to -.60) The control will be on the High Draft for a total
of 2 minutes.
5.  After 2 minutes is up, the combustion motor will go
down to low draft and the distribution blower will go on
high. Allow approximately 15 seconds to pass for the
combustion  motor  to  slow  before  checking  the  low
draft.
6.  If the low draft is between .35 and .45, record the
reading _____ in W.C.  If the reading is higher, slowly
turn  the  set  screw  counter-clockwise  until  the  draft
lowers. If the reading is lower, very slowly turn the set
screw clockwise until the draft increases.

NOTE: The test mode alternates from high to low
draft  every  60  seconds.  If  more  time  is  needed
for draft adjustment, wait until the next low draft
cycle.
NOTE: In some cases, the draft may not go as low
as .35 even with the set screw completely counter-
clockwise.

Combustion
Motor Speed
Control
Low draft only
set point.

The small straight
screwdriver slot is
plastic; therefore,
the unit can be
adjusted while in
operation.

Fig.14

Draft Meter bolt hole location

Fig.15

:

Low Draft Voltage Adjustment

Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.

Содержание Advance Pellet Stove

Страница 1: ...AFETY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDIN...

Страница 2: ...dvance Igniter Automatic Ignition System allow the unit to burna large variety of biomass fuels with varyingash content The Advance feed systemhas a maximum feed rate of 6 lbs per hour and a minumum m...

Страница 3: ...lly on 4 can be increased if higher burn rates are necessary The unit s maximum burn rate should not create less than 1 of ash on the burn pot front edge See Fig 2 Page 4 Overfeeding is not a safety c...

Страница 4: ...ed rate setting that works well use that setting Remember if your feed rate is too high you may waste fuel 5 This is usually a weekly maintence procedure Cleaning the burn pot with the scraper with a...

Страница 5: ...at the fire willnot go out as the roomtemperature goes above the control board setting The unit can only go to low burn and will remain there until it runs out of fuel or until more heat is needed and...

Страница 6: ...n With the unit burning in AUTO turn to Stove Mode and putthe fan on H Set the Temperature Dial to 7 Allow the unit to burn for about 30 minutes andcheck ash on frontof burn pot Fig 5 If the ash line...

Страница 7: ...e Troubleshooting section for more details A six blink status may be set if the stove is allowed to run out of pellets To reset turn mode selector to OFF then back on to the desired mode If the unit w...

Страница 8: ...icing Please take this into account when plac ing the stove Mobile Home Installation AFTER THE INSTALLATION IS COMPLETED Before the first fire is lit check and record the high and low draft reading nu...

Страница 9: ...s holding each rear shield Using a 5 16 nut driver or socket loosen the 2 screws about 4 or 5 turns Figure 12 Slide the rear shields straight outward until the ends come out of the rear retaining clip...

Страница 10: ...on fan blade change can be made by an authorized Harman Dealer These changes must be done with the use of a draft meter These changes affect the low and high burn rate air to fuel ratios A simple draf...

Страница 11: ...25 feet from the unit or in another room are not recommended It is recommended that the room sensor be installed even if only installed on the rear of the unit as a return air sensor The roomsensor i...

Страница 12: ...nd is not creating a negative pressure in the house Outside Air Outside air is optional except in mobile homes and where building codes require The benefit of outside air is mainly noticed in small ve...

Страница 13: ...his method provides excellent venting for nor mal operation and allows the stove to be installed clos est to the wall One inch from the wall is safe how ever two or three inches allows better access t...

Страница 14: ...s in method 6 4 Installing into an existing fireplace chimney US only This method can be used for normal operation This method also provides natural draft in the event of a power failure The damper ar...

Страница 15: ...vent pipe fittings Seal pipe joints with silicone in addition to the sealing system used by the manufac turer Pipe size should be increased to 4 using this method 6 Installing into an existing chimne...

Страница 16: ...nt pipe 7 Installing through the ceiling vent Through the ceiling vent follow PL vent manufacturer s recommendations when using wall and ceiling pass through Flashing Stormcollar 12 min 3 min 3 min Fi...

Страница 17: ...from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearance to a non mechanical air sup ply inlet to the building...

Страница 18: ...should be done in accordance with the Manufactured Home and Safety Standard HUD CFR 3280 Part 24 DO NOT INSTALL IN SLEEPING ROOM WARNING KEEP COMBUSTIBLES AWAY FROM FLUE OUTLET CAUTION CAUTION THE ST...

Страница 19: ...ash fines behind the ash pan This space behind the ash pan was designed to allow the fines to fall out of the vertical heat exchangers and collect where they are easily cleaned out rather than going...

Страница 20: ...end of the door while in the open position If thedoor is goingto be openedfor anextendedperiod of time it is suggested that it be removed see Fig 36 and set safely aside 3 Inspect the door gasket and...

Страница 21: ...hese connections between the hot leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the rear of the feeder body Not coiled inside the burn pot...

Страница 22: ...of the burn pot Figure 44 Slide the brick panel into the left corner of the fireboxwith the panel resting on the top edges of theburn pot Rotatetheright sideofthe brick panel through the dooropening...

Страница 23: ...rearflue tube Figure 46 Rotate the retainercoverhandle counter clockwise upward as far as it will go approximately90o Figure 47 Hold the intake coverhandle and pull until the side of thecover at ther...

Страница 24: ...ng Lift baffle up and out The right and left baffle are interchangeable 6 Now remove the heat exchanger baffle plates See Fig 51 52 To remove the left plate slide the center lock to the right To remov...

Страница 25: ...s too low for proper combustion the switch opens cuttin power to the feeder mo tor and the igniter element This switch is connected into the AC high voltage wires therefore the control may show the fe...

Страница 26: ...too low 3 Something is restricting fuel flow 4 Feed motor or draft motor has failed 5 Power failure or blown fuse SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fuel ratio is too rich A Feed rate too high...

Страница 27: ...nches Fuse Rating 6 amp BTU Range 0 to 48 000 Feed Rate 1 0 lbs hr on minimum 6 lbs hr on maximum Flue Size 3 inch Pellet Vent Pipe Maximum Wattage 480 Watts Start cycle and test Start Cycle Wattage 3...

Страница 28: ...28 Advance Wiring Diagram...

Страница 29: ...29 Advance Feeder Assembly...

Страница 30: ...l 3 00 06641 Front Glass 3 40 08728 Side Glass 2 3 40 08729 Hopper Lid Knob 3 43 02000 View Door Frame 3 43 06613 Gold 4 Black Nickel 5 Grill 3 43 06642 Gold 4 Black Nickel 5 Glass Divider Trim Black...

Страница 31: ...but not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filter...

Отзывы: