background image

3

The Advance pellet stove is more than just automatic ignition, it is also automatic temperature
control.  The automatic  system will  allow the  fire size  to be  adjusted to  match the  heating
needs  and  even  put  the  fire  out  if  necessary.  If  heat  is  needed  after  the  fire  is  out,  the
Advance will automatically re-ignite and adjust the fire size to match the heating need. The
totally automatic room sensor mode is recommended because of its efficiency.
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.

Automatic  Ignition/Operation

Room Temperature M ode: 

This setting will produce a room

temperature of  70 degrees  with the  di stributi on blower  at
medium speed.

This setting will produce medium heat with the
distribution blower on "low".

This setting will produce continuous maximum heat
output with the distribution blower at full speed.

Stove Temperature Mode

Igniter switch to "AUTO"

Room Temperature Mode

In "Room Temp Mode" heat output is controlled au-

tomatically by the Room Sensing Probe. When the Room
Sensing Probe calls for heat, the stove will increase out-
put. When  the Room Sensing  Probe is getting  close to
the set temperature, the stove will begin to level off out-
put and keep the fire burning at just the right temperature
to maintain that setting.

High  output  is  determined  by  the  feed  rate  set-

ting.  This  setting,  generally  on  #4,  can  be  increased  if
higher  burn  rates  are  necessary.  The  unit's  maximum
burn  rate  should  not  create  less than  1"  of  ash  on  the
burn pot front  edge. See Fig.2, Page  4. Overfeeding is
not a safety concern, but fuel may be wasted if unburned
pellets fall into the ash pan.

In "Room Temp Mode" a constant fuel consumption

rate is sacrificed for exact room temperature. Therefore,
as  it  gets colder    more  pellets  will be  burned  automati-
cally.

The distribution blower speed will vary according to

the position of the mode selector pointer, and fire size.

Igniter switch to "AUTO"

Stove Temperature Mod

e

This allows for automatic ignition upon start-up only.

The unit can then be set at any desired setting. The heat
output and fuel consumption will remain constant regard-
less of room temperature. The unit's maximum feed rate
should not create less than 1" of ash on the burn pot front
adge. See Fig 2, Page 4.

The unit's low burn or maintenance setting is as

low as it will go. It will not go out unless it runs out of
fuel or is turned off.

Shut-Down Procedure

To kill the fire or stop burning the stove, turn the Mode Selector to

"OFF". This will cause the fire to diminish and burn out. When the fire burns
out and the stove cools down everything will stop.

If you pull the plug to shut down the stove, all motors will stop. This

may cause incomplete combustion and smoke in the firebox. If the load door
is opened the smoke may escape.

The best way to shut down the stove is simply let it run out of pellets,

then the stove will shut down automatically.

Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.

Содержание Advance Pellet Stove

Страница 1: ...AFETY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDIN...

Страница 2: ...dvance Igniter Automatic Ignition System allow the unit to burna large variety of biomass fuels with varyingash content The Advance feed systemhas a maximum feed rate of 6 lbs per hour and a minumum m...

Страница 3: ...lly on 4 can be increased if higher burn rates are necessary The unit s maximum burn rate should not create less than 1 of ash on the burn pot front edge See Fig 2 Page 4 Overfeeding is not a safety c...

Страница 4: ...ed rate setting that works well use that setting Remember if your feed rate is too high you may waste fuel 5 This is usually a weekly maintence procedure Cleaning the burn pot with the scraper with a...

Страница 5: ...at the fire willnot go out as the roomtemperature goes above the control board setting The unit can only go to low burn and will remain there until it runs out of fuel or until more heat is needed and...

Страница 6: ...n With the unit burning in AUTO turn to Stove Mode and putthe fan on H Set the Temperature Dial to 7 Allow the unit to burn for about 30 minutes andcheck ash on frontof burn pot Fig 5 If the ash line...

Страница 7: ...e Troubleshooting section for more details A six blink status may be set if the stove is allowed to run out of pellets To reset turn mode selector to OFF then back on to the desired mode If the unit w...

Страница 8: ...icing Please take this into account when plac ing the stove Mobile Home Installation AFTER THE INSTALLATION IS COMPLETED Before the first fire is lit check and record the high and low draft reading nu...

Страница 9: ...s holding each rear shield Using a 5 16 nut driver or socket loosen the 2 screws about 4 or 5 turns Figure 12 Slide the rear shields straight outward until the ends come out of the rear retaining clip...

Страница 10: ...on fan blade change can be made by an authorized Harman Dealer These changes must be done with the use of a draft meter These changes affect the low and high burn rate air to fuel ratios A simple draf...

Страница 11: ...25 feet from the unit or in another room are not recommended It is recommended that the room sensor be installed even if only installed on the rear of the unit as a return air sensor The roomsensor i...

Страница 12: ...nd is not creating a negative pressure in the house Outside Air Outside air is optional except in mobile homes and where building codes require The benefit of outside air is mainly noticed in small ve...

Страница 13: ...his method provides excellent venting for nor mal operation and allows the stove to be installed clos est to the wall One inch from the wall is safe how ever two or three inches allows better access t...

Страница 14: ...s in method 6 4 Installing into an existing fireplace chimney US only This method can be used for normal operation This method also provides natural draft in the event of a power failure The damper ar...

Страница 15: ...vent pipe fittings Seal pipe joints with silicone in addition to the sealing system used by the manufac turer Pipe size should be increased to 4 using this method 6 Installing into an existing chimne...

Страница 16: ...nt pipe 7 Installing through the ceiling vent Through the ceiling vent follow PL vent manufacturer s recommendations when using wall and ceiling pass through Flashing Stormcollar 12 min 3 min 3 min Fi...

Страница 17: ...from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearance to a non mechanical air sup ply inlet to the building...

Страница 18: ...should be done in accordance with the Manufactured Home and Safety Standard HUD CFR 3280 Part 24 DO NOT INSTALL IN SLEEPING ROOM WARNING KEEP COMBUSTIBLES AWAY FROM FLUE OUTLET CAUTION CAUTION THE ST...

Страница 19: ...ash fines behind the ash pan This space behind the ash pan was designed to allow the fines to fall out of the vertical heat exchangers and collect where they are easily cleaned out rather than going...

Страница 20: ...end of the door while in the open position If thedoor is goingto be openedfor anextendedperiod of time it is suggested that it be removed see Fig 36 and set safely aside 3 Inspect the door gasket and...

Страница 21: ...hese connections between the hot leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the rear of the feeder body Not coiled inside the burn pot...

Страница 22: ...of the burn pot Figure 44 Slide the brick panel into the left corner of the fireboxwith the panel resting on the top edges of theburn pot Rotatetheright sideofthe brick panel through the dooropening...

Страница 23: ...rearflue tube Figure 46 Rotate the retainercoverhandle counter clockwise upward as far as it will go approximately90o Figure 47 Hold the intake coverhandle and pull until the side of thecover at ther...

Страница 24: ...ng Lift baffle up and out The right and left baffle are interchangeable 6 Now remove the heat exchanger baffle plates See Fig 51 52 To remove the left plate slide the center lock to the right To remov...

Страница 25: ...s too low for proper combustion the switch opens cuttin power to the feeder mo tor and the igniter element This switch is connected into the AC high voltage wires therefore the control may show the fe...

Страница 26: ...too low 3 Something is restricting fuel flow 4 Feed motor or draft motor has failed 5 Power failure or blown fuse SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fuel ratio is too rich A Feed rate too high...

Страница 27: ...nches Fuse Rating 6 amp BTU Range 0 to 48 000 Feed Rate 1 0 lbs hr on minimum 6 lbs hr on maximum Flue Size 3 inch Pellet Vent Pipe Maximum Wattage 480 Watts Start cycle and test Start Cycle Wattage 3...

Страница 28: ...28 Advance Wiring Diagram...

Страница 29: ...29 Advance Feeder Assembly...

Страница 30: ...l 3 00 06641 Front Glass 3 40 08728 Side Glass 2 3 40 08729 Hopper Lid Knob 3 43 02000 View Door Frame 3 43 06613 Gold 4 Black Nickel 5 Grill 3 43 06642 Gold 4 Black Nickel 5 Glass Divider Trim Black...

Страница 31: ...but not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filter...

Отзывы: