Chapter 5 – Configuration
Hardy H6800 Series Application Controllers User Guide
78
5.7 Option Parameters
5.7.1 Configuring Digital I/O States
Path:
Home screen > Operation Menu > Option > Digital I/O
The Digital I/O screen shows the state of the digital input/output on the main board. It also allows
you to flip the state of the digital outputs.
Parameter
Description
Base Board Digital Input Output
Input For Display Only
Read-only LEDs that show the following status indications for the main board’s two digital inputs:
•
1 or 2 is green = the input is sending a voltage signal to that input.
•
1 or 2 is red = there is no voltage signal for that input.
Output Control
Shows the states of the digital outputs. Press the 1 and/or 2 circles to toggle the output between 1
(green) and 0 (red) for digital output. Press the disk icon to send the state(s) to the application controller.
5.8 Metrology
Path:
Home screen > Operation Menu > Option> Metrology
The Metrology screen configures approval options and warmup delay time to meet
certification standards.
Parameter
Description
Approval Options
Select a
to apply to the scale. Selecting an approval option sets the scale to meet the
certification standard, but it does not generate a certificate. To obtain NTEP or Canada certification, you
must have the appropriate agency certify the application controller. If you choose NTEP or a Canadian
selection, you can no longer tare with a negative gross weight.
Range: None, OIML, CPA, NTEP, MC
Default: None
Warmup Delay Time
Amount of time that must pass before weight data is displayed. The time can be up to two decimal points
in minutes.