HI 6600 Series Modular Sensor System User Guide
Page | 23
Redundant DC power may also be supplied individually to each Weight Processing Module via the DC power
input terminal located on the bottom of the module. DC power supplied to individual Weight Processing
Modules is isolated and not distributed to other modules on the system.
At minimum, DC power must be supplied to the Gateway Module.
The maximum distance between the first and last module on a system is 500 feet (150 meters). The HardyNet
termination switch should be turned on for the first and last units in the series. In most cases, this is the HI
6600 Gateway module and the last HI 6610 Weight Processing Module on the network. All other HI 6610-WP
modules between the Gateway Module and the last weight processing module should have the termination
switches turned off.
NOTES:
DO NOT USE CROSS-OVER CABLES.
Port Numbers have no effect on cabling (i.e. connecting either Port 1 to Port 2 or Port 2 to Port
1) is acceptable.
DC Power Input
AVERTISSEMENT – Assurez-vous que la source d’alimentation ne dépasse pas
24 V. L’utilisation d’un mauvaise voltage peut résulter en dégâts matériels
et/ou des risques de blessures.
WARNING - Do not operate with incorrect line voltage. To do so will result in
property damage and/or personal injury. Make sure that the power source does
not exceed 24 VDC.
Содержание HI 6110
Страница 16: ...HI 6600 Series Modular Sensor System User Guide Page 16 ...
Страница 44: ...HI 6600 Series Modular Sensor System User Guide Page 44 ...
Страница 96: ...HI 6600 Series Modular Sensor System User Guide Page 96 General Troubleshooting Flow Chart Index ...
Страница 97: ...HI 6600 Series Modular Sensor System User Guide Page 97 A ElectricalandMechanicalReview ...
Страница 98: ...HI 6600 Series Modular Sensor System User Guide Page 98 A1 CheckingforUnstableComponentsinaWeighingSystem ...
Страница 100: ...HI 6600 Series Modular Sensor System User Guide Page 100 B1 GuidelinestoVerifyElectricalInstallation ...
Страница 101: ...HI 6600 Series Modular Sensor System User Guide Page 101 B2 GuidelinestoVerifyMechanicalInstallation ...
Страница 102: ...HI 6600 Series Modular Sensor System User Guide Page 102 B3 VerifyConfiguration FilterSettingstoImproveStability ...
Страница 103: ...HI 6600 Series Modular Sensor System User Guide Page 103 C IntegratedTechnicianandStabilityTestOverview ...
Страница 104: ...HI 6600 Series Modular Sensor System User Guide Page 104 ENon ReturntoZero SystemwithITSummingCard ...
Страница 106: ...HI 6600 Series Modular Sensor System User Guide Page 106 G Calibration Errors During Calibration ...
Страница 107: ...HI 6600 Series Modular Sensor System User Guide Page 107 H Mechanical Installation ...
Страница 108: ...HI 6600 Series Modular Sensor System User Guide Page 108 J Electrical Inspection ...
Страница 109: ...HI 6600 Series Modular Sensor System User Guide Page 109 K InstallationCheckPoints ...
Страница 110: ...HI 6600 Series Modular Sensor System User Guide Page 110 M WeightProcessor sOptionalFrontDisplayBlankorLocked ...
Страница 128: ...HI 6600 Series Modular Sensor System User Guide Page 128 ...
Страница 130: ...HI 6600 Series Modular Sensor System User Guide Page 130 Image of HI 6600 Hardy Gateway Module II Diagram ...
Страница 131: ...HI 6600 Series Modular Sensor System User Guide Page 131 Image of HI 6610 Weight Processing Module II Diagram ...
Страница 132: ...HI 6600 Series Modular Sensor System User Guide Page 132 OptionalHI6110DisplayPanelMountingTemplate ...