SECTION 1   INTRODUCTION

Water contamination in an industrial ammonia refrigeration 
system can lower system efficiency, and increase the 
electrical costs required to run the system’s refrigeration 
compressors. Ammonia refrigerant that is contaminated 
with water requires a lower suction pressure to maintain 
the same evaporator temperature than would pure ammonia 
refrigerant. The requirement to maintain a lower suction 
pressure than would be necessary if the water contamination 
were removed is a waste of electrical energy. 

For water removal, the AUTO-PURGER Plus has the 

following capacities:

1% system water concentration – ½ gallon of water 

removed per week,

5% system water concentration – 1 gallon of water removed 

per day,

10% system water concentration – 3 gallons of water 

removed per day,

20% or more system water concentration – 5 gallons of 
water removed per day.

MATERIAL SPECIFICATIONS

Material of construction: steel, ASTM A53 Grade B, ASTM 

A106 Grade B, ASTM A234 Grade WPB, ASTM A105, 
ASTM A36

Safe working pressure: 400 psig (28 bar)
Operating temperature: -50F to +240F (-50C to +115C)
Internal volume: 0.7 cubic feet (20 liters)
Normal refrigerant inventory: 0.35 cubic feet (10 liters) 

TABLE OF CONTENTS

Section 1 Introduction…………………….............Page 1
Section 2 Installation……………….....................Page 2
Section 3 Component Description……..............Page 6
Section 4 Purger Operation……………...............Page 19
Section 5 Service, Troubleshoot, Parts…..........Page 22

The AUTO-PURGER Plus is a totally automatic, electronically 

controlled refrigerant noncondensible gas (air) and 
water purger for reducing the energy costs of operating 
an ammonia refrigeration system. All models are 
preassembled, pre-wired, insulated, and include an 
automatic water bubbler, a relief valve, and an isolation 
service valve package. Installation requires piping the foul 
gas line, low-pressure pumped-liquid line, low-pressure 

liquid return line, suction line, water bubbler fill and drain 
lines, relief valve vent line, water purge line to a customer 

supplied container, a power connection, and wiring the 
remote purge point solenoid valves. Purge point solenoid 
valves must be purchased separately and must be a 
minimum of ½” (13 mm) port size.

In addition to the APPT08, APPT16, and APPT24, a 
computerized model—APPTC—is available where a 
separate plant computer or programmable logic controller 
(PLC) is used to independently operate the various remote 
purge point solenoid valves.

The AUTO-PURGER Plus can operate over a wide range of 

condensing pressures. This is important for refrigeration 
systems that operate at low condensing pressures during 
cold ambient conditions.

The number of purgers required for a system depends on 

the number of installed purge points. Twenty-four purge 
points is the maximum practical number per purger. For 
example, a system with 24 points at 10 minutes per point 
requires a 240 minute (4 hour) cycle. Each purge point 
can be purged six times a day. If this is not adequate, 
a second purger should be used and the purge points 
divided equally between the two purgers.

In a system with normal noncondensible loads, all models 
will handle a 750 ton (2600 kW) ammonia plant at suction 
pressures below atmospheric pressure or a 1500 ton 
(5300 kW) ammonia plant at positive suction pressures. 

The amount of noncondensibles in the system is based 

on many factors including age, maintenance practices, 
and operating temperature.

.

Содержание APPT08

Страница 1: ...igerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are preassembled pre wired insulated and include an automatic wate...

Страница 2: ...nces only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to be liquid...

Страница 3: ...pressor discharge main inlet Vertical condensers should be purged near the top of the vessel if possible For certain types of oil separators where very low velocities may exist near the top of the ves...

Страница 4: ...quid ammonia that typically is also contaminated with water which is to be removed by the AUTO PURGER Plus The liquid line solenoid valve B on the AUTO PURGER Plus closes when the AUTO PURGER Plus is...

Страница 5: ...ions to prevent injury or property damage ELECTRICAL CONNECTIONS The standard AUTO PURGER Plus requires a 115V 50 60Hz 17 amp electrical supply on a 20 amp circuit breaker models for 220V 50 60Hz 11 a...

Страница 6: ...iquid drainer separates any liquid condensed in the purge point piping This liquid is fed to the low pressure liquid return line Therefore only foul gas no liquid enters the condensing section of the...

Страница 7: ...d solenoid valve B to maintain the ammonia level in the evaporator shell b The low liquid level sensor prevents the electric heaters from energizing if no liquid is present which protects the heaters...

Страница 8: ...lso used to exit back through menu mode Navigate up Navigate down ENTER To enter a speci c menu hierarchy or enter a parameter change Auto Purger Plus Technology Package Color Touchscreen Figure 6 O A...

Страница 9: ...units for the display readout To change the selec on press or to switch the units Menu Screen 1 Air Purge Limit Purge Point Enable Water Collec on Display Units Air Purge Limit APPT can limit the amo...

Страница 10: ...ctory con gured set up parameters Consult Hansen prior to aPemp ng to change parameters Menu Screen 2 Version Language Alarm History Setup Screen Version This menu contains information which can t be...

Страница 11: ...hscreen as well as the color touchscreen but the touchscreen must be set to HMI Display Troubleshoo ng Help This menu allows the user to scroll through the error code messages for the APPT and read th...

Страница 12: ...n the APPT are reading The units displayed will match what is selected in Menu Screen 1 Display Units Status Screen 1 Status Screen 2 Status Screen 3 STATUS SCREENS FOR APPT O Status screen 1 will pro...

Страница 13: ...to give the Water Concentra on percentage Status Screen 4 Status Screen 5 Status Screen 6 O Status Screen 4 will provide the high side and low side pressure as recorded from the pressure transducers...

Страница 14: ...7 provides the state of the level sensors and the oat switch O Status Screen 8 will provide the opera ng mode the purger is in and the ac ve purge point not applicable for APPC model Status Screen 7 S...

Страница 15: ...he System Reset key has been pressed or power is cycled to the APPT while the Liquid Make Up Level Sensor is reading wet APPT will stay in this mode un l Liquid make Up Level Sensor goes dry This prev...

Страница 16: ...ra ng water mode to indicate the temperature of the ammonia water solu on units will match the selected display units O READY TO DRAIN WATER OPEN WATER PURGE SHUT OFF VALVE THEN PRESS OK KEY appears w...

Страница 17: ...ome to the screen below O nabled will stop the APPT from collec ng and saving the data to your storage device To remove the press the Remove Storage Device buPon When the dot turns green remove your a...

Страница 18: ...e accessed in two ways Menu Screen 3 has an op on for Troubleshoo ng Help Pressing this op on will bring you to the menu below where you can select which error condi on you are looking for O O The sec...

Страница 19: ...nutes as detected by the water concentration sensor the AUTO PURGER Plus switches to the CONCENTRATING WATER mode The purger stops collecting air isolates the mixture of water and ammonia and energize...

Страница 20: ...ASSEMBLY CHAMBER HIGH SIDE TO LOW SIDE BYPASS VALVE NORMALLY CLOSED WITH ORIFICE PURGE VALVE WATER PURGE LINE SHUT OFF VALVE NO ORIFICE WATER PURGE LINE STRAINER NO ORIFICE FOUL GAS LINE LOW PRESSURE...

Страница 21: ...n 10 psig 0 7 bar as detected by the low side pressure transducer the low side pressure assist solenoid valve F modulates to maintain 10 psig 0 7 bar in the evaporator chamber The concentrated water c...

Страница 22: ...ill inhibit the water concentration mode of the purger The following components must be checked when the refrigerant oil is manually drained 1 Low liquid level sensor SPSN 1 2 Liquid level make up sen...

Страница 23: ...ion line and shut off valves These should be a minimum size of On new installations also make sure the plastic shipping cap in suction line flange is removed Action Eliminate the restriction See also...

Страница 24: ...Oil in purger Symptom No frost around the low side oil drain valve Action Remove oil through both the low side and high side drain valves See Figure 1 per safe refrigeration procedures See also the Ca...

Страница 25: ...C Check Reconnect the PLC module s for the purge point solenoid coils Press the PURGE POINT ADV button to sequence through each purge point and verify the fuse does not blow If the fuse does blow that...

Страница 26: ...Add vinegar to the bubbler water Then clean with the supplied brush Use a water conditioning housing and cartridge in the water supply line to the purger Refer to drawing 2003 07 for additional instru...

Страница 27: ...enoid C D 70 1102 Kit Green Beacon Light solenoid B E F G ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50...

Страница 28: ...kW system or a 750 ton 2638 kW systemoperating below 0 psig 0bar g All models suitable for ammonia only SELECTING AN AUTO PURGER In addition to the AUTO PURGER AP Hansen Technologies offers three oth...

Отзывы: