2.0 OPERATION
2.1 Minimum/Maximum operating conditions
A.
Maximum inlet air pressure: refer to dryer serial number tag
B.
Minimum inlet air pressure: 30 psig (2.1 kgf/cm
2
)
C.
Maximum inlet air temperature: 120°F (49°C)
D.
Maximum ambient temperature:
Air-cooled models: 110°F (43°C)
Water-cooled models: 130°F (54°C)
E.
Minimum ambient temperature: 45°F (7°C)
2.2 Start-up
A.
Energize dryer. Green power on light will illuminate.
IMPORTANT: Energize dryer disconnect switch (provided
by others, sec NEC) 24 hours before refrigeration com-
pressor is started! Never use the disconnect switch to
shutdown the dryer for a extended period of time (except
for repair). Failure to follow these instructions may result in
a non-warrantable compressor failure.
NOTE: If there is no power to the control board for a
period of two weeks or more, it may return to the default
mode.
B.
Program Monitor
Press and hold Program Mode button until Main Menu screen
appears. Use the Up and Down arrow buttons to scroll through
the list of submenu choices. Press Enter button to view the
submenu that is displayed. Press ESC to exit the Main Menu
and return to Display mode.
1.
Language selection
a. Use the ‘Up’ and ‘Down’ arrow buttons to scroll through
the list of languages (choice of 10 available: English,
Deutsch, Francais, Espanol, Italiano, Polski, Dansk,
Dutch, Norsk and Suomi).
b. Press ‘Enter’ button to select the language that is
displayed.
c. Push ‘ESC’ at any time to return to the Main Menu.
2.
Setting Date & Time
a. Use the ‘Up’ and ‘Down’ arrow buttons to set minutes
(00 to 59). Press ‘Enter’ to accept new value.
b. Use the ‘Up’ and ‘Down’ arrow buttons to set hours (00
to 23). Press ‘Enter’ to accept new value.
c. Use the ‘Up’ and ‘Down’ arrow buttons to set year (00 to
99 representing 2000 to 2099). Press ‘Enter’ to accept
new value.
d. Use the ‘Up’ and ‘Down’ arrow buttons to set month
(three letter abbreviation). Press ‘Enter’ to accept new
value.
e. Use the ‘Up’ and ‘Down’ arrow buttons to set day (01 to
maximum for the month and year selected). Press
‘Enter’ to accept new value.
f.
Push ‘ESC’ at any time to return to the Main Menu.
C
S
E
1
2
3
4
5
6
7
8
9
10
11
12
1.
Temperature Indicator
2.
Operator Interface Display
3.
Power-on Light
4.
Compressor-on Light
5.
Alarm / Service Light
6.
Schedule On/Off and Enter Button
a. In display mode: Press to toggle between
SCHEDULE RUNNING and MANUAL OVERRIDE.
b. In program mode:
i.
Press to move to a lower level menu.
ii. Press to accept a value that has been edited.
7.
Program Mode (i) and Esc
a. In display mode: Press and hold to enter program
mode.
b. In program mode: Press to move to a higher level
menu.
8.
Up Arrow
a. In display mode: No function
b. In program mode:
i.
Press to view the next item in a list or to
increment a variable to a higher value. Press
and hold for accelerated incrementing.
ii. When the top of the list (or highest value) is
displayed, pressing the up button will cause
the display to wrap to the bottom of the list (or
lowest value).
9.
Down Arrow
a. In display mode: No function
b. In program mode:
i.
Press to view the previous item in a list or to
increment a variable to a lower value. Press
and hold for accelerated incrementing.
ii. When the bottom of the list (or lowest value) is
displayed, pressing the down button will cause
the display to wrap to the top of the list (or
highest value).
10. 1/0: Press at any time to turn the dryer on/off.
11. Drain test: Press at any time to momentarily the open
drains (like the current emm).
12. Reset: Press at any time to clear the alarm/service
message (if shown) and the alarm LED.
CONTROL PANEL