background image

16

A) Water downstream of dryer

B) High pressure drop across dryer

C) Checkpoint faults

1. Power on light off
2. Compressor on light off

3. Alarm/Service alert light on - check

Display for active conditions
SERVICE DRYER

LOW PRESSURE

HIGH PRESSURE
NOTE: If high refrigerant pressure
occurs, switch must be manually reset

HIGH TEMPERATURE
(also observed as high reading on
temperature indicator)

DRAIN

COMPRESSOR

HEATER

TEMP SENSOR

TROUBLESHOOTING GUIDE

1. Residual free moisture remaining in

downstream pipelines

2. Air bypass system is open
3. Inlet and Outlet connections are reversed
4. Air lines downstream of dryer are exposed to

temperatures below the dew point.

5. Excessive free moisture (bulk liquid) at dryer

inlet

6. Condensate not being drained
7. Dryer overloaded resulting in elevated dew

point.

8. Refrigeration system not  functioning

1. Excessive air flow
2. Freezing of moisture in evaporator because

of refrigeration system fault

3. Filter loaded with solid particulates

a. Power failure; open circuit
a. Compressor commanded off by manual

switch or programmed schedule

b. Open circuit
c. Control circuit open on high or low pressure

cutout

Service interval specified has elapsed

a. Hot gas bypass valve requires adjustment
b. Low on refrigerant

a. Lack of condenser cooling

Air-cooled - Ambient temperature too high,
clogged condenser fins, obstructed flow
across condenser, faulty fan motor or fan
control switch.

Water-cooled - Cooling temperature too
high, flow too low, clogged strainer, faulty
water regulating valve

a. Dryer overloaded

b. Refrigeration system off or not cooling

sufficiently

a. Drain line restricted or frozen
b. Drain mechanism faulty

a. Faulty compressor contactor.
b. Faulty N.O. auxiliary contact on compressor

contactor.

a. Faulty compressor contactor.
b. Faulty N.C. auxiliary contact on compressor

contactor.

a. Temperature sensor or wiring to sensor is

open (only the left-most LED in the tempera-
ture display will be illuminated).

b. Temperature sensor or wiring to sensor is

shorted (all of the LEDs in the temperature
display will be illuminated).

1. Blow out system with dry air

2. Check valve positions
3. Check for correct connection
4. Insulate or heat trace air lines exposed to

low ambients or dry air to lower dew point

5. Install separator ahead of dryer

6. See C below
7. See C below

8. See C below

1. Check flow rate
2. See C below

3. Replace filter element

a. Check for power to dryer
a. Check current command status

b. Check power to compressor
c. Check display for fault

Perform scheduled service

a. Contact qualified technician or

manufacturer’s service department

Check air temperature 6” in front of
condenser; Clean condenser and check
for free air flow;

Check fan and

switch operation

Check cooling medium temperature and
flow, clean strainer, check valve operation

a. Check compressed air flow, temperature,

and pressure

b. Check power to unit, power to compres-

sor, Low or High pressure faults. Have
qualified technician evaluate system

a. Open drain line
b Turn 3-way valve handle so it points out

from the front of the unit. Open and
adjust the manual petcock in rear leg for
manual draining.  Rebuild drain mecha-
nism.

a. Check wiring and operation of contactor.
b. Check wiring and operation of auxiliary

contact.

a. Check wiring and operation of contactor.
b. Check wiring and operation of auxiliary

contact.

a. Replace sensor or repair wiring.

b. Replace sensor or repair wiring.

 SYMPTOM

POSSIBLE CAUSE(S)

         CORRECTIVE ACTION

NOTE:  After fault correction, press reset button to clear display

Содержание HPRP 1000

Страница 1: ...MAINTENANCE 8 SIZING 9 ELECTRICAL SCHEMATICS 10 DIMENSIONS AND WEIGHT 14 ENGINEERING DATA 15 TROUBLESHOOTING GUIDE 16 PARTS LIST AIR COOLED UNITS 17 PARTS LIST WATER COOLED UNITS 18 WARRANTY 20 SERVI...

Страница 2: ...weather Damage to electrical and control components may result IMPORTANT WATER COOLED UNITS If unit is shut down below freezing temperatures the water cooled condenser may freeze and cause permanent d...

Страница 3: ...ntilated area Avoid locations immediately adjacent to cold exterior windows or walls or adjacent to high tem perature ovens or boilers D Clearances Free air flow Models 1000 to 1500 Front 24 inches 61...

Страница 4: ...At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the moisture s...

Страница 5: ...c Use the Up and Down arrow buttons to set year 00 to 99 representing 2000 to 2099 Press Enter to accept new value d Use the Up and Down arrow buttons to set month three letter abbreviation Press Ent...

Страница 6: ...slowly 5 Close air bypass valve 6 Dryer may be operated in Manual or scheduled modes NOTE Check for correct phasing of unit On air cooled models check fan rotation air must be pulled through the conde...

Страница 7: ...to discharge f Check drain operation push Drain push to test button to energize electric drain A flow of condensate and or air should be present at the drain outlet E Using the RS 232 port The RS 232...

Страница 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Страница 9: ...INLET INLET TEMPERATURES PRESSURES 80 F 90 F 100 F 110 F 120 F psig kgf cm2 27 C 32 C 38 C 43 C 49 C 50 3 5 1 35 1 05 0 84 0 69 0 56 80 5 6 1 50 1 17 0 95 0 79 0 66 100 7 0 1 55 1 23 1 00 0 82 0 70 12...

Страница 10: ...OR SPECIFIC WIRING INFORMATION 3 SCROLL COMPRESSORS REQUIRE PROPER PHASING SEE COMPRESSOR DATA PLATE FOR CORRECT WIRING SEQUENCE 4 WIRES 55 AND 56 ARE JUMPERED TOGETHER ON STANDARD DRAIN PKG COMPRESSO...

Страница 11: ...AND FAN THERMAL OVERLOADS ARE REMOVED 2 SEE FAN NAMEPLATE FOR SPECIFIC WIRING INFORMATION 3 SCROLL COMPRESSORS REQUIRE PROPER PHASING SEE COMPRESSOR DATA PLATE FOR CORRECT WIRING SEQUENCE 4 WIRES 55 A...

Страница 12: ...RING INFORMATION 3 SCROLL COMPRESSORS REQUIRE PROPER PHASING SEE COMPRESSOR DATA PLATE FOR CORRECT WIRING SEQUENCE 4 WIRES 55 AND 56 ARE JUMPERED TOGETHER ON STANDARD DRAIN PKG FAN1 NOTE 1 2 FAN3 2000...

Страница 13: ...9 10 11 20 21 19 16 17 18 34 35 15 TB2 TC TC 15 16 17 18 20 21 9 10 11 12 13 14 26 27 28 FILTER MONITOR COALESCING RJ 11 FILTER MONITOR RJ 11 WEB MONITOR RS232 PORT LOCAL REMOTE REMOTE STOP START CUST...

Страница 14: ...1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 85 2159 54 1372 56 1422 2 100 953 2500 6 2 238 1015 3000 6 2 263 1027 NOTE Dimension and weights are for reference on...

Страница 15: ...98 130 125 150 175 Minimum Circuit Ampacity 16 73 17 42 19 30 28 17 28 44 27 53 32 41 Branch Circuit Fuse Size amps 25 25 30 45 45 45 50 Watts 35 F Evaporator 100 F Ambient 7 850 9 223 9 777 12 621 10...

Страница 16: ...y a Faulty compressor contactor b Faulty N O auxiliary contact on compressor contactor a Faulty compressor contactor b Faulty N C auxiliary contact on compressor contactor a Temperature sensor or wiri...

Страница 17: ...1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 h c t i w S e r u s s e r P t n a r e g i r f e R h g i H 8 2 8 3 1 0 3 1 4 8 2 8 3 1 0...

Страница 18: ...L 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 1 3 8 3 1 0 3 1 4 h c t i w S e r u s s e r P t n a r e g i r f e R h g i H 5 3 8 3 1 0 3...

Страница 19: ...19 NOTES...

Страница 20: ...product or part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE I...

Отзывы: