69
Vol. 2.6 © 2020 Hanbell Precise Machinery Co., Ltd. All rights reserved
Figure 5.3 Protection terminal plates.
Specifications: Pt100 sensor
Recommended max. meas. Current for heat coefficient <0.1K – DC1 ~ 3 mA
Heating coefficient - 10m
Ω
/K
Sensor resistance at 0
℃
- 100
Ω
±
0.12
Ω
Change of resistance 0 ~ 100
℃
- 0.385
Ω
/K
Insulation test voltage U is – AC 1.5kV
Figure 5.4Pt100 sensor
Specifications: Pt1000 sensor
Recommended max. meas. Current for heat coefficient < 0.1K –DC0.2 ~ 2mA
Sensor resistance at 0
℃
- 1000
Ω
±
1.20
Ω
Change of resistance 0 ~ 100
℃
- 3.85
Ω
/K
Insulation test voltage U is – AC 1.5kV
Figure 5.5 Pt1000 sensor
1.
Please specify Pt100 or Pt1000 sensors when placing orders to Hanbell. In
addition, all models can be equipped with Pt100 or Pt1000 sensors to precisely
measure motor coil temperatures for control of motor cooling.