5.4 Compressor Electrical and Safety Practices
5.4.1 Electrical Safety Precautions:
1.
Once connected to the compressor, the power supply of the voltage would get
very dangerous. Only qualified electricians and electrical engineers are allowed to
the work installation. It shall be in strict accordance with the manual operation of
the program as well as national regulations and safety codes before installation.
2.
Users and installers shall be in accordance with the National Electrical Code as
standard to provide grounding and install a protective circuit.
3.
Before performing any maintenance operation, make sure the power switch is
turned off to avoid accidents.
4.
Before normal operation of the compressor or unacknowledged power is off, do
not open the compressor terminal box to avoid danger.
5.
After confirming the direction of rotation of the motor while the terminal without
insulation protection, make sure to stay away from the compressor and
assembling unit, to avoid the risk of electric shock.
6.
When doing compressor maintenance work, inspection or parts replacement, it is
a must to cut off the main power supply to the terminal discharge in order to avoid
the risk of electric shock.
5.4.2 The Inspection and Preparation before Electrical Wiring
5.4.2.1 Inspection of Unpacking
1.
All compressors have been passed the strict test by Hanbell. Users are
unauthorized to disassemble to inspection, if necessary, please contact Hanbell
Company.
2.
Check the motor terminal box of compressor firstly when unpacking if there is
damage, collision or deformation.
3.
After first or a long time running, when compress start-up, it must uses DC2500V
meg - ohmmeter to measure motor terminal box of the main terminal and the chamber
cold insulation resistance test, the insulation value shall not less than the value
determined by the formula as followed.
In the formula: R
―
Motor Winding Insulation of Resistance (M
Ω
)
UN
―
Rated Insulation Voltage (V)
PN
―
Motor Power Rating (KW)
When the motor is damp or the insulation resistance is lower than the calculated values, it
shall take action of drying motor stator, drying temperature must not exceed 120
℃
.
NOTE: Hanbell compressor has been test passed by national standards withstanding
voltage testing. Users and installation contactor are not allowed to do the testing. If
necessary, please contact with Hanbell Company.