background image

   

              

          User Manual RDx-xxxDT-10.31 

 

 

Page 5 of 8

                                                                                                                                      

www.hanbayinc.com | 1 800 315 4461        

Rev.2020.4                                                                                                                                                                                               

 

[email protected] 

Functionality of the RDx-xxxDT: 
 

The RDx can operate as a 3-position or 4-position actuator. The 4

th

 position is enabled by turning Dip 8 ON. 

 

3-pos Functionality (Dip 8 OFF) 

 

Input#1 

(Pin 1) 

Input#2 

(Pin 2) 

Action taken 

High 

High 

Moves to or remains in center position 

Low 

High 

Moves to or remains in right position 

High 

Low 

Moves to or remains in left position 

Low 

Low 

Moves to or remains in right position (Input#1 has 
precedence over Input #2) 

 

The feedback from the RDx-xxxDT is as follows: 

Output#1 

(Pin 3) 

Output#2 

(Pin 4) 

Meaning   

High = 4.5vDC   Low = 0.8vDC 

High 

High 

Actuator output is in center position 

High 

Low 

In Right position  

Low 

High 

In Left position  

Low 

Low 

Actuator is moving, or has stalled and given up trying to 
reach a requested position. 
You may retry to reach any position by cycling alternate 
inputs and trying the original again. Repeated failures to 
reach the position will require troubleshooting. 

 
4-pos Functionality (Dip 8 ON) 
 

Input#1 

(Pin 1) 

Input#2 

(Pin 2) 

Action taken 

High 

High 

Moves to or remains in center position 

Low 

High 

Moves to or remains in right position 

High 

Low 

Moves to or remains in left position 

Low 

Low 

Moves to or remains in back position 

 

 

 

The feedback from the RDx-xxxDT is as follows: 

Output#1 

(Pin 3) 

Output#2 

(Pin 4) 

Meaning   

High = 4.5vDC   Low = 0.8vDC

 

Low 

Low 

Actuator is at requested position  

High 

Low 

Actuator is moving  

Low 

High 

Actuator has stalled. The stall can be cleared by making 
the actuator turn in the other direction. 

 

Direction of rotation and using Input 1 
 

To change the direction of rotation on the actuator change the setting on Dip12 and power up the actuator again. 
 
 

 

VERY IMPORTANT:

 Input 1 must always be used if only one input is used to operate the valve. 

When the actuator is operated using input 1 an automatic calibration is done every time the valve 
is actuated. This does not happen on input 2. 

 
 

Right 

Top View 

onto valve or 

other 

appliance 

Center 

Back 

Left 

Top View 

onto valve or 

other 

appliance 

Center 

 

Right 

Left 

Содержание RD-DT-10.31 Series

Страница 1: ...iring pg 2 Connecting power and signal pg 3 Manual override pg 3 Operation pg 4 6 DIP Switch settings pg 4 Functionality pg 5 Torque Settings pg 6 Appendix pg 6 7 Calibration pg 6 Trouble shooting pg 6 Dimensions pg 7 Factory Presets pg 8 Installation Mounting Holes for a mounting bracket Holes are threaded for 20 and are approximately 275 deep For dimensions see page 7 ...

Страница 2: ...g Cut the cable to the length required and then connect according to the following wire color schematic Wire color schematic for Turck 6 cable Pin Color DC power supply only 6 White 24VDC 5 Black Power Gnd 4 Pink Output TTL2 3 Grey Output TTL1 2 Blue Input TTL2 1 Brown Input TTL1 Connect the power The RDx xxxDT may be connected to voltages ranging from 12 24 VDC The power consumption will range fr...

Страница 3: ...nput 1 TTL I O Signals Input 2 Output 2 Output 1 USER SUPPLIED GND GND 2 1 1 2 RL max drive current 2mA External I O device supplied by user 1mA RDx RDx series with manual override The actuator is certified for hazardous locations The additional manual override gear case and handle do not require a certification Operation of the manual override when power is applied will be difficult as the actuat...

Страница 4: ...lly 3 DIP 8 With DIP switch 8 in the ON position the actuator will move to 4 positions It will also alter the function of the output signals In the OFF position the actuator is limited to three positions DIP 9 Run Calibrate Putting DIP switch 9 into the OFF position will disable the actuator positioning control and the motor will not move regardless of the input signals When DIP 9 is moved back in...

Страница 5: ...riginal again Repeated failures to reach the position will require troubleshooting 4 pos Functionality Dip 8 ON Input 1 Pin 1 Input 2 Pin 2 Action taken High High Moves to or remains in center position Low High Moves to or remains in right position High Low Moves to or remains in left position Low Low Moves to or remains in back position The feedback from the RDx xxxDT is as follows Output 1 Pin 3...

Страница 6: ... if the actuators output gear gets manually rotated while the actuator is powered down and can t properly realign to the center by itself Troubleshooting Upon noticing a problem your first step should almost always be to recalibrate the actuator by switching DIP 9 on then off all while the actuator is powered This alone can solve basic problems See section 3 on this page for more details If the ac...

Страница 7: ... 1 800 315 4461 Rev 2020 4 hanbaysales hanbayinc com Main Dimensions RxL RxM RxH Desiccant sticks These sticks change colour when exposed to moisture When they change from the original color blue to pink the actuator has been exposed to an excess of moisture ...

Страница 8: ...User Manual RDx xxxDT 10 31 Page 8 of 8 www hanbayinc com 1 800 315 4461 Rev 2020 4 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number ...

Отзывы: