Connect the signal: 

 

Locate the correct connection terminals as shown on the previous page, then connect your input signal on  
pos. 1 and 2 as shown below. Feedback, if applicable is connected to positions 3 and 4. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 

 
 

 

1   2  3   4  5   6  

 

P1

 

Input #1

 

TTL I/O Signals

 

Input #2

 

Output #2

 

Output #1

 

USER SUPPLIED

 

GND

 

GND

 

2

 

1

 

1

 

2

 

RL 
(max drive 
current 
2mA)

 

External 
I/O device 
supplied 
by user 
 < 1mA

 

RDx

 

 

RDx series with manual override 

 
The actuator is certified for hazardous 
locations. 
The additional manual override gear case 
and handle do not require a certification. 
 
Operation of the manual override when 
power is applied will be difficult as the 
actuator will try to maintain the valve in 
the position it has been commanded to. 
Power should be removed if the valve is 
to be moved manually. 

Содержание RD-DT-10.31 Series

Страница 1: ...iring pg 2 Connecting power and signal pg 3 Manual override pg 3 Operation pg 4 6 DIP Switch settings pg 4 Functionality pg 5 Torque Settings pg 6 Appendix pg 6 7 Calibration pg 6 Trouble shooting pg 6 Dimensions pg 7 Factory Presets pg 8 Installation Mounting Holes for a mounting bracket Holes are threaded for 20 and are approximately 275 deep For dimensions see page 7 ...

Страница 2: ...g Cut the cable to the length required and then connect according to the following wire color schematic Wire color schematic for Turck 6 cable Pin Color DC power supply only 6 White 24VDC 5 Black Power Gnd 4 Pink Output TTL2 3 Grey Output TTL1 2 Blue Input TTL2 1 Brown Input TTL1 Connect the power The RDx xxxDT may be connected to voltages ranging from 12 24 VDC The power consumption will range fr...

Страница 3: ...nput 1 TTL I O Signals Input 2 Output 2 Output 1 USER SUPPLIED GND GND 2 1 1 2 RL max drive current 2mA External I O device supplied by user 1mA RDx RDx series with manual override The actuator is certified for hazardous locations The additional manual override gear case and handle do not require a certification Operation of the manual override when power is applied will be difficult as the actuat...

Страница 4: ...lly 3 DIP 8 With DIP switch 8 in the ON position the actuator will move to 4 positions It will also alter the function of the output signals In the OFF position the actuator is limited to three positions DIP 9 Run Calibrate Putting DIP switch 9 into the OFF position will disable the actuator positioning control and the motor will not move regardless of the input signals When DIP 9 is moved back in...

Страница 5: ...riginal again Repeated failures to reach the position will require troubleshooting 4 pos Functionality Dip 8 ON Input 1 Pin 1 Input 2 Pin 2 Action taken High High Moves to or remains in center position Low High Moves to or remains in right position High Low Moves to or remains in left position Low Low Moves to or remains in back position The feedback from the RDx xxxDT is as follows Output 1 Pin 3...

Страница 6: ... if the actuators output gear gets manually rotated while the actuator is powered down and can t properly realign to the center by itself Troubleshooting Upon noticing a problem your first step should almost always be to recalibrate the actuator by switching DIP 9 on then off all while the actuator is powered This alone can solve basic problems See section 3 on this page for more details If the ac...

Страница 7: ... 1 800 315 4461 Rev 2020 4 hanbaysales hanbayinc com Main Dimensions RxL RxM RxH Desiccant sticks These sticks change colour when exposed to moisture When they change from the original color blue to pink the actuator has been exposed to an excess of moisture ...

Страница 8: ...User Manual RDx xxxDT 10 31 Page 8 of 8 www hanbayinc com 1 800 315 4461 Rev 2020 4 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number ...

Отзывы: