User Manual RDx-xxxDT-10.31
Page 2 of 8
www.hanbayinc.com | 1 800 315 4461
Turck connector not included
in the Class 1, Div 1 Groups
B, C & D rated explosion
proof enclosures.
Appropriate rated cable
glands or conduit should be
installed by qualified
personnel in accordance with
site requirements.
Wiring:
The actuator comes standard with a Turck 6 position connector
and a 20’ cable with plug. Cut the cable to the
length required and then connect according to the following wire color schematic:
Wire color schematic for
“Turck 6” cable:
Pin
Color
DC power supply only
6
White
+24VDC
5
Black
Power Gnd
4
Pink
Output TTL2
3
Grey
Output TTL1
2
Blue
Input TTL2
1
Brown
Input TTL1
Connect the power:
The
RDx-xxxDT
may be connected to voltages ranging from:
12
– 24 VDC.
The power consumption will range from max. 3.0A to approx. min.100mA
when the actuator is active. When not moving, the actuator draws around
50mA.
Terminal
1 2 3 4 5 6
GND
V+
DC Voltages
1 2 3 4 5 6
P1
*For non-explosion proof R-Series
Turck connector/cable pinout