background image

   

              

          User Manual RDx-xxxDT-10.31 

 

 

Page 2 of 8

                                                                                                                                      

www.hanbayinc.com | 1 800 315 4461        

Rev.2020.4                                                                                                                                                                                               

 

[email protected] 

Turck connector not included 
in the Class 1, Div 1 Groups 
B, C & D rated explosion 
proof enclosures. 
Appropriate rated cable 
glands or conduit should be 
installed by qualified 
personnel in accordance with 
site requirements. 

Wiring: 

 
The actuator comes standard with a Turck 6 position connector 

and a 20’ cable with plug. Cut the cable to the 

length required and then connect according to the following wire color schematic:  
 

Wire color schematic for 

“Turck 6” cable:

 

 

 

 
 
 
 

 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 

Pin 

Color 

DC power supply only 

White 

+24VDC 

Black 

Power Gnd 

Pink 

Output TTL2 

Grey 

Output TTL1 

Blue 

Input TTL2 

Brown 

Input TTL1 

 

 

Connect the power:  

 

The 

RDx-xxxDT

 may be connected to voltages ranging from:   

12 

– 24 VDC.  

 
The power consumption will range from max. 3.0A to approx. min.100mA 
when the actuator is active. When not moving, the actuator draws around 
50mA.  
 

 
 
 
 
 

 

  Terminal  

1 2 3 4 5 6  

GND

 

V+

 

DC Voltages

 

   1   2   3   4   5   6   

 

P1

 

*For non-explosion proof R-Series 

 
 
 

 

 
 

 

Turck connector/cable pinout 

 

Содержание RD-DT-10.31 Series

Страница 1: ...iring pg 2 Connecting power and signal pg 3 Manual override pg 3 Operation pg 4 6 DIP Switch settings pg 4 Functionality pg 5 Torque Settings pg 6 Appendix pg 6 7 Calibration pg 6 Trouble shooting pg 6 Dimensions pg 7 Factory Presets pg 8 Installation Mounting Holes for a mounting bracket Holes are threaded for 20 and are approximately 275 deep For dimensions see page 7 ...

Страница 2: ...g Cut the cable to the length required and then connect according to the following wire color schematic Wire color schematic for Turck 6 cable Pin Color DC power supply only 6 White 24VDC 5 Black Power Gnd 4 Pink Output TTL2 3 Grey Output TTL1 2 Blue Input TTL2 1 Brown Input TTL1 Connect the power The RDx xxxDT may be connected to voltages ranging from 12 24 VDC The power consumption will range fr...

Страница 3: ...nput 1 TTL I O Signals Input 2 Output 2 Output 1 USER SUPPLIED GND GND 2 1 1 2 RL max drive current 2mA External I O device supplied by user 1mA RDx RDx series with manual override The actuator is certified for hazardous locations The additional manual override gear case and handle do not require a certification Operation of the manual override when power is applied will be difficult as the actuat...

Страница 4: ...lly 3 DIP 8 With DIP switch 8 in the ON position the actuator will move to 4 positions It will also alter the function of the output signals In the OFF position the actuator is limited to three positions DIP 9 Run Calibrate Putting DIP switch 9 into the OFF position will disable the actuator positioning control and the motor will not move regardless of the input signals When DIP 9 is moved back in...

Страница 5: ...riginal again Repeated failures to reach the position will require troubleshooting 4 pos Functionality Dip 8 ON Input 1 Pin 1 Input 2 Pin 2 Action taken High High Moves to or remains in center position Low High Moves to or remains in right position High Low Moves to or remains in left position Low Low Moves to or remains in back position The feedback from the RDx xxxDT is as follows Output 1 Pin 3...

Страница 6: ... if the actuators output gear gets manually rotated while the actuator is powered down and can t properly realign to the center by itself Troubleshooting Upon noticing a problem your first step should almost always be to recalibrate the actuator by switching DIP 9 on then off all while the actuator is powered This alone can solve basic problems See section 3 on this page for more details If the ac...

Страница 7: ... 1 800 315 4461 Rev 2020 4 hanbaysales hanbayinc com Main Dimensions RxL RxM RxH Desiccant sticks These sticks change colour when exposed to moisture When they change from the original color blue to pink the actuator has been exposed to an excess of moisture ...

Страница 8: ...User Manual RDx xxxDT 10 31 Page 8 of 8 www hanbayinc com 1 800 315 4461 Rev 2020 4 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number ...